background image

 

 

6

 

 

 

2.2.2 Upflow Installation 

 
When the furnace is installed in the downflow position on a 
combustible floor, the clearances from combustibles must 
be adhered to. The downflow base DFB-104 or 
KLASB1001DET can be used to ensure these clearances. 
Refer to  figure 3 and the installation instructions provided 
with the base. 

 

The burner must always be installed in the same manner, 
regardless of the discharge position of the furnace. Refer 
to figure 3 for additional details. 
 

Figure 3  -   Downflow Installation 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.3.5 

Horizontal 

Installation 

 

When the furnace is installed in the horizontal position, 
either suspended or on a combustible floor with a choice of 
right or left discharge, the clearances from combustible 
material must be adhered to. If the unit is installed on a 
combustible floor, the horizontal floor base HFB-101 or 
KLASB0701DET can be used to ensure these clearances. 
Refer to the instructions supplied with the base. 

 

The burner must always be installed in the same manner, 
regardless of the discharge position of the furnace. Refer 
to figure 4 for additional details. 
 

Figure 4  -   Horizontal Installation 

 
 
 
 
 
 

2.3 ELECTRICAL

 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted 
ground to minimize the risk of bodily harm, if ever an 
electrical problem develops. A green ground screw is 
supplied with the control box for that purpose.

  

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local 
codes. 

 

The control system depends on the correct polarity of 
the power supply. Connect “HOT” wire (H) and 
“NEUTRAL” wire (N) as shown in figures 10 and 11. 

 

A separate line voltage supply should be used, with 
fused disconnect switch or circuit breaker, between the 
main power panel and the unit. 

 

Only copper wire may be used for the 115V circuit on 
this unit. If wires need to be changed, the replacements 
must have the same temperature resistance as the 
originals. 
 

2.4 INSTALLATION

 

OF

 

THE

 

THERMOSTAT 

A thermostat must be installed to control the 
temperature of the area to be heated. Follow the 
instructions supplied with the thermostat. Also refer to 
the wiring diagrams provided with the heating/air 
conditioning unit. The connections must be made as 
indicated on the following diagrams and the wiring 
diagrams, figures 10 and 11. 

 

Figure 5  -   Thermostat wiring, heating and air 

conditioning with 4-speed motor 

 

 

 
 
 
 
 
 
 
 

 

Filter 24 x 24 

Downflow base is 
required for 
combustible floor 

Burner position 

DNS-1227A 

Horizontal floor base 
required for combustible 

Burner position 

Filter 24 x 24 

DNS-1227A 

Summary of Contents for OMF154L20A

Page 1: ...FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper w...

Page 2: ...NEY VENTING 8 2 8 COMBUSTION AIR SUPPLY AND VENTILATION 8 2 9 OIL TANK 9 2 10 DUCTING 9 2 11 SUPPLY AIR ADJUSTMENTS 4 SPEED MOTORS 9 2 12 SUPPLY AIR ADJUSTMENTS ECM VARIABLE SPEED MOTORS 10 2 13 INSTA...

Page 3: ...urnace Dimensions 18 Figure 10 Wiring diagram 4 speed motor PSC 19 Figure 11 Wiring diagram variable speed motor ECM 20 Figure 12 Parts list with 4 speed motor PSC 21 Figure 13 Parts list with variabl...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to pre...

Page 6: ...ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance...

Page 7: ...lect nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 Air and Turbulator Settings Before starting the burner for the first time adjust the...

Page 8: ...of the cool down cycle If the test is not in line with the above call a QUALIFIED SERVICE TECHNICIAN 2 8 COMBUSTION AIR SUPPLY AND VENTILATION WARNING Poisonous carbon monoxide gas hazard Comply with...

Page 9: ...indoor pools c Furnaces installed near chemical storage areas The installation must carefully be verified to ensure that the combustion air comes from outside 2 10 1 Air filter A properly sized air f...

Page 10: ...ier on the HUM terminal It supplies 120 VAC electric power when the burner is in operation A 24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a...

Page 11: ...ing drawn into the suction side of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted acco...

Page 12: ...duct just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 The temperature rise is calculated by subtracting the return...

Page 13: ...exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the bu...

Page 14: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 15: ...Canadian regulation 86 7 85 3 86 7 85 3 AFUE From ASHRAE 103 standard and US regulation 86 3 85 0 86 3 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for w ire sizing Amps Max fuse size Am...

Page 16: ...ShortRun On Delay CFM Level Time Off Delay CFMLevel Time A 1 OFF 2 OFF 0 90 13 90 sec 31 30 sec 50 4 min B 1 ON 2 OFF 1 10 13 60 sec 31 30 sec 38 5 min C 1 OFF 2 ON ALL 13 90 sec 31 30 sec 56 5 min D...

Page 17: ...OF FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN...

Page 18: ...18 Figure 9 Furnace Dimensions...

Page 19: ...19 Figure 10 Wiring diagram 4 speed motor PSC...

Page 20: ...20 Figure 11 Wiring diagram variable speed motor ECM...

Page 21: ...21 Figure 12 Parts list with 4 speed motor PSC B500111A...

Page 22: ...WIRE CHANNEL INT 30 B03829 BLOWER DIVIDER 31 B03838 BLOWER SLIDE One blower slide included 32 B03835 02 LATERAL BAFFLE 33 B03867 01 FILTER RACK KIT 34 B03828 FLOOR 35 B03855 02 SIDE PANEL ASSEMBLY LE...

Page 23: ...23 Figure 13 Parts list with variable speed motor ECM B50112A...

Page 24: ...NNEL INT 29 B03829 BLOWER DIVIDER 30 B03838 BLOWER SLIDE One blower slide included 31 B03835 02 LATERAL BAFFLE 32 B03867 01 FILTER RACK KIT 33 B03828 FLOOR 34 B03855 02 SIDE PANEL ASSEMBLY LEFT Panel...

Reviews: