Error handling
10 Error handling
10.1 Error handling at UNIGATE
®
EL
If the Gateway detects an error, the error is signalled by the “State“ LED lighting red and, simulta-
neously, the error number being indicated by means of LEDs “Error No.“ as shown in the table
below. A distinction can be made between two error categories:
Serious errors (1-5): In this case, the Gateway must be switched off and switched back on again.
If the error occurs again, the Gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
For user-defined errors the flash frequency is 0.5 hertz. The error is displayed as long as defined
by "Set Warning Time".
In the configuration mode these displays are not valid and only meant for internal use.
Table 1: Error handling at UNIGATE
®
EL
LED8 LED4 LED2 LED1
Error no.
resp. ID
Error description
System error (2x/sec)
Error description with
Universal Script-EL (Delivery
status)
User error (1x/sec)
0
0
0
0
0
Reserved
0
0
0
1
1
Hardware fault
0
0
1
0
2
EEROM error
0
0
1
1
3
Internal memory error
CL hardware not supported
0
1
0
0
4
Fieldbus hardware error or
wrong Fieldbus-ID
0
1
0
1
5
Script error
Hardware for "Universal EL"
script not supported
0
1
1
0
6
Reserved
unknown protocol
0
1
1
1
7
RS-transmit buffer overflow
1
0
0
0
8
RS-receive buffer overflow
1
0
0
1
9
RS timeout
Modbus TCP (server) Timeout
response
Modbus TCP client: no response
from server
1
0
1
0
10
General fieldbus error*
1
0
1
1
11
Parity-or frame-check-error
Modbus TCP (server) response
error
1
1
0
0
12
Reserved
Modbus TCP client Universal
1
1
0
1
13
Fieldbus configuration error
1
1
1
0
14
Fieldbus data buffer overflow Modbus TCP (server)
1
1
1
1
15
Reserved
Modbus TCP (client) general
error
general script error*