Connecting/disconnecting the sounders output:
The sounders are connected and disconnected by using the sounder silence and
activation keys:
•
With the sounders connected and on standby, if you press the sounders silence key,
the sounders will be disconnected.
•
With the sounders disconnected, if you press the activate sounders key, the sounders
will be connected.
6.4.5- Test mode
This operation mode is designed for the maintenance of the installation. The unit is in
this mode when one of the zones is in test mode. This mode is indicated as follows:
•
General test indicator:
activated, blinking.
•
Active test zone indicators:
The indicator corresponding to the zone in test mode
will blink.
In this operation mode, any alarm caused in the test zone will be reflected in the unit
for 3 seconds. After this time the unit will automatically be reset.
Configuring the test mode:
A zone in test mode is configured by pressing the key of the zone you wish to put into
test mode. To take a zone out of test mode, do the following:
•
Press the button of the corresponding zone:
test mode is activated.
•
Press the general test button:
test mode is deactivated.
6.4.6- Out of service mode
The unit is out of service when there is no mains power supply and the batteries are
operating at below 22V. In this state the panel will not indicate any type of event that
may occur in the system; it will not detect alarms or faults. The indication that the unit
is out of service is the following:
•
General fault warning
activated intermittently.
•
Out of service warning
activated continuously.
•
Acoustic warning
activated continuously.
•
Fault output
activated.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...