background image

9.13.3

Heat rise adjust

This DIP switch is used to select desired temperature rise
in the heating mode.
Refer to table 15.

Table 15 – Heat rise adjust

S4-1

RISE

OFF

35 °F

ON

30°F

9.13.4

Continuous fan speed

Using the communicating thermostat R02P032, select
the LOW continuous fan speed. In User Menu, go to "Fan
Settings" and choose "LOW".

9.13.5

Furnace test mode

S4-2 and S4-3 - The Test Switches will place the furnace
into a test mode, operating the furnace at continuous
input rates of either 100% of full rate (maximum fire) or
40% of full rate (minimum fire). This is accomplished by
setting the Test Switches. See table 16.
To enter the furnace test mode, proceed as follows:

1. Switch the 120 volt power to the furnace OFF. Do

not change settings with control energized.

2. Position Test Switches for the desired test mode.

3. Switch the 120 volt power to the furnace ON.

4. Set the thermostat mode to HEAT; adjust the set

point at least 4°F above room temperature to
demand a call for heating.

The furnace will operate at the fixed test mode until on e
of the following conditions :

• The thermostat is satisfied and the call for heat is

removed.

• The furnace has been in test mode continuously for

sixty minutes, at which time the furnace control will
exit the test mode and proceed to normal heating
operation as configured.

Test mode cannot be

activated again unless line voltage power to the
furnace is cycled off and back on. This is true even
if the DIP switches remain configured to the test
settings

Table 16 – Test mode

S4-2

S4-3

DESCRIPTION

ON

OFF

40% TEST

OFF

ON

100% TEST

10

USER’S

INFORMATION

MANUAL

Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.

Installation and service must be performed by a qualified
installer, service agency, or the gas supplier.
Read all instructions in this manual and retain this and all
additional instructions for future reference.
To keep your operating costs low and to eliminate
unnecessary service calls, we have provided a few
guidelines. These guidelines will help you understand
how your gas furnace operates and how to maintain it so
you can get years of safe and dependable service. Read
all the instructions in this manual, and keep all manuals
for future reference.
For your safety, read the following before operating your
furnace:

1. The furnace area must be kept clear and free

of combustible materials, gasoline, and other
flammable vapors and liquids.

2. Insulating materials may be combustible. A furnace

installed in an attic or other insulated space must be
kept free and clear of insulating materials. Examine
the furnace when it is installed and also any time
insulation is added.

3. For proper safe operation, the furnace needs air

for combustion and ventilation.

Do not block or

obstruct air openings to the area in which the
furnace is installed, and the spacing around the
furnace.

4. This furnace is equipped with an ignition device

which automatically lights the burners.

5. Should the gas supply fail to shut off or if

overheating occurs, shut off the gas valve to the
furnace before shutting off the electrical supply.

6. Do not use the furnace if any part has been under

water.

A flood damaged furnace is extremely

dangerous. Attempts to use the furnace can result
in fire or explosion.

A qualified service agency

should be contacted to inspect the furnace and
to replace all gas controls, control system parts,
electrical parts that have been wet, or the entire
furnace if deemed necessary.

7. Examine the furnace installation to determine that:

• All flue gas carrying areas external to the

furnace, such as the chimney and vent
connector, are clear and free of obstructions.

• Vent connector is in place, slopes upward, and

is physically sound without holes or excessive
corrosion.

• Return air duct connection(s) is physically

sound, sealed to the furnace casing, and
terminates outside the space containing the
furnace.

• Physical support of the furnace is sound

without sagging, cracks, gaps, etc. around the

28

Summary of Contents for CC15-M-V

Page 1: ...future reference Caution Do not tamper with the unit or its controls Call a qualified service technician HOMEOWNER Please keep this manual near the furnace for future reference Manufactured by Dettson...

Page 2: ...1 NON COMMUNICATING MODULATING ONE STAGE OR TWO STAGE THERMOSTAT 16 7 3 2 THERMOSTAT INPUT 16 7 4 ALTERNATE POWER SUPPLY 17 8 VENTING AND COMBUSTION AIR PIPING 19 8 1 GENERAL 19 8 2 DIRECT VENT 19 8 3...

Page 3: ...Alternate horizontal termination A 22 Figure 23 Alternate horizontal termination B 22 Figure 24 Alternate horizontal termination C 22 Figure 25 Direct vent clearance 23 Figure 26 Other than Direct ve...

Page 4: ...assess the damage and to replace all critical parts that were in contact with water 3 Do not store gasoline or any other flammable substances such as paper or carton near the furnace 4 Do not stack it...

Page 5: ...o be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace See section 5 DUCT INSTALLATION This furnace may be installed with a two pipe sealed combus...

Page 6: ...th the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or Natural Gas and Propane Installation code CSA B149 1 9 After it has been determined that each appliance connected to the venting system properl...

Page 7: ...n Code NSCNGPIC CAN CSA B149 1 General installation NFGC and the NFPA 90B For copies contact the National Fire Protection Association Inc Battery march Park Quincy MA 02269 or for only the NFGC contac...

Page 8: ...in this manual The furnace should be located as close to the chimney vertical venting or to the outside vent wall horizontal venting as possible 2 3 1 Location relative to cooling equipement The cooli...

Page 9: ...on Figure 3 Dimensions Figure 4 Top view Figure 5 Drain Trap Localisation Figure 6 Pressure switch connections for multipositions 4 1 UPFLOW The condensate trap must be outside the furnace casing Use...

Page 10: ...gths 1 4 5 and 2 9 25 3 Remove the appropriate knock out for drain trap Refer to Figure 5 for the location of the drain trap in downflow configuration 4 Cut open the pressure port located on the conde...

Page 11: ...er to ensure proper drainage of the condensate See figure 12 4 3 1 Horizontal Condensate drain connection 1 Remove PVC tubes from the ID blower condensate box and vent collector and block the openings...

Page 12: ...ith local building codes 12 The venting must be drained using a PVC 636 tee Connect this tee to a P trap and connect it to your condensate drain Commercially available condensate trap exist for use wi...

Page 13: ...fasteners for type of ductwork used Seal supply and return duct connections to the furnace with code approved tape or duct sealer Ductwork passing through an unconditioned space should be insulated t...

Page 14: ...ot have a 90 degree elbow and 10 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in...

Page 15: ...ert the gas valve to propane 1 Move the switch located on the valve to the off position 2 Remove the NAT GAS label from the top of the gas valve 3 Using a pair of tweezers or needle nose pliers place...

Page 16: ...mum mode of operation and will give the best temperature control with minimal temperature variation from the desired set point Operation with a 2 stage thermostat will proceed as follow call on W1 wil...

Page 17: ...te Power from an alternate power supply that is non sinusoidal may damage the furnace electronics or cause erratic operation Contact the alternate power supply manufacturer for specifications and deta...

Page 18: ...Figure 17 Wiring Diagram 18...

Page 19: ...rrent edition of the National Fuel Gas Code and the vent or liner manufacturer s installation instructions Care must be taken to prevent the exhaust gases from one appliance from contaminating the com...

Page 20: ...e 2 Count the number of elbows for each pipe 3 For each pipe multiply the number of elbows by the equivalent length for the type of elbow used see table 11 Record the equivalent length of all the elbo...

Page 21: ...INATION All clearance specified in this manual are in accordance with the current CSA B149 1 Natural and Propane Installation Code and the current ANSI Z223 1 NFPA 54 National Fuel Gas Code For cleara...

Page 22: ...r the elbows to fit on the pipes Holes in the roof for two pipe terminations should be spaced no more than 18 457 mm apart Termination elbows will be installed after the vent and combustion air pipe a...

Page 23: ...Figure 25 Direct vent clearance 23...

Page 24: ...Figure 26 Other than Direct vent clearance 24...

Page 25: ...ve the burner compartment control access door 3 IMPORTANT Be sure that the manual gas control has been in the OFF position for at least five minutes Do not attempt to manually light the main burners 4...

Page 26: ...oth pressure switches quickly Once both pressure switches are sensed to be closed the inducer will run for 25 seconds before the ignition trial starts Hot surface igniter is energized during the pre p...

Page 27: ...esent the furnace will not operate in any mode and a fault will be displayed 9 12 REPLACING FURNACE CONTROL In the event that the furnace control must be replaced the memory card must be detached from...

Page 28: ...r future reference To keep your operating costs low and to eliminate unnecessary service calls we have provided a few guidelines These guidelines will help you understand how your gas furnace operates...

Page 29: ...g 3 Leave the building immediately 4 Immediately call your gas supplier Follow the gas supplier s instructions 5 If you cannot reach the gas supplier call the fire department 10 2 OPERATING YOUR FURNA...

Page 30: ...sense current is weak or weird 1 Clean or replace de flame sensor 2 Check gas outlet pressure 3 Take a combustion analysis A dirty flamme sensor needs to be investigate 13 Flame lost 1 Clean or replac...

Page 31: ...e gas valve will immediately close flame will be lost blower motor operation will immediately stop and the furnace will shut down normally with Inducer post purge at the correct speed After the post p...

Page 32: ...Outlet gas pressure high fire 100 Outlet gas pressure low fire 40 Static pressure in return Static pressure in supply Temperature rise Is drain trap filled with water Is drain trap outlet vented with...

Page 33: ...Table 18 Specification table 1 Maximum CFM acheived in standard duct systems 2 Maximum CFM acheived using SmartDuct system 33...

Page 34: ...12 PART LIST Figure 27 Exploded view...

Page 35: ...Figure 28 Exploded view continued...

Page 36: ...Table 19 Part list Chinook Compact...

Page 37: ...Table 20 Part list continued...

Page 38: ...13 NOTES 38...

Page 39: ...39...

Page 40: ...40...

Reviews: