Technical data
Deutschmann Automation GmbH & Co. KG
32
UNIGATE Fieldbus Gateway CANopen® - ProfibusDP V. 2.3
26.8.11
9
Technical data
9.1
Device data
The technical data of the module is given in the table below.
No. Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP24 / IP67
Protection against foreign bodies
and water to IEC 529 (DIN 40050)
3
Cooling
Convection
No additional cooling required
4
Service life
10 years
5
Housing size
90 mm x 127 mm x 55 mm
W x H x D
6
Installation position
Any
7
Weight
0.3 kg
8
Operating temperature
0ºC... +45ºC (w/o forced convection)
0ºC... +65ºC (with forced convection)
9
Storage/transport temperature -40ºC ... +70ºC
10
Atmospheric pressure
during operation
during transport
795 hPa ... 1080 hPa
660 hPa ... 1080 hPa
11
Installation altitude
2000 m
4000 m
Unrestricted
Restricted -
Ambient temperature
40 ºC
12
Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
13
Particles / dirt
Sand and dust may not penetrate the device
14
External
power supply
10.8...30 V DC
Standard power supply unit to DIN
19240
15
Current consumption at
24 V DC
Typ. 120 mA
max 150 mA
At 10.8V.
typ. 350 mA
16
Power supply at the
Profibus interface
5 V DC / max. 50 mA
(max. 50 mA at
30 ºC ambient
temperature)
17
Reverse voltage protection
Yes
But does not function!
18
Short-circuit protection
Yes
19
Overload protection
Poly-switch
Thermal fuse
20
Undervoltage detection
(USP)
9 V DC
21
Emergency power supply
5 ms
Device fully operable
22
Insulation voltage
500 V DC
IEC 1131-2
Table 2: Technical data of the module