104889 Page 5
STEP 8:
NOT FOR USE ON EAX-300W
Multi-door & SK function wiring connection
(if required).
1-1/2
8a: Remove board
1"
Recommended hole size:
Drill 7/8 dia, (1) place
Common
Terminal
Closed
Diagram shown typical for two door magnetic switches:
MS-1039S & MS-1059S wire in series.
MS-2049 (Red wire not used)
Weatherized not available for SK installations
Closed contact when
door is closed
NOTES:
1. If wire runs longer than 10 feet, must use twisted pair.
2. 1/16" slotted jeweler screwdriver required.
Disconnect power
& cut (JP1) jumper
Screw wires to (P1) terminal block
(18ga Max wire dia) (not available on weatherized)
Fitting or nut NOT included
(1/2" connector P/N PP-5107)
Common
Closed
Mag
Switch 1
Mag
Switch 2
Remove
(2) screws
8b: Drill hole
8c: Reassembly
8d: SK Wire connections
Applying a small amount
of lube to threads will aid
when removing the cover
in the future.
Hook at bottom, then tilt
cover over backplate
See instruction 103137 for magnetic
switch mounting procedure
STEP 9: INSTALL DEVICE
Turn key CW
to lock cover
CAUTION:
Do not over tighten