background image

 

1.2) 

INSTALLATION 

 

This  unit  must  be  installed  by  a  qualified,  professional 
installer  in  accordance  with  these  instructions  and  CSA 
B139  section  4.3.  If  improperly  installed,  a  hazardous 
condition could result. 
 
The  power  venter  shall  not  be  installed  on  incinerators, 
incinerating  toilets,  condensing  type  appliances  or  solid 
fuel burning appliances. 
 
The  installation  shall be in accordance with the existing 
codes  and  regulations  established  by  the  authorities 
having jurisdiction. 
 
The venting unit may be installed through a combustible 
wall with a maximum thickness of 8 inches or through a 
non-combustible  wall  of  16  inches  including  a 
combustible exterior wall of no more than 8 inches. The 
minimum wall thickness is 2 inches. A type B vent shall 
not be used in the venting system. 
 
 

1.2.1)  General installation guidelines 

 

The first step in installing the power venter is to find the 
location that is in accordance with the following criteria: 
 

 

The flue discharge terminal of the venting system 
shall  be  installed  not  less  than  7  feet  above  any 
paved driveway or paved walkway; 

 

A power venting system shall not terminate within 
6  feet  of  a  mechanical  air  supply  inlet  to  any 
building including soffit opening or within 6 feet of 
a window, door or property line; 

 

The  flue  discharge  terminal  shall  not  be  installed 
within 3 feet horizontally of the vertical center-line 
above a gas meter/regulator assembly; 

 

The  venting  system  discharge  terminal  shall  not 
be installed less than 1 foot above grade level; 

 

The  discharge  of  the  flue  gases  shall  not  be 
above a paved sidewalk or paved driveway which 
is  located  between  two  buildings  where  their  use 
is common to both buildings; 

 

The  vent  terminal  shall  be  installed  such  a  way  
that  the  flue  gases  do  not  jeopardize  people, 
overheat  combustible  structures  or  enter  any 
openings of surrounding building within 6 feet; 

 

The vent terminal shall not be within 6 feet of any 
gas service regulator vent outlet or within 3 feet of 
any oil tank vent or oil tank fill inlet; 

 

The  vent  terminal  shall  not  be  less  than  6  feet 
from  an  adjacent  building  or  closer  than  3  feet  to 
an inside corner of an L shaped structure; 

 

The  vent  terminal  shall  not  be  less  than  6  feet 
from another combustion appliance air intake; 

 

The  bottom  of  the  vent  termination  shall  not  be 
installed less than 1 foot above any surface where 
snow, ice or debris may accumulate; 

 

The  vent  termination  shall  not  be  located  such  a 
way  that  damage  is  caused  to  the  brick  work, 
mortar,  wood  or  other  components  of  the  con-
struction by flue gas condensate or temperature; 

 

The  vent  termination  shall  not  be  located 
underneath a veranda, porch or deck. 

 
 

1.3) 

List of components 

 
Please consult Figure 1. The parts being shipped with 
the power venter are: 

a.  The "Fan-motor" assembly (stainless steel casing). 

Part number SWV-1M-2S or SWV-2M-2S; 

b.  A  junction  box  with  a  pressure  switch,  factory 

mounted. Part number R99F001; 

c.  A  3  to  6  inch  flue-pipe  reducer  with  integrated 

back-flow damper. Part number FD-02; 

d.  A  6  to  5  inch  fitting;  for  SMH-3  kit  only.  Part 

number Z07F010; 

e.  A  6  to  8  inch  fitting;  for  SMH-5  kit  only.  Part 

number Z07F005. 

 
 

1.4) 

Power venter installation 

 
Verify if the power venter is correctly sized according to 
Table 1. All appliances must enter the vent system on 
the inlet side of the power venter. 
 
You  must  install  a  barometric  draft  regulator  in 
accordance  with  your  heating  unit  instruction  manual. 
See Figure 1. 
 
 

Summary of Contents for SMH-1-BR

Page 1: ...ied service technician Save these instructions for future reference Printed in Canada Printed on 100 recycled paper SIDEWALL VENTER Models SMH 1 DE SMH 6 DE SMH 3 DE SMH 4 DE SMH 5 DE SMH 1 BR SMH 4 B...

Page 2: ......

Page 3: ...reech of the heating unit and the power venter inlet This distance is the linear sum of all vertical and horizontal connecting pipes with a maximum of 4 90o elbows See Figure 1 Therefore the maximum e...

Page 4: ...ed between two buildings where their use is common to both buildings The vent terminal shall be installed such a way that the flue gases do not jeopardize people overheat combustible structures or ent...

Page 5: ...1 50 SWV 2M 2S SMH 4 DE Beckett or Riello HMS 027 to 035 6 0 65 to 0 85 SWV 1M 2S SMH 1 DE Beckett or Riello HMS 041 to 062 6 1 00 to 1 50 SWV 2M 2S SMH 4 DE Beckett or Riello AMP 075 to 105 5 0 50 to...

Page 6: ...inside wall as closely as possible to the location where the vent pipe enters this wall Secure the junction box to the wall with two screws ensuring that the pressure switch is vertical If the wall i...

Page 7: ...specified in Figures 5A to 5M With this arrangement the command to the power venting system will come from the heating unit through its operational control to the power venter motor When a steady stat...

Page 8: ...st The installer must verify if the ignition of the burner is smooth when the heating unit operation is interrupted by means of the thermostat limit control or the power venter proving switch If the i...

Page 9: ...m the vent before operation To access the blower wheels remove the fan motor assembly cover and remove the blower wheels by unscrewing the attachment to the blower 3 1 3 Pressure switch The pressure s...

Page 10: ...DNS 0225 Rev A DNS 0226 Rev A FIGURE 1 SMH system General arrangement FIGURE 2 Main system dimensions...

Page 11: ...11 DNS 0229 Rev A DNS 0227 Rev A DNS 0228 Rev A FIGURE 3 Location of the SMH system on the wall Installation on a COMBUSTIBLE wall FIGURE 4A Installation on a NON COMBUSTIBLE wall FIGURE 4B...

Page 12: ...12 DNS 0230 Rev C DNS 0397 Rev C FIGURE 5A AMI AMT IM and OLS 2 speeds Beckett or Riello AMT SM and OLS 2 speeds Beckett FIGURE 5B...

Page 13: ...13 DNS 0231 Rev C DNS 0232 Rev C FIGURE 5C AMI and HE 1 speed Beckett FIGURE 5D AMI and HE 1 speed Riello...

Page 14: ...14 DNS 0407 Rev C FIGURE 5E AMT SM and OSR 2 speeds Riello...

Page 15: ...15 FIGURE 5F AMP and OMB Riello...

Page 16: ...16 FIGURE 5G AMP and OMB Beckett DNS 0622 Rev A...

Page 17: ...17 FIGURE 5H FIGURE 5I DNS 0238 Rev B LO 1MQH LO 2M FBR 1 LO 1M3M MBP MBP F MBP 2 CCC and MBP U BRF and BFF DNS 0239 Rev B...

Page 18: ...18 FIGURE 5J FIGURE 5K DNS 0233 Rev D DNS 0234 Rev D FIGURE 5J HMT HML HMI and HMD with triple aquastat Beckett or Riello HMR HML HMT HMI and HMD with double aquastat Beckett...

Page 19: ...19 FIGURE 5L DNS 0235 Rev B DNS 0240 Rev C AME and HME Beckett FIGURE 5M Water heater CMO32 CMO50 30RB 32E2 50E2 IB 30 IB32 R and IB50 O Beckett...

Page 20: ...0 For SMH 4 SMH 5 and SMH 6 12 Cover support insulation B00733 13A Cover support B00705 For SMH 1 and SMH 3 13B Cover support B01074 For SMH 4 SMH 5 and SMH 6 14 Gasket outlet pipe B01150 Brown 1 15 G...

Reviews: