background image

 

 

8

 

 

 

chimney into which a solid fuel burning furnace is already 
being vented. 

 

Before venting this furnace into a chimney, its condition must 
be checked and repairs made, if necessary. Also, the chimney 
lining and dimensions must conform to local and national 
codes. 

 

2.6.2  Factory Built Chimneys

 

Oil fired furnaces are approved for use with “L” type vents. The 
unit may also be used with an approved chimney of proper 
dimensions and temperature ratings as specified in the 
installation code. Refer to chimney manufacturer’s instructions 
for proper installation. 

2.6.3 Draft Regulator 

It is recommended that a draft regulator be installed in cases 
where the draft is either high or variable due to external 
conditions. Follow the instructions provided with the regulator.

 

 

2.6.4 Side-wall Venting 

 

The heating unit is approved for side-wall venting. This system 
includes model VTK-3 / KLAVT0201DET side-wall venter and 
a 5” insulated vent pipe, model IFV5 / KLAFVxx01DET. Refer 
to the installation instructions provided with the venting system. 

2.7 BLOCKED

 

VENT

 

SHUT-OFF

 

DEVICE

 

(BVSO)

 

FOR

 

CHIMNEY

 

VENTING 

CAUTION 

It is imperative that this device be installed by a qualified service 
technician. 

 

A positive pressure venting system (Sealed Combustion System 
or Direct Vent) 

MUST NOT

 use the BVSO. Follow the 

instructions supplied with the venting system. 

 

This device is designed to detect the insufficient evacuation of 
combustion gases in the event of a vent blockage. In such a 
case the thermal switch will shut down the oil burner. The 
device will then need to be re-armed MANUALLY. 

 

Refer to the detailed instructions and wiring diagrams supplied 
with the BVSO for the installation and wiring procedures. The 
length of wires supplied with the unit is such that the safety 
device must be installed between the flue outlet of the 
appliance and the draft regulator, as indicated in the 
instructions. 

 

It is also essential that the BVSO be maintained annually. For 
more details refer to the instructions supplied with the device 
itself, as well as Section 3. of this Manual. 
 

2.7.1  BVSO Performance Test 

 

The purpose of the following test is to check that the electrical 
outlet on the furnace, designated to the BVSO, is functional. 

 

1.  Start up the burner; 
2.  Remove the three-pole plug from the BVSO outlet on the 

furnace; 

3.  The burner must shut-off immediately, while the blower 

continues to run to the end of the cool-down cycle. 

 

If the test is not in line with the above, call a QUALIFIED 
SERVICE TECHNICIAN. 

 

2.8 COMBUSTION

 

AIR

 

SUPPLY 

AND

 

VENTILATION 

 

WARNING

 

 

Poisonous carbon monoxide gas hazard. 

 

Comply with NFPA 31 (U.S.) and CSA B139 (Canada) 
standards for the installation of Oil Burning 
Equipment and applicable provisions of local building 
codes to provide combustion and ventilation air. 

 

Failure to provide adequate combustion and 
ventilation air can result in death, bodily injury and/or 
property damage. 

 

Oil furnaces must have an adequate supply of combustion 
air. It is common practice to assume that older homes 
have sufficient infiltration to accommodate the combustion 
air requirement for the furnace. However, home 
improvements such as new windows, doors, and weather 
stripping have drastically reduced the volume of air 
infiltration into the home.

 

 

Refer to oil furnace installation codes relative to 
combustion and ventilation air requirements. Consult 
Section 2.2 in this manual, specifically for units installed in 
an enclosed space.  

 

Home air exhausters are common. Bathroom and kitchen 
fans, power vented clothes dryers and water heaters all 
tend to create a negative pressure condition in the home. 
Should this occur the chimney becomes less and less 
effective and can easily downdraft. In certain cases, 
mechanically supplied air, by way of a blower, interlocked 
with the unit, is necessary. It is the installer’s responsibility 
to check that. 

2.8.1 

Contaminated Combustion Air  

Installations in certain areas or types of structures will 
increase the exposure to chemicals or halogens that may 
harm the furnace. These conditions will require that only 
outside air be used for combustion. 

 

The following areas or types of structures may contain or 
be exposed to certain substances, potentially requiring 
outside air for combustion: 

 

a. Commercial 

buildings; 

b.  Buildings with indoor pools; 
c. 

Furnaces installed near chemical storage areas. 

 

Exposure to the following substances: 
a.  Permanent wave chemicals for hair; 
b.  Chlorinated waxes and cleaners; 
c. 

Chlorine based swimming pool chemicals; 

d.  Water softening chemicals; 
e.  De-icing salts or chemicals; 
f. Carbon 

Tetrachloride; 

g.  Halogen type refrigerants; 
h.  Cleaning solvents (such as perchloroethylene); 
i. 

Printing inks, paint removers, varnishes, etc. ; 

j. Hydrochloric 

acid; 

k. 

Solvent based glue; 

l. 

Antistatic fabric softeners for clothes dryers; 

m.  Acid based masonry cleaning materials. 

2.8.2  Burner with Outdoor Combustion Air Kit

 

Certain burners are designed to function with combustion 
air taken directly from the outside. Follow the instructions 

Summary of Contents for OMF154L20A

Page 1: ...FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper w...

Page 2: ...NEY VENTING 8 2 8 COMBUSTION AIR SUPPLY AND VENTILATION 8 2 9 OIL TANK 9 2 10 DUCTING 9 2 11 SUPPLY AIR ADJUSTMENTS 4 SPEED MOTORS 9 2 12 SUPPLY AIR ADJUSTMENTS ECM VARIABLE SPEED MOTORS 10 2 13 INSTA...

Page 3: ...urnace Dimensions 18 Figure 10 Wiring diagram 4 speed motor PSC 19 Figure 11 Wiring diagram variable speed motor ECM 20 Figure 12 Parts list with 4 speed motor PSC 21 Figure 13 Parts list with variabl...

Page 4: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 5: ...designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to pre...

Page 6: ...ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance...

Page 7: ...lect nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 Air and Turbulator Settings Before starting the burner for the first time adjust the...

Page 8: ...of the cool down cycle If the test is not in line with the above call a QUALIFIED SERVICE TECHNICIAN 2 8 COMBUSTION AIR SUPPLY AND VENTILATION WARNING Poisonous carbon monoxide gas hazard Comply with...

Page 9: ...indoor pools c Furnaces installed near chemical storage areas The installation must carefully be verified to ensure that the combustion air comes from outside 2 10 1 Air filter A properly sized air f...

Page 10: ...ier on the HUM terminal It supplies 120 VAC electric power when the burner is in operation A 24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a...

Page 11: ...ing drawn into the suction side of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted acco...

Page 12: ...duct just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 The temperature rise is calculated by subtracting the return...

Page 13: ...exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the bu...

Page 14: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 15: ...Canadian regulation 86 7 85 3 86 7 85 3 AFUE From ASHRAE 103 standard and US regulation 86 3 85 0 86 3 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for w ire sizing Amps Max fuse size Am...

Page 16: ...ShortRun On Delay CFM Level Time Off Delay CFMLevel Time A 1 OFF 2 OFF 0 90 13 90 sec 31 30 sec 50 4 min B 1 ON 2 OFF 1 10 13 60 sec 31 30 sec 38 5 min C 1 OFF 2 ON ALL 13 90 sec 31 30 sec 56 5 min D...

Page 17: ...OF FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN...

Page 18: ...18 Figure 9 Furnace Dimensions...

Page 19: ...19 Figure 10 Wiring diagram 4 speed motor PSC...

Page 20: ...20 Figure 11 Wiring diagram variable speed motor ECM...

Page 21: ...21 Figure 12 Parts list with 4 speed motor PSC B500111A...

Page 22: ...WIRE CHANNEL INT 30 B03829 BLOWER DIVIDER 31 B03838 BLOWER SLIDE One blower slide included 32 B03835 02 LATERAL BAFFLE 33 B03867 01 FILTER RACK KIT 34 B03828 FLOOR 35 B03855 02 SIDE PANEL ASSEMBLY LE...

Page 23: ...23 Figure 13 Parts list with variable speed motor ECM B50112A...

Page 24: ...NNEL INT 29 B03829 BLOWER DIVIDER 30 B03838 BLOWER SLIDE One blower slide included 31 B03835 02 LATERAL BAFFLE 32 B03867 01 FILTER RACK KIT 33 B03828 FLOOR 34 B03855 02 SIDE PANEL ASSEMBLY LEFT Panel...

Reviews: