background image

1.

AC

– Air Conditioner provides approximately 400

CFM per ton for greater efficiency and humidity
control with the AC/HP CFM ADJUST set to the
nominal (NOM) tap. To achieve more or less than
400 CFM per ton, move tap to (HI) or (LO) position
respectively. Refer to appropriate airflow tables for
exact CFM setting.

2.

HP

-COMFORT – Heat Pump Comfort provides ap-

proximately 350 CFM per ton for higher than normal
heating air delivery temperature.

3.

HP

-EFF – Heat Pump Efficiency provides same

airflow for heating and cooling modes to increase
overall HP efficiency; approximately 400 CFM per
ton with the AC/HP CFM ADJUST set to the nomi-
nal (NOM) tap.

The factory setting is AC (Refer to Figure 10 and Figure
16).

2.6.4

AC/HP CFM adjust

Select Medium, Low, or High Airflow

To provide airflow at rates described above, the AC/HP
ADJUST select is factory set to the nominal (NOM) tap.
The adjust selections HI/LO will regulate airflow supplied
for all operational modes.
HI provides 10% airflow over nominal unit size selected
and LO provides 10% airflow below nominal unit size se-
lected.
Setting options are provided to adjust airflow supplied
to meet individual installation needs for such things as
noise, comfort, and humidity removal. (Refer to Figure
10 and Figure 16).

2.6.5

ON/OFF delay

Select desired time delay profile

NOTE:

Delay selections are active in cooling and heat

pump heating modes only. Electric heating modes have
a one (1) minute OFF delay at 50% airflow and zero (0)
ON delay programmed into the ECM motor that cannot
be overridden.

Four (4) motor operation delay profiles are pro-

vided to customize and enhance system operation. (Re-
fer to Figure 10 and Figure 16).
Selection options are:

1.

0/90

: No ON delay and 90 second OFF delay at

100% airflow (factory setting).

2.

30/90

: 30 second ON delay with no airflow and 90

second OFF delay at 100% airflow profile. Used
when it is desirable to allow system coils time to
heat-up/cool-down in conjunction with the airflow.

3.

0/0

: No delay option. Used for servicing unit or

when a thermostat is utilized to perform delay func-
tions.

4.

ENH

: enhanced selection provides a 30 second ON

delay with no airflow followed by 150 seconds at
70% airflow, and no OFF delay for added comfort.
This profile will minimize cold blow in heat pump
operation and could enhance system efficiency.

2.6.6

Continuous fan

NOTE:

If installed with a two-stage outdoor unit, do not

select HI speed continuous fan. If HI is selected, low
stage compression will also run HI fan speed possibly
resulting in insufficient dehumidification.

Select desired fan speed when thermostat is

set on continuous fan. (Refer to Figure 10 and Figure
16)

1.

LO speed

– factory setting, 50% cooling mode air-

flow.

2.

MED speed

– move connector to MED, 80% cool-

ing mode airflow.

3.

HI speed

– move connector to HI, 100% cooling

mode airflow.

2.6.7

Low-voltage circuit

Fusing and Reference

The low-voltage circuit is fused by a board-mounted 5-
amp automotive fuse placed in series with the trans-
former SEC2 and the R circuit.

The C circuit of the

transformer is referenced to chassis ground through a
printed circuit run at SEC1 connected to metal standoff
marked with ground symbol.

2.6.8

Basic furnace configuration

The following basic configuration of the furnace will pro-
vide ARI rated performance of an air conditioner:

1.

HEAT KW/CFM

– Select the heater range for the

size electric heater installed.

2.

AC/HP SIZE

– Select system size installed.

3.

SYSTEM TYP

E – Select system type AC

4.

AC/HP CFM ADJUST

– Select NOM.

5.

ON/OFF DELAY

– Select 0/90 profile.

6.

CONTINUOUS FAN

– Select desired fan speed

when thermostat is set to continuous fan.

The following basic configuration of the furnace will pro-
vide ARI rated performance of a heat pump:

1.

HEAT KW/CFM

– Select the heater range for the

size electric heater installed.

2.

AC/HP SIZE

– Select system size installed.

3.

SYSTEM TYPE

– Select system type HP-EFF

4.

AC/HP CFM ADJUST

– Select NOM.

5.

ON/OFF DELAY

– Select 0/90 profile.

6.

CONTINUOUS FAN

– Select desired fan speed

when thermostat is set to continuous fan.

7

Summary of Contents for SUPREME SUP A240V12 Series

Page 1: ...its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE IN STALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWN...

Page 2: ...mostat 9 3 3 6 Electric heating mode Communicating thermostat 9 3 3 7 Heat pump heating mode Modlating thermostat outdoor unit single stage 9 3 3 8 Heat pump heating mode Modulating thermostat outdoor...

Page 3: ...alified service technician immedi ately to assess the damage and to replace all criti cal parts that were in contact with water c Do not store gasoline or any other flammable sub stances such as paper...

Page 4: ...ample it is recommended to install the unit on a cement base 2 5 cm to 5 0 cm 1 to 2 thick In addition the heater should also be located close to the center of the air distribution system 2 2 CLEARANC...

Page 5: ...pted ground to minimize the risk of bodily harm A ground terminal is supplied with the control box for that purpose A connector is supplied on the ground terminal to ground an added accessory In the e...

Page 6: ...mode is comfort able and economical Generally speaking on a single stage thermostat a reading of the current must be taken with an ammeter as follows 1 Move the anticipator to its highest setting rend...

Page 7: ...d to operate prop erly with system components with which it is installed To successfully configure a system see information printed on circuit board label located next to select pins move the 6 select...

Page 8: ...t up cool down in conjunction with the airflow 3 0 0 No delay option Used for servicing unit or when a thermostat is utilized to perform delay func tions 4 ENH enhanced selection provides a 30 second...

Page 9: ...control will detect the humidistat contact opening on increasing humidity and reduce its airflow to approximately 80 of nominal cooling mode airflow This reduction will increase the system latent cap...

Page 10: ...o Y Y2 and R to O b Furnace delivers single stage cooling airflow 3 3 3 Cooling mode two stage First stage low cooling Thermostat closes cir cuits R to G R to O and R to Y1 Furnace delivers low stage...

Page 11: ...ir temperature from the supply air tempera ture If the temperature rise exceeds the temperature spec ified in Table 2 by 5 F 2 8 C move the AC HP CFM ADJUST black wire to high HI position If the exces...

Page 12: ...nt changes Dirty filters have an adverse ef fect on the performance of the central heating system 4 2 MOTOR LUBRICATION Do not lubricate the blower motor since it is permanently lubricated 5 FURNACE I...

Page 13: ...ected cooling delays Cooling 2 stages with Electric Heat Continous Fan G ON Fan ON at the selected continous fan CFM Fan switch ON OFF Fan OFF Thermostat calls for 1st stage Heat W1 ON Fan ON at 50 of...

Page 14: ...DH ON Compressor ON Fan ON after delays at 80 of the selected Cooling CFM OFF Compressor OFF Fan OFF after selected cooling delays Thermostat calls for 1st stage Heat Heat pump heating mode Y1 G ON Co...

Page 15: ...5 3 7 4 3 1 5 3 7 Electrical element 6 240V 208V Kw 4 3 1 5 3 7 Blower motor Consumption 240V 208V Amp Max 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 2 3 2 7 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heati...

Page 16: ...sides the back and below KOE Identical on the 2 sides Identique sur les 2 cot s KOE A 35mm 44mm 1 3 8 1 3 4 B 29mm 7 8 A B Identique sur les 2 cot s au dos et en dessous DNS1455 rev C 927mm 36 1 2 559...

Page 17: ...s 24VAC input to Y1 only Y Y2 not powered CONTINUOUS FAN CFM1 CFM1 CFM1 AC HP SIZE A C size CONTINUOUS FAN CONTINUOUS FAN CONTINUOUS FAN Selection TONS YELLOW wire position YELLOW wire position YELLOW...

Page 18: ...to Y1 only Y Y2 not powered CONTINUOUS FAN 24 VAC R input on G only CFM1 CFM1 CFM1 AC HP SIZE A C size CONTINUOUS FAN CONTINUOUS FAN CONTINUOUS FAN Selection TONS YELLOW wire position YELLOW wire pos...

Page 19: ...ON OFF DELAY Adjustment ON Delay OFF Delay WHITE wire position Time CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec DELAY PROFILE FOR ELECTRIC HEATING MODE...

Page 20: ...Figure 16 Electrical diagram SUPREME Advantage ECM ELECTRICAL DIAGRAM DIAGRAMME LECTRIQUE ADVANTAGE AVANTAGE ECM 19...

Page 21: ...rev E 31 12 15 16 17 11 6 8 9 18 19 20 21 22 13 14 7 10 REV DESCRIPTION A C DATE PAR A Nouveau dessin 21963 2015 03 24 F H B Changement disjoncteur CQC 22327 2015 05 19 F H C Ajoute support de filtre...

Page 22: ...upreme 15kw 21 B04284 Electrical sequencer kit Supreme 10kw 22 B04350 02 Top door 23 B04349 Bottom door assembly 24 B04357 01 Blower assembly Supreme 10 25kw 1 2hp ECM 25 B04357 02 Blower assembly Sup...

Reviews: