Hardware ports, switches and LEDs
Deutschmann Automation GmbH & Co. KG
27
UNIGATE
®
fieldbus gateway UNIGATE
®
EL - DeviceNet
™
V. 1.0
22.6.17
Switch positions
9.4.3
Termination (DeviceNet)
If the Gateway is operated as the first or last physical device in the DeviceNet, there must be a
bus termination at this Gateway. In order to do this, either a bus terminating resistor must be acti-
vated in the connector or the resistor (220
) integrated in the Gateway must be activated. In
order to do this, slide the slide switch to position ON. In all other cases, the slide switch must
remain in position OFF. Please refer to the general Fieldbus literature for further information on
the subject of bus termination.
9.4.4
DIP-switch
The DIP-switch is used to set the Node-ID and baud rate according to picture 3.
Picture 1: DIP-switch
Switch
postions
S4
Switch
postions
S5
Function
Description
D
D
Firmware-
Update
Ext.-Board
(Description see chapter 12)
E
E
Test mode
(Description see chapter 4.2)
Note:
This mode can only be terminated by a reboot.
F
F
Config mode
(Description see chapter 4.1)
Note:
This mode can only be terminated by a reboot.