background image

Table 1: Supply air adjustment on cooling mode

MOTOR

HP

COOLING

CAPACITY
(0.5 ‘’ w.c.)

BLOWER

SPEED

(Motor 120V)

BLOWER

SPEED

(Motor 240V)

1/3

1.5

LOW

LOW

2.0

MED-LOW

LOW

2.5

MED-HIGH

MED

3.0

HIGH

HIGH

1.0

2.5

LOW

LOW

3.0

MED-LOW

MED-LOW

3.5

MED-LOW

MED-HIGH

4.0

MED-HIGH

MED-HIGH

5.0

HIGH

HIGH

If heating and air-cooling speeds are the same, the
orange wire and the blue wire can be connected on the
same terminal on the motor.

2.7

INSTALLATION OF
ACCESSORIES

WARNING

E

LECTRICAL SHOCK HAZARD

Turn OFF electrical power at the fuse box
or service panel before making any electrical
connection and ensure that a proper ground
connection

is

made

before

connecting

line

voltage.
Failure to do so can result in death or bodily injury.

2.7.1

Humidifier and electronic air cleaner

For single-phase models, this unit is equipped with a 120
VAC terminal for the connection of accessories up to a
maximum of 2 amps. A humidifier and an electronic air
cleaner can be wired to terminals L1 and N of the unit.
Refer to the wiring diagrams in this manual (Figure 12
and Figure 13).

A field supplied 24 VAC transformer

can be installed for accessories using 24 VAC. For three-
phases models or if the accessories draw more than 2
amps, a separate power source must be used.

Some accessories require control relays. A location has
been set aside in the unit for the installation of relays:
a 24 VAC (part number L01H009).

In addition, a 24

VAC relay can be wired between terminals W1 and C
to be activated during a call for heat. Refer to the wiring
diagrams for the location of the relay RACC on the control
panel and in accessory instructions.

2.7.2

Use of a heat pump

When using a heat pump, a thermostat with dual fuel
option or a fossil fuel kit is required that prevents the
operation of the electric elements and the heat pump at
the same time. Refer to the instructions provided with the
thermostat or the “Fossil Fuel” kit for the proper wiring of

the furnace and the heat pump.
The simultaneous operation of the electric elements and
the heat pump will cause overheating of either unit.
The safety controls of the appliances will shut down the
elements or heat pump, since they are not designed to
function in this fashion.

3

OPERATION

3.1

START-UP

Before starting up the unit, be sure to check that the
following items are in compliance:

1. The electrical installation and ventilation are

conform;

2. The blower access door is in place and the blower

rail locking screws are well tightened;

3. The blower speed adjustments for heating and air

conditioning are appropriate and in accordance
with to the specifications in this manual;

4. The thermostat of the room is in heating mode and

is set higher than the ambient temperature;

5. The breakers on front panel are set on the “ON”

position.

To start the unit, turn the main electrical switch on.

3.2

USE OF MANUAL FURNACE
CONTROLS ON ADVANTAGE
FURNACE

When there is a demand for heat, the pilot light (L-1)
comes on. Refer to the wiring diagram.
When the “HI/LO” switch is put into the “LO” position, it
will shut down approximately half the elements.

However, it is important to put the switch back to
the “HI” position during the winter months to ensure
adequate heating.

Also, this switch must remain in the “HI” position when
a 2-stage or outdoor thermostat is used to control the
electric elements of the second stage.

Refer to the

diagram in Section 2.5. The “ON/OFF VENT/FAN” switch
engages the blower in the continuous low speed mode.
This will filter the air and provide for better air distribution
in the building.
The 15 A circuit breaker is there to protect the motor
and the control circuit conductors. If the unit does not
function, press the circuit breaker button to see if it may
have disengaged due to a power surge. If the breaker
has to be pressed again, the unit must be checked by a
qualified service technician.

Figure 10: Advantage furnace controls

7

Summary of Contents for ADVANTAGE SUPXX-A120D12

Page 1: ...0 INSTALLER SERVICE TECHNICIAN Attention Do not tamper with the unit or its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FU...

Page 2: ...ATION 9 5 FURNACE INFORMATION 9 6 TECHNICAL SPECIFICATIONS 10 7 NOTES 22 List of figures Figure 1 Upflow Configuration 4 Figure 2 Downflow Configuration 4 Figure 3 Horizontal Configuration 4 Figure 4...

Page 3: ...d for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual...

Page 4: ...8 VAC power supply to the control panel thermostat hook up as shown on the wiring diagram 2 1 POSITIONING THE FURNACE WARNING FIRE AND EXPLOSION HAZARD The furnace must be installed in a level positio...

Page 5: ...and or property damage 2 4 ELECTRICAL SYSTEM The SUPREME furnace is completely pre wired and all field wiring must be connected to the terminal blocks on the unit It requires 2 service wires of 240 20...

Page 6: ...t be changed to the 208V position 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated Follow the instructions supplied with the thermo...

Page 7: ...nd return air connectors to avoid the transmission of vibration To make the unit run even quieter the installer should 1 Use two elbows between each outlet and the supply and return air plenum 2 Cover...

Page 8: ...structions provided with the thermostat or the Fossil Fuel kit for the proper wiring of the furnace and the heat pump The simultaneous operation of the electric elements and the heat pump will cause o...

Page 9: ...on of the average airflow To do that the following formula should be used Liter s 0 82 amps volts Diff temperature C CFM 3 1 amps volts Diff temperature F Tables 5 and 6 show estimated airflows for va...

Page 10: ...rmostat higher than room temperature If the unit does not start up cut the power and call a qualified service technician When calling for service or ordering a replacement part specify the model and s...

Page 11: ...5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7...

Page 12: ...1 5 9 5 1 5 9 5 1 5 9 5 1 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Total Consumpti...

Page 13: ...or Consumption 240V 208V Amp Max 2 6 2 3 5 9 5 1 Heating Elements Consumption 240V 208V Amp 57 8 50 1 72 2 62 6 Total Consumption 240V 208V Amp 60 4 52 3 78 1 67 7 Ampacity 240V 208V Amp 76 66 93 81 S...

Page 14: ...est 5CFM Data taken with air filter in place Table 6 Airflow CFM SUPREME with 1HP motor Furnace equipped with a 1HP 120 blower motor Blower External static pressure inche of W C Speed 0 2 0 3 0 4 0 5...

Page 15: ...559mm 22 25mm 1 SUPPLY ALIMENTATION 508mm x 508mm 20 x 20 REVISIONS REV DESCRIPTION A C DATE PAR Figure 12 Advantage Dimensionsi 451mm 17 3 4 451mm 17 3 4 RETURN 483mm x 483mm 19 x 19 RETOUR Identical...

Page 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...

Page 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...

Page 18: ...Figure 15 lectrical diagram Supreme Advantage PSC 3 phases ELECTRICAL DIAGRAM DIAGRAMME L CTRIQUE ADVANTAGE AVANTAGE PSC 3 PHASES 17...

Page 19: ...20 23 24 25 28 27 B50147 rev F 7 8 9 10 11 12 13 5 6 REV DESCRIPTION A C DATE PAR B Changement Disjoncteur 22314 2015 05 15 F H C Ajoute support de filtre Change item 1 22388 2015 07 01 F H D TIQUETT...

Page 20: ...10 15 18 20 kW 20 B01889 Motor support band and legs 21 L06K004 Motor 1hp 120v PSC Supreme 20 kW 22 L06K005 Motor 1hp 240v PSC Supreme 20 kW 23 L06G007 Motor 1 3hp 120v PSC Supreme 10 15 18 20 kW 24...

Page 21: ...rev F 9 12 13 14 8 6 7 15 16 17 18 19 10 11 REV DESCRIPTION A C DATE PAR B Changement disjoncteur pour CQC 22326 2015 05 19 F H C Ajoute support de filtre Change item 1 22389 2015 07 01 F H D TIQUETT...

Page 22: ...18 20 23 25 kw 24 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 23 25 27 30 kw 25 Z01I036 Blower 112 9R 1hp Supreme 20 23 25 27 30 kw 26 Z01I035 Blower 112 8R 1 3hp Supr me 10 15 18 20 23 25 kw 27...

Page 23: ...7 NOTES 22...

Page 24: ...23...

Reviews: