TABLE 7
Air Flow Data, Models 120 / 156
SW1- HEAT
DIP switch position
HEAT INPUT
(USGPH)
CFM avec SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
0,85
1450
1640
1235
B
(1=ON, 2=OFF)
1,00
1700
1920
1445
C
(1=OFF, 2=ON)
1,10
1850
2090
1575
D
(1=ON, 2=ON)
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
5,0
1315
1510
1115
B
(1=ON, 2=OFF)
4,0
1050
1210
895
C
(1=OFF, 2=ON)
3,5
920
1055
780
D
(1=ON, 2=ON)
3,0
790
905
670
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
5,0
1750
1925
1575
B
(1=ON, 2=OFF)
4,0
1400
1540
1260
C
(1=OFF, 2=ON)
3,5
1225
1350
1105
D
(1=ON, 2=ON)
3,0
1050
1155
945
SW4- DELAY
DIP switch position
HEAT INPUT
(USGPH)
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
A
(1=OFF, 2=OFF)
0,85
13% - 45 sec.
44% - 30 sec
38% - 3 min.
B
(1=ON, 2=OFF)
1,00
13% - 30 sec.
44% - 30 sec
38% - 3 min.
C
(1=OFF, 2=ON)
1,10
13% - 30 sec.
50% - 30 sec
38% - 3 min.
D
(1=ON, 2=ON)
All
13% - 30 sec.
100% - 0 sec
100% - 2 min.
No adjustment
required
A/C size
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
-
All
No delay
No delay
100% - 90 sec.
Off Delay is the time required to cool down the heat exchanger with low CFM, to minimize cool draft in the air distribution system.
DELAY PROFILE FOR COOLING OR HEAT PUMP HEATING MODE
In Cooling - Dehumidification mode, with no 24 VAC input to DH, the CFMs are reduced by 15%.
in the system and then runs up to normal speed.
The CFMs shown are reduced by 55% if there is 24 VAC input to Y1 (Slow speed of a 2-speed compressor)
OIL HEATING MODE
24 VAC input (R) on W only
in the system and then runs up to normal speed.
CONTINUOUS FAN
24 VAC input (R) on G only
COOLING OR HEAT PUMP HEATING MODE*
24 VAC input (R) to G, Y/Y2 and O (for cooling)
Same value as DIP switch position A
DELAY PROFILE FOR OIL HEATING MODE
PreRun and ShortRun are the periods of time when the the blower starts at very low CFM to minimize the distributon of cool air
PreRun and ShortRun are the periods of time when the the blower starts at very low CFM to minimize the distributon of cool air
Off Delay is the time required to cool down the coil (heating mode) with low CFM, to mimimize cool draft in the air distribution system.