background image

 

 

6

Figure 6: 1-stage thermostat with outdoor control for 2-

stage function, electric heating only 

 
 
 
 
 
 
 
 
 

 

Figure 7: 1-stage thermostat, electric heat and cooling 

application 

 
 
 
 
 
 
 
 
 
 

 

Figure 8: 2-stage thermostat, electric heating and air 

conditioning 

 
 
 
 
 
 
 
 
 
 

 

2.5.2. 

Ducts and filters 

 
The ducts must be sized such a way as to accommodate the 
specified airflow and the available static pressure.  Refer to 
the applicable local and/or national installation codes. 
 
Insulate the ducts that lead through non-heated areas.  Use 
flexible supply and return air connectors to avoid the 
transmission of vibration.  To make the unit run even quieter, 
the installer should: 
1.  Use two elbows between each outlet and the supply and 

return air plenum; 

2.  Cover the vertical sections of the supply and return air 

duct with soundproofing material; 

3.  Use baffles in short radius elbows; 
4.  Use flexible hangers to suspend the ducts. 
 

The 

SUPREME

 furnace is equipped with a filter frame for the 

blower compartment.  It must be installed on the outside of 
one of the three sides or the bottom of the furnace.  Once 
the location of the installation has been determined, use the 
four square knockouts for ease of cutting the opening. 
 
A heat pump or an air conditioner can be added to this 
furnace, in either the supply or return air duct.  Carefully 
follow the instructions provided with these appliances to 
ensure proper installation and hook-up to the electric 
furnace.  Refrigerant and drainage pipes must in no way 
hinder access to the furnace panels. 

 
2.6 SUPPLY 

AIR 

ADJUSTMENTS

 

 
On units equipped with 4-speed blower motors, the supply 
air must be adjusted based on heating/air conditioning 
output and the static pressure of the duct system.  For the 
desired airflow, refer to the Table 1 and 2, as well as the 
Tables 4 and 5 for the airflow based on static pressure. 
 
For the adjustment of the airflow on heating mode, to obtain 
the temperature rise described in the technical specification 
table (Table 3), the red wire must be positioned on the 
terminal corresponding to the LOW, MED-LOW, MED-HIGH 
or HIGH blower speed.  Blower speeds are adjusted in 
factory for 0.5 inch static pressure. 
 
For the adjustment of the airflow on air-cooling mode, to 
obtain a sufficient airflow (350 to 450 CFM per Ton), the blue 
wire must be positioned on the terminal corresponding to the 
LOW, MED-LOW, MED-HIGH or HIGH blower speed.  
Blower speeds are adjusted in factory for 0.5 inch static 
pressure. 

 

Table 1: Supply air adjustment on heating mode 

 

FURNACE 

INPUT 

POWER 

KW 

HP 

MOTOR 

STATIC 

PRESSUR

E (in. w.c) 

RECOMMENDE

D BLOWER 

SPEED 

0.2 LOW 

SUP10 10  1/3 

0.5 LOW 
0.2 MED-LOW 

SUP15 15  1/3 

0.5 MED-LOW 
0.2 MED-LOW 

SUP18 18  1/3 

0.5 MED-LOW 
0.2 MED-LOW 

SUP20 20  1/3 

0.5 MED-HIGH 
0.2 MED-HIGH 

SUP23 23  1/3 

0.5 MED-HIGH 
0.2 MED-LOW 

SUP20 20  1.0 

0.5 MED-LOW 
0.2 MED-LOW 

SUP23 23  1.0 

0.5 MED-LOW 
0.2 MED-LOW 

SUP27 27  1.0 

0.5 MED-LOW 

 

Table 2: Supply air adjustment on air cooling mode 

 

FURNACE HP 

MOTOR 

COOLING 

CAPACITY  

(0.5” w.c.) 

RECOMMENDED  
BLOWER SPEED 

1.5 LOW 
2.0 MED-LOW 
2.5 MED-HIGH 

SUP10, 15, 18, 

20 and 23 

1/3 

3.0 HIGH 
2.5 LOW 
3.0 MED-LOW 
3.5 MED-HIGH 
4.0 HIGH 

SUP20, 23 and 

27 

1.0 

5.0 HIGH 

 

Summary of Contents for SUPREME SUP10-M2401A

Page 1: ...J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper MULTI POSITION INSTALLER SERVICE TECHNICIAN USE THE INF...

Page 2: ...8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 0 FURNACE INFORMATION 9 TABLES Table 1 Supply air adjustment on heating mode 6 Table 2 Supply air adjustment on air cooling mode 6 Table 3 Technical speci...

Page 3: ...tch or circuit breaker ii The air filter and how to change it check monthly and clean or replace if necessary f Before calling for service be sure to have the information of section 5 of your manual c...

Page 4: ...o clearance to combustible material regardless of the heating capacity 2 2 2 Supply air ducts Ducts for furnaces with a heating capacity up to and including 20 k W can be installed with a zero clearan...

Page 5: ...acement these must be copper wires only with same temperature rating as originals 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated...

Page 6: ...no way hinder access to the furnace panels 2 6 SUPPLY AIR ADJUSTMENTS On units equipped with 4 speed blower motors the supply air must be adjusted based on heating air conditioning output and the stat...

Page 7: ...door is in place and the blower rail locking screws are well tightened 3 The blower speed adjustments for heating and air conditioning are appropriate and according to the specifications in this manu...

Page 8: ...certain that the unit does not operate above the temperatures specified in the Technical Specifications Table 2 This is particularly important if a cooling coil or a heat pump has been installed in th...

Page 9: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 10: ...nd size Shipping weight Maximum cooling capacity ELECTRICAL SYSTEM GENERAL INFORMATION BLOWER DATA factory adjusted to a staic pressure of 0 5 W C 1 20 x 20 3 tons SUPxx M2401B 19 x 19 12 x 10 2 Calcu...

Page 11: ...11 Figure 9 Furnace dimensions...

Page 12: ...12 Figure 10 Wiring diagram 3 wires 10 kW...

Page 13: ...13 Figure 11 Wiring diagram 3 wires 15 kW...

Page 14: ...14 Figure 12 Wiring diagram 3 wires 18 20 kW...

Page 15: ...15 Figure 13 Wiring diagram 3 wires 23 kW...

Page 16: ...16 Figure 14 Wiring diagram 3 wires 27 kW...

Page 17: ...17 Figure 15 PARTS LIST Supreme with 1 3 HP and 1 HP motor SUPxx M2401A or SUPxx M2401B B50130A dwg...

Page 18: ...L 22A B04125 ELECTRICAL KIT 10kw 22B B04124 ELECTRICAL KIT 15kw 22C B04123 ELECTRICAL KIT 18 20kw 22D B04122 ELECTRICAL KIT 23 25kw 22E B04121 ELECTRICAL KIT 27kw 23 B04091 MOUNTING PLATE FOR ELECTRIC...

Reviews: