background image

Table 17 – Error codes single stage

LED

Desription

1 flash, pause

System Lockout

2 flash, pause

Pressure switch stuck
close

3 flash, pause

Pressure switch stuck
open

4 flash, pause

Open limit switch

5 flash, pause

Open rollout switch

6 flash, pause

115VAC polarity

7 flash, pause

Low flame sense

continuous
flashing

Flame

has

been

sensed when no flame
should be present

10

SINGLE

STAGE

PSC

MOTOR

Furnaces with model number CXX-1-D are equipped
with a fixed speed motor. This motor provides ease in
adjusting the blower speeds in cooling or heating mode.
Blowers should be adjusted by the installer to match
the installation requirements so as to provide the correct
heating temperature rise and cooling load.

10.1

Selecting the blower speed on
PSC motor

These blower speeds are set for a temperature rise
of 55°F at normal static pressure.

Blowers should

be adjusted by the installer to match the installation
requirements so as to provide the correct heating
temperature rise and cooling load.

To adjust the

circulator blower speed, proceed as follow:

1. Turn off the power to the furnace

2. Select the heating and cooling blower speeds that

match the installation requirements.

3. Relocate the desired motor leads to the desired

speed on the motor. The red wire locate the heating
speed and the blue wire locate de cooling speed.

4. If heating and cooling speeds are the same, a

jumper wire must be used between the heat and
cool terminal on the control board. The unused
leads must be connected to the “PARK” terminal on
the control board.

5. Turn on power to the furnace.

6. Verify

proper

temperature

rise.

Excessive

temperature can cause limit switch tripping.

Figure 31 – PSC motor connections

Table 18 – Suggested heating fan speed on single
stage furnace

INPUT BTU/hr

SPEED

45 000

LOW

60 000

MED-LOW

75 000

MED-LOW

105 000

HIGH

120 000

HIGH

Table 19 – CFM C45-1-D/C45-2-D

MOTOR
SPEED

Static pressure

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

1120

1095

1045

1020

970

915

845

780

710

640

MED-
HIGH

1047

1045

980

940

880

835

775

715

665

585

MED

935

950

910

865

820

780

730

670

600

565

LOW

930

925

875

835

800

760

710

660

605

545

Table 20 – CFM C60-1-D/C60-2-D

MOTOR
SPEED

Static pressure

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

1374 1372 1370 1305 1230 1155 1085 1005 945

860

MED-
HIGH

1198 1195 1134 1085 1025 975

925

875

814

740

MED

1155 1150 1100 1050 1000 955

905

860

795

725

LOW

1026 1005 980

945

905

865

820

780

720

655

Table 21 – CFM C75-1-D/C75-2-D

MOTOR
SPEED

Static pressure

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

1617 1615 1540 1440 1355 1280 1204 1182 1060 980

MED-
HIGH

1675 1670 1590 1480 1382 1300 1219 1192 1065 982

MED

1500 1496 1388 1289 1188 1133 1087 1083 1015 975

LOW

1272 1197 1148 1108 1042 967

913

824

777

749

Table 22 – CFM C105-1-D/C105-2-D

MOTOR
SPEED

Static pressure

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

HIGH

1748 1740 1615 1515 1430 1355 1285 1195 1110 1030

MED-
HIGH

1700 1655 1550 1435 1360 1285 1230 1150 1080 990

MED

1415 1405 1325 1240 1180 1135 1070 1005 930

845

LOW

1165 1130 1065 1025 975

935

870

830

775

705

28

Summary of Contents for C105-1-D

Page 1: ...old in US and Canada INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace and keep the document near the unit for future reference HOMEOWNER Pl...

Page 2: ...MET 14 5 4 SETTING GAS OUTLET PRESSURE 14 5 4 1 Adjusting 2 stage gas valve 15 5 4 2 Adjusting single stage gas valve 15 6 ELECTRICAL CONNECTIONS 17 6 1 120V WIRING 17 6 2 24V WIRING 17 6 3 FUSE 17 6...

Page 3: ...Stage PSC Wiring diagram 33 Figure 33 Two Stage PSC Wiring diagram 34 Figure 34 Single Stage ECM Wiring diagram 35 Figure 35 Dimensions 38 Figure 36 Exploded view CXX 1 X part 1 39 Figure 37 Exploded...

Page 4: ...assess the damage and to replace all critical parts that were in contact with water 3 Do not store gasoline or any other flammable substances such as paper or carton near the furnace 4 Do not stack it...

Page 5: ...o be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace See section 4 DUCT INSTALLATION This furnace may be installed with a two pipe sealed combus...

Page 6: ...th the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or Natural Gas and Propane Installation code CSA B149 1 9 After it has been determined that each appliance connected to the venting system properl...

Page 7: ...ng Systems ANSI NFPA 90B National Standard of Canada Natural Gas and Propane Installation Code NSCNGPIC CAN CSA B149 1 General installation NFGC and the NFPA 90B For copies contact the National Fire P...

Page 8: ...water Not be installed directly on any combustible material other than wood flooring Be located close to the chimney or vent and attached to an air distribution system Refer to section 7 Place the un...

Page 9: ...r slightly leaned forward to help drain condensate 3 1 1 Right side condensate drain trap connection Figure 1 Right side connection See figure 1 and read the following instructions 1 Remove the oblong...

Page 10: ...supply duct going through the floor and the proper slope of the furnace for condensate drainage Also the base allows sufficient spacing for the venting and the drain trap When installing the furnace...

Page 11: ...ssure switch assembly Figure 5 Connecting pressure switch in downflow position 3 3 HORIZONTAL RIGHT Figure 6 Horizontal right position Figure 7 Horizontal right slope When installing the furnace in ho...

Page 12: ...on of flue gas 9 On the remaining 5 inlets connect black caps 1x5 8 and 2x1 2 These caps are provided in the parts bag 3 3 2 Horizontal right multiposition pressure switch connection Figure 8 Horizont...

Page 13: ...ub of the drain trap Cut the provided 5 8 tubing at appropriate length to reach the drain trap 8 Reroute the vent collector drain tube to one of the 1 2 stubs of the drain trap Cut the provided 1 2 tu...

Page 14: ...n of vibration Many states provinces and localities are considering or have implemented standards and or restrictions on duct sizing practices ductwork leakage and or ductwork thermal airflow and elec...

Page 15: ...d local codes Refer to current edition of NFGC in the U S A Refer to current edition of CAN CSA B149 1 in Canada Installations must be made in accordance with all authorities having jurisdiction Use a...

Page 16: ...wise 7in lb minimum 12 Turn on electrical power to the system 13 Make a call for heat on the thermostat 14 Using a leak detection solution or soap suds check for leaks at the pressure boss screw If a...

Page 17: ...l Gas Propane High fire 100 3 0 8 6 Low fire 70 1 55 5 0 Figure 16 Typical gas pipe arrangement Table 6 Maximum capacity of pipe Cu ft Hr for pipe length ft m Nominal Iron pipe size in mm Internal dia...

Page 18: ...r cooling operation Use only AWG No 18 color coded copper thermostat wire Use AWG No 18 color coded copper thermostat wire for lengths up to 100ft 30 5m For wire lengths over 100 ft use AWG No 16 wire...

Page 19: ...1 4 per foot of run so that condensate drains toward the furnace Support horizontal vent piping at least every five feet No sags or dips are permitted The vent pipe and combustion air pipe must termin...

Page 20: ...nt pipe installations in Canada must conform to the requirements of CAN CSA B149 code PVC and CPVC vent systems must be composed of pipe fittings cements and primers listed to ULC S636 and must be of...

Page 21: ...distribution of primer and cement 8 Clean and dry all surfaces to be joined 9 Check dry fit of the pipe and mark insertion depth on the pipe 10 After the pipes have been cut and preassembled apply a...

Page 22: ...allation codes and the requirements of the gas supplier and the instructions in this manual A vent for this appliance shall not terminate over public walkways near soffit vents or crawl space vents or...

Page 23: ...of or sidewall for vent and combustion air pipes Sidewall holes for two pipes vent terminations should be side by side allowing space between the pipes for the elbows to fit on the pipes Holes in the...

Page 24: ...Figure 26 Alternate horizontal termination C Figure 27 Venting gasket 23...

Page 25: ...Figure 28 Direct vent clearance 24...

Page 26: ...Figure 29 Other than Direct vent clearance 25...

Page 27: ...light the main burners 3 Set the thermostat to it lowest setting and turn off furnace electrical power 4 Replace the burner compartment control access door WARNING Failure to replace the burner door c...

Page 28: ...fan on S2 30 sec 45 sec Table 16 Option switch single stage delay to fan off heating HEAT delay DIPSWITCH to fan off S3 S4 60 sec ON ON 90 sec OFF ON 120 sec ON OFF 180 sec OFF OFF 9 3 Cool mode A cal...

Page 29: ...minal on the control board The unused leads must be connected to the PARK terminal on the control board 5 Turn on power to the furnace 6 Verify proper temperature rise Excessive temperature can cause...

Page 30: ...cate the 1st stage heating and the blue wire locate de cooling speed 4 If heating and cooling speeds are the same a jumper wire must be used between the heat and cool terminal on the control board The...

Page 31: ...air it Call a qualified service technician Force or attempted repair may result in a fire or explosion 13 1 WHAT TO DO IF YOU SMELL GAS WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnin...

Page 32: ...excess dirt from a cleanable filter shake filter and or use a vacuum cleaner Wash filter in soap or detergent water and replace after filter is dry Cleanable filters do not need to be oiled after was...

Page 33: ...5 9 20 75 000 120 60 1 127 104 13 1 15 5 20 105 000 120 60 1 127 104 16 4 19 7 20 120 000 120 60 1 127 104 16 4 19 7 20 Two Stage ECM motor UNIT VOLT HERTZ PHASE OPERATING VOLT RANGE MAX UNIT UNIT AMP...

Page 34: ...Figure 32 Single Stage PSC Wiring diagram...

Page 35: ...Figure 33 Two Stage PSC Wiring diagram...

Page 36: ...Figure 34 Single Stage ECM Wiring diagram...

Page 37: ...essure high fire 100 Outlet gas pressure low fire 70 Static pressure in return Static pressure in supply Temperature rise Is drain trap filled with water Is drain trap outlet vented with a Tee Are con...

Page 38: ...ve Make sure flame rod is clean and properly wired 9 Improper grounding or polarity 120V hot and neutral reversed 120V should be read between Hot and ground 0V should be read between Neutral and groun...

Page 39: ...Figure 35 Dimensions 38...

Page 40: ...Figure 36 Exploded view CXX 1 X part 1...

Page 41: ...Figure 37 Exploded view CXX 1 X part 2...

Page 42: ...7 26 B30157 26 B30157 26 B30157 26 30 Ignitor R03K005K R03K005K R03K005K R03K005K R03K005K 31 Roll out switch R02N022 R02N022 R02N022 R02N022 R02N022 32 Gas manifold orifice included B40527 B40528 B40...

Page 43: ...Figure 38 Exploded view Cxx 1 D part 1...

Page 44: ...Figure 39 Exploded view Cxx 1 D part 2...

Page 45: ...B40903 B40903 B40903 B40903 B40903 31 Venting flange gasket B40567 B40567 B40567 B40567 B40567 32 Drain trap B40760 B40760 B40760 B40760 B40760 33 Venting flange B40533 B40533 B40533 B40533 B40533 34...

Page 46: ...Figure 40 Exploded view Cxx 2 D part 1...

Page 47: ...Figure 41 Exploded view Cxx 2 D part 2...

Page 48: ...ng gasket B40903 B40903 B40903 B40903 B40903 33 Venting flange gasket B40567 B40567 B40567 B40567 B40567 34 Drain trap B40760 B40760 B40760 B40760 B40760 35 Venting flange B40533 B40533 B40533 B40533...

Reviews: