background image

Figure 8: 1-stage thermostat, electric heating and air
conditionning

Figure 9: 2-stage thermostat, electric heating and air
conditioning

2.5.1

Anticipator adjustment (if required)
on thermostat equipped with heat
anticipator adjustment

Some thermostats are equipped with a heat anticipator
that must be adjusted according to the instructions
supplied.

This is to ensure that the heating mode is

comfortable and economical. Generally speaking, on a
single stage thermostat, a reading of the current must be
taken with an ammeter as follows:

1. Move the anticipator to its highest setting, rendering

it ineffective.

2. Remove the wire from the W1 terminal of the

furnace and connect an ammeter between the
terminal and the wire.

3. Call for heat by raising the set point on the

thermostat and allow the furnace to run for 3 to 4
minutes to reach its peak output.

4. Once the current has stabilized, a reading should

be taken and the anticipator adjusted to that value.
If longer heating cycles are desired, the anticipator
can be set to a higher value

2.5.2

Air ducts

The ducts must be sized such a way as to accommodate
the specified airflow and the available static pressure.
Refer to the applicable local and/or national installation
codes. Insulate the ducts that lead through non-heated
areas. Use flexible supply and return air connectors to
avoid the transmission of vibration. To make the unit run
even quieter, the installer should:

1. Use two elbows between each outlet and the

supply and return air plenum;

2. Cover the vertical sections of the supply and return

air duct with soundproofing material;

3. Use baffles in short radius elbows;

4. Use flexible hangers to suspend the ducts.

A heat pump or an air conditioner can be added to this
furnace, in either the supply or return air duct. Carefully
follow the instructions provided with these appliances to
ensure proper installation and hook-up to the electric
furnace. Refrigerant and drainage pipes must in no way
hinder access to the furnace panels.

2.6

SUPPLY AIR ADJUSTMENTS

The supply air must be adjusted based on heating/air
conditioning output and the static pressure of the duct
system. For the desired airflow, refer to Table 1, as well
as Table 4 and Table 5 for the airflow based on static
pressure.
For the adjustment of the airflow on heating mode, to
obtain the temperature rise described in the technical
specification table Table 2 and Table 3), the orange wire
must be positioned on the terminal corresponding to the
LOW, MED-LOW, MED-HIGH or HIGH blower speed.
For the adjustment of the airflow on air-cooling mode,
to obtain a sufficient airflow (350 to 450 CFM per
Ton), the blue wire must be positioned on the terminal
corresponding to the LOW, MED-LOW, MED-HIGH or
HIGH blower speed.
Blower speeds are adjusted in factory for 0.5 inch W.C.
static pressure.

6

Summary of Contents for ADVANTAGE SUPXX-A120D12

Page 1: ...0 INSTALLER SERVICE TECHNICIAN Attention Do not tamper with the unit or its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FU...

Page 2: ...ATION 9 5 FURNACE INFORMATION 9 6 TECHNICAL SPECIFICATIONS 10 7 NOTES 22 List of figures Figure 1 Upflow Configuration 4 Figure 2 Downflow Configuration 4 Figure 3 Horizontal Configuration 4 Figure 4...

Page 3: ...d for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual...

Page 4: ...8 VAC power supply to the control panel thermostat hook up as shown on the wiring diagram 2 1 POSITIONING THE FURNACE WARNING FIRE AND EXPLOSION HAZARD The furnace must be installed in a level positio...

Page 5: ...and or property damage 2 4 ELECTRICAL SYSTEM The SUPREME furnace is completely pre wired and all field wiring must be connected to the terminal blocks on the unit It requires 2 service wires of 240 20...

Page 6: ...t be changed to the 208V position 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated Follow the instructions supplied with the thermo...

Page 7: ...nd return air connectors to avoid the transmission of vibration To make the unit run even quieter the installer should 1 Use two elbows between each outlet and the supply and return air plenum 2 Cover...

Page 8: ...structions provided with the thermostat or the Fossil Fuel kit for the proper wiring of the furnace and the heat pump The simultaneous operation of the electric elements and the heat pump will cause o...

Page 9: ...on of the average airflow To do that the following formula should be used Liter s 0 82 amps volts Diff temperature C CFM 3 1 amps volts Diff temperature F Tables 5 and 6 show estimated airflows for va...

Page 10: ...rmostat higher than room temperature If the unit does not start up cut the power and call a qualified service technician When calling for service or ordering a replacement part specify the model and s...

Page 11: ...5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7...

Page 12: ...1 5 9 5 1 5 9 5 1 5 9 5 1 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Total Consumpti...

Page 13: ...or Consumption 240V 208V Amp Max 2 6 2 3 5 9 5 1 Heating Elements Consumption 240V 208V Amp 57 8 50 1 72 2 62 6 Total Consumption 240V 208V Amp 60 4 52 3 78 1 67 7 Ampacity 240V 208V Amp 76 66 93 81 S...

Page 14: ...est 5CFM Data taken with air filter in place Table 6 Airflow CFM SUPREME with 1HP motor Furnace equipped with a 1HP 120 blower motor Blower External static pressure inche of W C Speed 0 2 0 3 0 4 0 5...

Page 15: ...559mm 22 25mm 1 SUPPLY ALIMENTATION 508mm x 508mm 20 x 20 REVISIONS REV DESCRIPTION A C DATE PAR Figure 12 Advantage Dimensionsi 451mm 17 3 4 451mm 17 3 4 RETURN 483mm x 483mm 19 x 19 RETOUR Identical...

Page 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...

Page 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...

Page 18: ...Figure 15 lectrical diagram Supreme Advantage PSC 3 phases ELECTRICAL DIAGRAM DIAGRAMME L CTRIQUE ADVANTAGE AVANTAGE PSC 3 PHASES 17...

Page 19: ...20 23 24 25 28 27 B50147 rev F 7 8 9 10 11 12 13 5 6 REV DESCRIPTION A C DATE PAR B Changement Disjoncteur 22314 2015 05 15 F H C Ajoute support de filtre Change item 1 22388 2015 07 01 F H D TIQUETT...

Page 20: ...10 15 18 20 kW 20 B01889 Motor support band and legs 21 L06K004 Motor 1hp 120v PSC Supreme 20 kW 22 L06K005 Motor 1hp 240v PSC Supreme 20 kW 23 L06G007 Motor 1 3hp 120v PSC Supreme 10 15 18 20 kW 24...

Page 21: ...rev F 9 12 13 14 8 6 7 15 16 17 18 19 10 11 REV DESCRIPTION A C DATE PAR B Changement disjoncteur pour CQC 22326 2015 05 19 F H C Ajoute support de filtre Change item 1 22389 2015 07 01 F H D TIQUETT...

Page 22: ...18 20 23 25 kw 24 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 23 25 27 30 kw 25 Z01I036 Blower 112 9R 1hp Supreme 20 23 25 27 30 kw 26 Z01I035 Blower 112 8R 1 3hp Supr me 10 15 18 20 23 25 kw 27...

Page 23: ...7 NOTES 22...

Page 24: ...23...

Reviews: