6
Figure 6: 1-stage thermostat with outdoor control for 2-
stage function, electric heating only
Figure 7: 1-stage thermostat, electric heat and cooling
application
Figure 8: 2-stage thermostat, electric heating and air
conditioning
2.5.2.
Ducts and filters
The ducts must be sized such a way as to accommodate the
specified airflow and the available static pressure. Refer to
the applicable local and/or national installation codes.
Insulate the ducts that lead through non-heated areas. Use
flexible supply and return air connectors to avoid the
transmission of vibration. To make the unit run even quieter,
the installer should:
1. Use two elbows between each outlet and the supply and
return air plenum;
2. Cover the vertical sections of the supply and return air
duct with soundproofing material;
3. Use baffles in short radius elbows;
4. Use flexible hangers to suspend the ducts.
The
SUPREME
furnace is equipped with a filter frame for the
blower compartment. It must be installed on the outside of
one of the three sides or the bottom of the furnace. Once
the location of the installation has been determined, use the
four square knockouts for ease of cutting the opening.
A heat pump or an air conditioner can be added to this
furnace, in either the supply or return air duct. Carefully
follow the instructions provided with these appliances to
ensure proper installation and hook-up to the electric
furnace. Refrigerant and drainage pipes must in no way
hinder access to the furnace panels.
2.6 SUPPLY
AIR
ADJUSTMENTS
On units equipped with 4-speed blower motors, the supply
air must be adjusted based on heating/air conditioning
output and the static pressure of the duct system. For the
desired airflow, refer to the Table 1 and 2, as well as the
Tables 4 and 5 for the airflow based on static pressure.
For the adjustment of the airflow on heating mode, to obtain
the temperature rise described in the technical specification
table (Table 3), the red wire must be positioned on the
terminal corresponding to the LOW, MED-LOW, MED-HIGH
or HIGH blower speed. Blower speeds are adjusted in
factory for 0.5 inch static pressure.
For the adjustment of the airflow on air-cooling mode, to
obtain a sufficient airflow (350 to 450 CFM per Ton), the blue
wire must be positioned on the terminal corresponding to the
LOW, MED-LOW, MED-HIGH or HIGH blower speed.
Blower speeds are adjusted in factory for 0.5 inch static
pressure.
Table 1: Supply air adjustment on heating mode
FURNACE
INPUT
POWER
KW
HP
MOTOR
STATIC
PRESSUR
E (in. w.c)
RECOMMENDE
D BLOWER
SPEED
0.2 LOW
SUP10 10 1/3
0.5 LOW
0.2 MED-LOW
SUP15 15 1/3
0.5 MED-LOW
0.2 MED-LOW
SUP18 18 1/3
0.5 MED-LOW
0.2 MED-LOW
SUP20 20 1/3
0.5 MED-HIGH
0.2 MED-HIGH
SUP23 23 1/3
0.5 MED-HIGH
0.2 MED-LOW
SUP20 20 1.0
0.5 MED-LOW
0.2 MED-LOW
SUP23 23 1.0
0.5 MED-LOW
0.2 MED-LOW
SUP27 27 1.0
0.5 MED-LOW
Table 2: Supply air adjustment on air cooling mode
FURNACE HP
MOTOR
COOLING
CAPACITY
(0.5” w.c.)
RECOMMENDED
BLOWER SPEED
1.5 LOW
2.0 MED-LOW
2.5 MED-HIGH
SUP10, 15, 18,
20 and 23
1/3
3.0 HIGH
2.5 LOW
3.0 MED-LOW
3.5 MED-HIGH
4.0 HIGH
SUP20, 23 and
27
1.0
5.0 HIGH
Summary of Contents for SUPREME SUP10-M2401A
Page 11: ...11 Figure 9 Furnace dimensions...
Page 12: ...12 Figure 10 Wiring diagram 3 wires 10 kW...
Page 13: ...13 Figure 11 Wiring diagram 3 wires 15 kW...
Page 14: ...14 Figure 12 Wiring diagram 3 wires 18 20 kW...
Page 15: ...15 Figure 13 Wiring diagram 3 wires 23 kW...