background image

 

deliver  a  temperature  rise  within  the  range  specified  on  the 
rating  plate,  between  the  return  and  supply  pressure  at  the 
external duct static pressure noted on the rating label. 
 
Adjust  the  fan  speed  ACCORDING  TO  THE  OIL  INPUT 
SELECTED, so that the temperature rise is within the range 
specified  on  the  rating  plate  (see  Table  2).    Consult  the 
wiring diagram for speed changes on the direct drive motor. 
 
In  the  oil  mode,  the  blower  start  /  stop  is  controlled  by  a 
helical  bi-metal  Fan-Limit  Control,  which  is  adjusted  to  start 
at  110°F  and  stop  at  90°F.  These  are  factory  set  li mits  and 
must not be changed or tampered with. 
 
3.2.5 

Limit Control check 

 
The  Limit  Control  is  factory  adjusted  according  to  Figure  1.  
After  the  furnace  has  been  in  operation  for  at  least  15 
minutes, restrict the return air supply by blocking the filters or 
closing  the  return  registers  and  allow  the  furnace  to  shut 
down  on  high limit.   The  burner  will  shut  OFF  and  the  main 
blower should continue to run. 
 
Remove the restriction and the burner should come back on 
in a few minutes. 
 
Constant Blower Switch 
 
This  furnace  is  equipped  with  a  constant  low  speed  blower 
option.    Whenever  the  room  thermostat  is  not  calling  for 
heating or cooling, the blower will run on low speed in order 
to provide air circulation.  If this constant blower option is not 
desired, the rocker switch on the side of the control box can 
be used to turn off this feature. 
 

Figure 1 : Limit Control adjustment 

 

 

   

  DNS-0355 Rev A

 

1  Limit “FAN OFF” 

90°

2  Limit “FAN ON” 

110°

3  Limit “HI” 

190°

 

 
 

3.2.6 

Limit Control adjustment 

 
Changing the Low Limit "FAN ON" and limit "HI" on the Fan 
limit control can cause malfunction of the furnace and cause 
premature wear of the heat exchanger. 

 

CAUTION 

 

Modification  of  the  factory  set  limits  will  void  the 
warranty. 

 

 
3.2.7 

BVSO performance test 

 
The  purpose  of  the  following  test  is  to  check  that  the 
electrical  outlet  on  the  furnace,  designated  to  the  BVSO,  is 
functional. 

1.  Start up the burner; 

2.  Remove  the  three-pole  plug  from  the  BVSO  outlet  on 

the furnace; 

3.  The  burner  must  shut-off  immediately,  while  the  blower 

continues to run to the end of the cool-down cycle. 

 
If  the  test  is  not  in  line  with  the  above,  call  a  QUALIFIED 
SERVICE TECHNICIAN. 
 
 
 

4.0  MAINTENANCE 

 
This  furnace  should  never  be  operated  without  an  air  filter.  
Disposable filters should be replaced at least once a year.  If 
equipped  to  provide  cooling,  filters  should  be  replaced  a 
minimum of twice a year. 
 
In order to avoid injuries, be sure to cut the power to the unit 
before commencing maintenance work. 
 
For  optimum  performance,  the  oil  burner  nozzle  should  be 
replaced at least once a year. Contact an authorized service 
technician if you are unsure of this procedure. 
 
The  procedure  for  the  installation  and/or  replacement  of  a 
nozzle is outlined in the oil burner instruction manual that is 
supplied with the furnace. 
 
After  replacing  the  nozzle,  the  burner  should  be adjusted  in 
accordance with the “COMBUSTION CHECK” section of this 
manual. 

 

WARNING 

 

Be sure to turn all power “OFF” upstream from the unit 

when servicing the furnace, unless power is required for 
specific  operations.  Failure  to  comply  with  this 
CAUTION  can  result  in  bodily  harm  and/or  cause  a  fire 
hazard. 

 

 
4.1 

HEAT EXCHANGER CLEANING 

 
Ordinarily, it is not necessary to clean the heat exchanger or 
flue  pipe  every  year,  but  it  is  advisable  to  have  a  qualified 
service  technician  check  the  unit  before  each  heating 
season  to  determine  whether  cleaning  or  replacement  of 
parts is required. 
 

Summary of Contents for LOW-BOY AME15-79

Page 1: ...79 AME20 90 AME25 100 DNS 0671 R v A C Fabriqu par Industries Dettson Inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS...

Page 2: ...igne de mazout 8 3 2 3 V rification de la combustion 9 3 2 4 V rification de l ajustement du ventilateur 9 3 2 5 V rification des limiteurs de temp rature 10 3 2 6 Ajustement du limiteur 10 3 2 7 V ri...

Page 3: ...ation de cet appareil par une personne non qualifi e peut endommager l quipement et ou conduire des conditions hasardeuses susceptibles d entra ner des dommages corporels IMPORTANT Toutes les exigence...

Page 4: ...contr le des odeurs D autre part en plus de l air de combustion une quantit suffisante d air doit tre fournie pour la ventilation incluant l air n cessaire pour le confort et des conditions de travai...

Page 5: ...11 Chemin es foyers vents et appareils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L temp...

Page 6: ...ce de votre unit et l amp rage nominal afin de choisir un disjoncteur et une protection de calibre suffisant L unit requiert une alimentation 240 120 Volts AC 60 Hz 3 fils plus mise la terre Installer...

Page 7: ...S il y a panne de ventilateur ou obstruction excessive dans le conduit d air chaud le g n rateur est muni d un contr le de haute limite qui emp che le br leur de surchauffer et d endommager le g n rat...

Page 8: ...peut tre allum ou non Voyant AUTO RELEVE et voyant ELECTRICITE Lorsque le voyant AUTO RELEVE est allum en m me temps que le voyant ELECTRICITE ceci signifie qu il y a un probl me sur le mode MAZOUT V...

Page 9: ...u un quivalent 3 Afin d effectuer la v rification de la combustion suivre les tapes suivantes a Percer un orifice d analyse des gaz de diam tre minimum appropri e environ 9 32 dans le tuyau de raccord...

Page 10: ...ider le bon fonctionnement de la prise BVSO sur l unit de chauffage seulement 1 Faire fonctionner le br leur 2 D brancher la prise 3 p les identifi e BVSO sur l unit 3 Le br leur doit s arr ter imm di...

Page 11: ...t pouvez inspecter visuellement ou l aide d un voltm tre chacun des l ments Si vous avez changer un l ment suivez la proc dure suivante 1 D branchez les 2 fils lectriques de l l ment retirer 2 D visse...

Page 12: ...t adresse du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp...

Page 13: ...van 0 65 80W 0 75 80W 0 85 80W Ajustement air de combustion bande obturateur 0 7 1 4 0 9 SYST ME LECTRIQUE Volts Hertz Phase 240 120 60 1 Contr le du transformateur 40 VA DONN ES TECHNIQUES DU VENTILA...

Page 14: ...MENT APPLICATION D GAGEMENT MINIMUM FOURNAISE 15 cm 6 PLENUM D ALIMENTATION 5 cm 2 AUTRE C T FOURNAISE 60 cm 24 ARRI RE FOURNAISE 60 cm 24 DESSUS FOURNAISE OU PLENUM 5 cm 2 DESSOUS FOURNAISE PLANCHER...

Page 15: ...15 Figure 3 Emplacement des composantes principales Figure 4 Localisation du tiroir d l ments DNS 0202 R v C DNS 0209 R v A...

Page 16: ...16 Figure 5 D montage du tiroir d l ment...

Page 17: ...17 Figure 6 Diagramme lectrique...

Page 18: ...18 Figure 7 Liste de pi ces B50047 Rev A...

Page 19: ...PLAQUE DE RETENUE 30 B02301 GARNITURE SORTIE DES GAZ 31 B02311 ASS SORTIE DES GAZ 32 B02312 ASS PIEGE A SON COMPLET 33 F07O001 ECROU HEXAGONAL A BRIDE 3 8 16NC LAITON 34 Z99F050 POIGNE ENCASTRE NOIR 3...

Page 20: ...SUS 70 B01154 PORTE D ACCES 71 B01095 ASS D LEMENTS 72 A00207 11 FIL ELECTRIQUE ROUGE 73 A00201 19 FIL ELECTRIQUE NOIR 74 L04J002 BRIDE DE CABLE 7 8 NOIR 75 B01123 03 TIROIR D L MENT 76 B01123 01 TIRO...

Page 21: ...Printed on 100 recycled paper DNS 0671 Rev A C Manufactured by Industries Dettson inc 3400 Industrial Boulevard Sherbrooke Quebec Canada J1L 1V8 www dettson ca INSTALLER SERVICE TECHNICIAN USE THE INF...

Page 22: ...OIL MODE 7 3 2 1 Operational checklist 7 3 2 2 Purging the oil line 8 3 2 3 Combustion check 8 3 2 4 Fan adjustment check 8 3 2 5 Limit Control check 9 3 2 6 Limit Control adjustment 9 3 2 7 BVSO perf...

Page 23: ...e installation of oil burning equipment wiring and flue connections must be followed some of the codes that may be applicable are CSA B139 Installation code for oil burning equipment ANSI NFPA 31 Inst...

Page 24: ...equate to provide air for combustion ventilation and dilution of flue gases This determination must be made on an individual installation basis and must take into consideration the overall volume of t...

Page 25: ...himney the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into the chimney The following requirements are provided for a safe venting system a Ensur...

Page 26: ...y harm An internal filter rack located in the blower compartment is provided as standard equipment with this furnace A sufficient clearance should be provided for air filter access Refer to Table 2 fo...

Page 27: ...rner problem If the furnace is in the oil mode with both the AUTO RELIEF and OIL lights on there is a problem with the electrical system Twelve hours following detection of AUTO RELIEF the furnace wil...

Page 28: ...rformance from the oil burner the following set up procedures must be followed by referring to the Technical Specifications Table 2 in this manual 1 A test kit to measure the smoke flue draft and over...

Page 29: ...unction of the furnace and cause premature wear of the heat exchanger CAUTION Modification of the factory set limits will void the warranty 3 2 7 BVSO performance test The purpose of the following tes...

Page 30: ...lace an element follow the steps below 1 Disconnect the 2 wires attached to the element 2 Remove the metal screws that hold the frame on the drawer bottom of the drawer 3 Remove the frame by unscrewin...

Page 31: ...rvice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F A...

Page 32: ...le 100 PSIG pump pressure Delavan 0 65 80W 0 75 80W 0 85 80W Combustion air adjustment shutter band 0 7 1 4 0 9 ELECTRICAL SYSTEM Volts Hertz Phase 240 120 60 1 Control transformer 40 VA BLOWER DATA B...

Page 33: ...E A R A N C E S F U RN A CE 15 c m 6 S U P P LY P L E N U M 5 c m 2 O T HE R S I DE F U RN A CE 60 c m 24 B A C K F U RN A CE 60 c m 24 T O P F U RN A CE O R P LE NU M 5 c m 2 B O T T O M F U RN A CE...

Page 34: ...14 Figure 3 Location of main componants Figure 4 Location of element drawer DNS 0202 R v C DNS 0209 R v A...

Page 35: ...15 Figure 5 Element drawer removal...

Page 36: ...16 Figure 6 Electrical Diagram...

Page 37: ...17 Figure 7 Parts List B50047 Rev A...

Page 38: ...ation 29 B02305 Holding plate 30 B02301 Breech plate gasket 31 B02311 Breech plate 32 B02312 Sound trap ass y 33 F07O001 Hex nut brass 34 Z99F050 Recessed handle black 35 Z04F010 Paper filter 16 x 20...

Page 39: ...70 B01154 Acces door 71 B01095 Electrical element ass y 72 A00207 11 Red w ire 73 A00201 19 Black w ire 74 L04J002 Cable clamp 75 B01123 03 Element draw er 76 B01123 01 Element draw er 77 B01123 02 El...

Page 40: ...20...

Reviews: