32
GB
This state indicates that Zones 1 and 2 have entered the alarm setting, or the trigger
manual pushbutton has been activated. In this state the central carries out the following
actions:
•
Activated Mode indicator (second state).
•
Increase the output frecuency of the sounder output State 1:
2 Hz.
•
Sirens’ ON indicator State 2.
•
Sirens’ output activation State 2:
continuous tone.
•
Acoustic indicator:
continuously.
•
Display activation:
Shows the countdown until the triggering of the extinction,
(Display shows it intermittently).
This state can’t silence the state sirens, neither canceling the extinction block if the
process can be reseted( EN12094-1 requirement).
Once the activate mode is reached, the following actions can be carried out:
•
Activation of the manual external Pause push buttons:
For the Extinction process
meanwhile they’re pushed.
•
Activation of the manual external Stop push buttons:
Stops definitely the
extinction process.
6.6.4- Extinción Estado Disparado
This state indicates that the countdown initiated in the previous state has reached 0.
( This state could not be reached in case of fault in any of the stop or cancel manual
push buttons). In this state the following actions are carried out:
•
Acoustic indicator:
Continously sounding.
•
Triggered State indicator:
blinking
•
Activation output sounder state 1:
4Hz
•
Activation output sounder state 2: continuous tone.
•
Activation of the sing
“Do not enter, extinction triggered”.
•
On indicator of sign and bottle:
Fixed
•
Activation of the bottle exit :
Activation of the bottles’ solenoid.
•
Acoustic indicator active:
continuously.
•
Displays’ activation:
Shows 000 intermittently.
•
•
•
6.6.5- Triggering Ended Extinction State
Once the previous state is reached and the inundation time is over (progammable
timer, 60 seconds fabric setup).
The extinction process is finished.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...