Implemented protocols in UNIGATE® EL
Deutschmann Automation GmbH & Co. KG
41
UNIGATE
®
fieldbus gateway UNIGATE
®
EL - DeviceNet
™
V. 1.0
22.6.17
15.2 Configuration options for the individual transport protocols
15.2.1
Parameter TCP response time (0 off 1..65 sec)
The TCP connection to the Ethernet interface can be monitored with this parameter.
If after the set response time no more data is received from the Ethernet interface the TCP con-
nection will be automatically disconnected and then rebuilt.
The response time can be set between 1-65 seconds. If the value is set to "0" (default), the para-
meters or the monitoring is inactive.
(EL)
Transport
protocol
Parameter
TCP
server
(port 23)
UDP
TCP
server
TCP
client
Modbus
TCP
server
Modbus
TCP
client
Universal
Modbus
TCP
server
Universal
Modbus
TCP client
(EL) IP address
UNIGATE
(EL) Subnet
mask
(EL) IP address
gateway
(EL) IP address
target
(EL) Send port
(dec)
(EL) Receive
port (dec)
(EL) TCP
response time
(0 off 1..65sec)
Modbus
Timeout (10ms)
RX Poll Retry
RX Poll Delay
(10 ms)
Req. 1-22
Slave ID
Req. 1-22 Mod-
bus Function
Req. 1-22
StartAdr (hex)
Req. 1-22
No of Points
(dec)
Req. 1-22
Fieldbus
Map Adr(Byte)