5.3- System Test
Before handling any other part of the system, please
verify the solenoid is disconnected from the bottle.
A quick test of the system can be performed as follows:
•
Create a fault, such as a loop open circuit or a power failure, and check that the fault
relay operates and the fault is indicated on the LEDs and LCD.
•
Cause an alarm to occur and check that the alarm relay outputs are activated and the
correct sounders operate (after the correct delay, if programmed).
•
Configure the system mode as MANUAL and AUTOMATIC , cause an alarm to occur
in Zone 1 and Zone 2, and check that all the extinction process is generated.
•
Configure the system mode as MANUAL and AUTOMATIC, cause an alam to occure
in Zone 1 and Zone 2, and check that the buttons STOP and ABORT work properly..
•
Configure the system mode as MANUAL and AUTOMATIC and check that if the
Manual triggering button is activated, it works as expected
Note: A power failure may take several minutes to be indicated.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...