6500 Series Control Head w/ XD10 Controller Standard Turnstile Testing
The XD10 logic controller on the 6500 Series Control Head can be activated by contact closures
between 24VDC+ and the relevant input. New technology allows for simpler on-board testing
as well. To diagnose issues with the unit, press A on the keypad to cycle between screens until
the testing mode screen appears.
other menu screens. The unit should unlock for the duration of the directional timer or until
the unit is rotated. If the button is pressed twice, it should allow two rotations or time out
based on the mult-swipe setting. If the button is held and the one shot timers are disabled,
the unit will continue to remain open until the button is released and another rotation or
timeout occurs.
With the testing mode screen open, press and r to activate in direction 1. The unit
should unlock and allow one rotation. If the unit successfully functions this way, repeat the
same for direction 2 by pressing the - button.
If everything is functioning properly from the menu test but not with access control, either
access control is not connected properly, is normally closed instead of normally open, or is
access control system.
If the unit successful unlocks but does not re-lock upon rotation, try to manually trigger
the appropriate limit switch for the direction that is not working correctly. If this helps, it
is likely that the limit switch is not properly being triggered by the limit switch cam. Either
adjust the height of the limit switch cam or tweak the lever on the limit switch a bit closer
to the limit switch cam’s tip.
If the unit does not successfully re-lock after manually triggering the limit switch, ensure
that it is wired properly. Return to the home screen and press / hold the limit switch. If the
switch is being held but the “Active Pins” display does not include the switch being held, it
may be necessary to replace the switch. Note that there is a short delay from when the
switch is triggered to when the display will register it as active, however this is normal.
If there are other issues with operation, check out the troubleshooting guide for additional
diagnostic procedures or call Designed Security, Inc. for assistance.
512-321-4426
INS-DS100R-190401
Designed Security, Inc. - 1402 Hawthorne Street, Bastrop Texas 78602 - (800) 272-3555
sales@dsigo.com
21