background image

Customer Documentation DEV 5071  

64 

 Copyright DEV Systemtechnik GmbH 2007-2017 

 

Country-
code 

Coordinates 

Time Zone 

Comments 

NA 

-2234+01706 

Africa/Windhoek 

 

NC 

-2216+16627 

Pacific/Noumea 

 

NE 

+1331+00207 

Africa/Niamey 

 

NF 

-2903+16758 

Pacific/Norfolk 

 

NG 

+0627+00324 

Africa/Lagos 

 

NI 

+1209-08617 

America/Managua 

 

NL 

+5222+00454 

Europe/Amsterdam 

 

NO 

+5955+01045 

Europe/Oslo 

 

NP 

+2743+08519 

Asia/Kathmandu 

 

NR 

-0031+16655 

Pacific/Nauru 

 

NU 

-1901-16955 

Pacific/Niue 

 

NZ 

-3652+17446 

Pacific/Auckland 

most locations 

NZ 

-4357-17633 

Pacific/Chatham 

Chatham Islands 

OM 

+2336+05835 

Asia/Muscat 

 

PA 

+0858-07932 

America/Panama 

 

PE 

-1203-07703 

America/Lima 

 

PF 

-1732-14934 

Pacific/Tahiti 

Society Islands 

PF 

-0900-13930 

Pacific/Marquesas 

Marquesas Islands 

PF 

-2308-13457 

Pacific/Gambier 

Gambier Islands 

PG 

-0930+14710 

Pacific/Port_Moresby 

 

PH 

+1435+12100 

Asia/Manila 

 

PK 

+2452+06703 

Asia/Karachi 

 

PL 

+5215+02100 

Europe/Warsaw 

 

PM 

+4703-05620 

America/Miquelon 

 

PN 

-2504-13005 

Pacific/Pitcairn 

 

PR 

+182806-0660622  America/Puerto_Rico 

 

PS 

+3130+03428 

Asia/Gaza 

Gaza Strip 

PS 

+0350542 Asia/Hebron 

West Bank 

PT 

+3843-00908 

Europe/Lisbon 

mainland 

PT 

+3238-01654 

Atlantic/Madeira 

Madeira Islands 

PT 

+3744-02540 

Atlantic/Azores 

Azores 

PW 

+0720+13429 

Pacific/Palau 

 

PY 

-2516-05740 

America/Asuncion 

 

QA 

+2517+05132 

Asia/Qatar 

 

RE 

-2052+05528 

Indian/Reunion 

 

RO 

+4426+02606 

Europe/Bucharest 

 

RS 

+4450+02030 

Europe/Belgrade 

 

RU 

+5443+02030 

Europe/Kaliningrad 

Moscow-01 - Kaliningrad 

RU 

+5545+03735 

Europe/Moscow 

00 - west Russia 

RU 

+4844+04425 

Europe/Volgograd 

00 - Caspian Sea 

RU 

+5312+05009 

Europe/Samara 

00 - Samara, Udmurtia 

RU 

+5651+06036 

Asia/Yekaterinburg 

02 - Urals 

RU 

+5500+07324 

Asia/Omsk 

03 - west Siberia 

RU 

+5502+08255 

Asia/Novosibirsk 

03 - Novosibirsk 

RU 

+5345+08707 

Asia/Novokuznetsk 

03 - Novokuznetsk 

RU 

+5601+09250 

Asia/Krasnoyarsk 

04 - Yenisei River 

RU 

+5216+10420 

Asia/Irkutsk 

05 - Lake Baikal 

RU 

+6200+12940 

Asia/Yakutsk 

06 - Lena River 

RU 

+1353314 Asia/Khandyga 

06 - Tomponsky, Ust-
Maysky 

RU 

+4310+13156 

Asia/Vladivostok 

07 - Amur River 

RU 

+4658+14242 

Asia/Sakhalin 

07 - Sakhalin Island 

RU 

+1431336 Asia/Ust-Nera 

07 - Oymyakonsky 

RU 

+5934+15048 

Asia/Magadan 

08 - Magadan 

RU 

+5301+15839 

Asia/Kamchatka 

08 - Kamchatka 

RU 

+6445+17729 

Asia/Anadyr 

08 - Bering Sea 

RW 

-0157+03004 

Africa/Kigali 

 

SA 

+2438+04643 

Asia/Riyadh 

 

SB 

-0932+16012 

Pacific/Guadalcanal 

 

SC 

-0440+05528 

Indian/Mahe 

 

SD 

+1536+03232 

Africa/Khartoum 

 

SE 

+5920+01803 

Europe/Stockholm 

 

SG 

+0117+10351 

Asia/Singapore 

 

Summary of Contents for 5071

Page 1: ... DEV 5071 High Power DC Supply DEV Systemtechnik GmbH Grüner Weg 4A 61169 Friedberg GERMANY Tel 49 6031 6975 100 Fax 49 6031 6975 114 support dev systemtechnik com www dev systemtechnik com Revision 2017 12 19 DEV 91 0073 C ...

Page 2: ...les 14 4 2 4 Reboot of the Device and Restore of the Factory Default Settings 15 4 3 Device Factory Settings 16 4 3 1 Factory Settings for the Power Supply and Limits Information 16 4 3 2 Factory Default Network Settings 17 4 3 3 Factory Default SNMP Settings 17 4 4 Communication Interface Configuration 18 4 4 1 Serial Interface 18 4 4 2 Ethernet Interface 18 4 4 2 1 Ethernet Connection 18 4 4 2 2...

Page 3: ... 4 2 5 2 application channelTable channelEntry channelOn 44 5 5 4 2 5 3 application channelTable channelEntry channelACInputStatus 45 5 5 4 2 5 4 application channelTable channelEntry channelTempWarning 45 5 5 4 2 5 5 application channelTable channelEntry channelFanStatus 45 5 5 4 2 5 6 application channelTable channelEntry channelOutVoltageSet 45 5 5 4 2 5 7 application channelTable channelEntry ...

Page 4: ...n 52 6 1 1 Power Supply Errors 52 6 1 2 Fan Errors 52 6 1 3 Other Errors 52 7 CONNECTORS 53 8 TECHNICAL DATA 54 9 OPTIONS 54 10 SPARE PARTS 54 11 CONFORMANCE DECLARATIONS 54 11 1 Certificate of Conformance 54 11 2 EU Declaration of Conformity 57 12 GLOSSARY 58 13 TABLE OF TIME ZONES 59 14 NOTES 67 APPENDIX A DATA SHEET DEV 5071 ...

Page 5: ...21 and Option 22 B 19 DEC 2013 WP Complete rework C 19 DEC 2017 WP Minor changes 2 INTRODUCTION Thank you for purchasing a DEV 5071 High Power DC Supply This customer documentation is intended to familiarize you with the installation and operation of the device The DEV 5071 chassis for professional use can be equipped with one to four power supply modules thus realizing a reliable powerful and usu...

Page 6: ...t of the product DEV Systemtechnik warrants that the software and firmware designated by DEV Systemtechnik for use with the product will execute its programming instructions if installed properly DEV Systemtechnik does not warrant that the operation of the product software or firmware will be uninterrupted or error free 2 2 LIMITATION OF WARRANTY The preceding warranty does not apply to defects re...

Page 7: ...5 4 is included in the delivery of the device The Web Interface provides features for checking the health status of the device and for changing specific parameters The implementation of SNMP Simple Network Management Protocol via the Ethernet interface is intended for the remote surveillance and control of the device chapter 5 5 3 1 2 Other Options By default the product is delivered with 3 power ...

Page 8: ... handling of a power supply module chapter 4 2 3 AC LED 3 This green LED being lit indicates whether the AC connection of the corresponding power supply module is supplied with AC If the LED is blinking the input voltage is out of range DC LED 4 This green LED being lit indicates that the power supply module is delivering DC to the output terminals of the device If the LED is blinking an overload ...

Page 9: ...manages the surveillance and control functionality 4 5 6 Ethernet RS 232 Reset Ethernet connector 5 This interface is used for the communication via Web Interface or via SNMP Please refer to chapter 4 4 2 for the configuration of the interface RS 232 connector 4 The serial interface can be used for changing the network setup chapter 4 4 2 2 Reset button 6 The reset push button of the CPU module ca...

Page 10: ...AUTION HAZARDO US ENERGY BEHIND COVER CAUTION HOT SURFACE 1 9 10 8 7 3 2 4 5 6 Ethernet RS 232 Reset 1 DC output terminals behind plastic cover 2 AC plug for power supply module slot 4 3 AC plug for power supply module slot 3 4 RS 232 connector Sub D 9 f 5 Ethernet connector RJ 45 6 Reset button 7 AC plug for power supply module slot 2 8 AC plug for power supply module slot 1 9 DC output terminals...

Page 11: ...rounding Fixture Before installing the DEV 5071 into a 19 rack the DEV 65 0033 grounding fixture being part of the delivery has to be assembled to the rear side of the chassis It is the choice of the customer how the bracket is to be installed on the left side or on the right side and the grounding bolt facing towards the rack or towards the chassis In the following figure it was chosen the right ...

Page 12: ...4 3 AC plug for power supply module slot 3 4 RS 232 connector Sub D 9 f 5 Ethernet connector RJ 45 6 Reset button 7 AC plug for power supply module slot 2 8 AC plug for power supply module slot 1 9a DC output terminals V 9b DC output terminals V 10 Grounding bolt of grounding fixture DEV 65 0033 here assembled on the right side The chassis needs to be connected with the DEV 65 0033 grounding fixtu...

Page 13: ...rminals double hole lugs with 5 8 15 875 mm center distance and 90 cable taps are recommended e g Burndy YA2CL 2TC14 90 capable of AWG 2 i e 35 mm wires As an alternative a number of ring tongue terminals with an inner diameter of 6 mm and a maximum outer diameter of 14 mm can be used The number of cables and the diameters of the cables depend on the current to be supplied and the length of the ca...

Page 14: ...s are hot pluggable it is recommended to power down the device for exchange operations for safety reasons and to avoid short circuits 1 2 Removal of a power supply module First with the thumb of the left hand push the metal lever 1 of the power supply module to the left This releases the plastic handle 2 of the plastic cover which now can be actuated with the index finger of the left hand Pull gen...

Page 15: ... to all installed power supply modules at power up in parallel or there are different latencies within the power supply modules Additionally it is possible that there were applied changes on the setup of the device e g adding or swapping power supply modules Therefore it is highly recommended to reboot the device after power up or after applying changes to the setup of the DEV 5071 The reboot of t...

Page 16: ...es not physically affect the output current limits of the single power supply modules There are limits for each power supply module which need to be considered The output power depends on the AC input voltage A module delivers up to 1200 W if supplied with 100 120 V AC and is capable to deliver 2000 W if supplied with 200 240 V AC The output voltage of a power supply module thus of the DEV 5071 ca...

Page 17: ...MP settings of the device are Read Community public Write Community private Local Remote changeable per SNMP Note that if a Trap Destination IP Address is defined without the explicit assignment of a port the standard SNMP trap port 162 is assigned implicitly For changing the SNMP setup please refer to chapter 5 4 5 4 There are software factory defaults for some SNMP objects please refer to the co...

Page 18: ...n can be established by a crossed Ethernet cable or via a local hub switch with straight Ethernet cables and the network setup of the PC is to be altered that it is in the same subnet as the device So if it is intended to use the factory default network settings the IP address of the standalone PC should be set to 192 168 0 xxx with xxx ranging from 001 254 except 11 which is the address of the de...

Page 19: ...ng the Enter or key on the keyboard When using MS Windows HyperTerminal select the Properties entry from the File menu and click on the Settings tab There select ANSI from the Emulation drop down list and then click on the ASCII Setup button to uncheck Send line ends with line feeds as shown in the following figure 4 4 2 2 1 Start and Termination of the Configuration Program In this application th...

Page 20: ...ory default network settings please refer to chapter 4 3 2 When using the q choice the configuration program terminates and the login message is displayed again none login When using the x choice the configuration program saves all changes made and reboots the device your choice x CR rebooting the device please wait When rebooting all processes are stopped and the reboot of the device is initializ...

Page 21: ...changed After that the choices list reappears 4 4 2 2 4 3 set gateway This choice is used to change the gateway address of the device your choice 3 CR Current gateway is 192 168 0 99 Enter gateway NONE to clear To change the current gateway address type in a different valid address to clear the address type in NONE CR and just entering CR maintains the current setting Enter gateway NONE to clear C...

Page 22: ...erface is disabled for modifying the settings of the device but open for surveillance and status queries 5 1 2 Remote Mode The Remote Mode is implemented for operation via SNMP In Remote Mode the status of the power supplies is still indicated via the LEDs at the device and via Web Interface but the control functionality of the Web Interface is disabled 5 2 INITIALIZATION OF THE DEVICE The device ...

Page 23: ...itional license keys at any time please contact DEV Systemtechnik Note The screenshots shown in the following were made from the Web Interface of a DEV 5071 equipped with three power supply modules Other configurations deviate from the layout but not from the basic functionality of the Web Interface 5 4 1 Start of the Web Interface To start the Web Interface open a web browser recommended is Mozil...

Page 24: ...en is not accessible make sure that the computer accessing the device is in the same subnet of the common network chapter 4 4 2 1 The Web Interface permits the definition of a number of users with different permission chapter 5 4 5 2 for accessing the Web Interface in parallel in accordance to the number of installed licenses An additional user who tries to log in receives a corresponding notifica...

Page 25: ...s subject As a common feature between the Status Tab and the Control Tab two buttons and two indicators are located at the bottom of the window in the middle indicating that the device is either in Remote Mode as shown in the screenshot above or in Local Mode as shown in the screenshot of chapter 5 4 3 Changing the operation mode of the device via Web Interface is performed by clicking on the desi...

Page 26: ...uration and regarding the health status of the device The round indicators are equivalent to the physical LEDs green ok red error amber service excess tempera ture or gray off blinking LEDs on the power supply modules will be shown here as static only at the device please refer to chapter 3 2 1 for details on the indicator information The internal status table in the middle of the Status Tab addit...

Page 27: ...ow shows appearing and pending errors with the corresponding error message and a date time stamp The AC Line 3 error shown in the Active Events Window of the screenshot was triggered for demonstration purpose just by pulling a primary power connector To obtain more details on the errors detected by the device please click on the Error Log button to open the Error Log Window 5 4 3 1 Error Log Windo...

Page 28: ... of the Active Events Window in the Status Tab chapter 5 4 3 If an acknowledged error occurs again the counter in the table is increased and the acknowledgement is reset i e the X disappears An error can be acknowledged by highlighting i e clicking on the corresponding line and by operating the Acknowledge Entry button then The Delete Entry button is intended to remove acknowledged and not pending...

Page 29: ...n the right side see below At the bottom of the Control Tab five buttons are located The functionality of the Remote button the Local button and the Logout button were already described in chapter 5 4 2 The Cancel button and the Save button are required for modifications in the available panels see below They are functional only if one of the radio buttons in the list on the left side of the Contr...

Page 30: ...In the upper Status section first the status indicators AC OK DC OK Service and Fault are displayed Then the measured temperature of the power supply module is shown in C 2 Within the Setup section the corresponding power supply module can be turned on or off by selecting the appropriate radio button On or Off The change becomes effective after the Save button was operated in Local Mode Note that ...

Page 31: ...evice can be modified and the maximum output current can be adjusted The value for the maximum output current serves as a threshold for alarming purposes only I e the CPU module sums up the measured currents of the installed power supply modules and compares it against this value If the sum exceeds the value an alarm is triggered Note that values above 100 A can be entered as integer value e g 163...

Page 32: ...umentation DEV 5071 32 Copyright DEV Systemtechnik GmbH 2007 2017 5 4 5 Setup Tab The Setup Tab contains a number of buttons in order to branch out in the different setup functionalities described in the following ...

Page 33: ...uage from the drop down list Language and click on the button Change Language A window pops up to confirm the action A click on the button Exit closes the functionality and initiates the return to the Setup Tab Note English and German are the languages supported by the current firmware version 5 4 5 2 User Setup The currently logged in user has to have admin permission to access the User Setup fun...

Page 34: ...lete a user select a user from the drop down list User List that it appears in the field User Name Click on the button Delete User A confirmation window pops up and the user is deleted from the User List A click on the button Exit closes the functionality and initiates the return to the Setup Tab Note As already mentioned user names and passwords are case sensitive When adding a new user this user...

Page 35: ... entries Gateway Nameserver 1 and Nameserver 2 if required are to be specified by their IP addresses the Nameserver entries are used for the resolution of the Timeserver fields only The Time Server fields are used to specify one or two timeservers either via full qualified domain name or via IP address To specify the time zone an appropriate string is to be entered in the field Time Zone The list ...

Page 36: ...Local Mode and Remote Mode via SNMP please refer to chapter 5 5 4 2 1 Additionally up to four Trap Receiver IP Addresses can be defined via the IP address and the port in the format ip address port e g 192 168 0 29 121 If port is not specified the standard SNMP trap port 162 is assumed Finally a click on the download icon initiates the download of the MIB of the device The three buttons at the bot...

Page 37: ... 5 Restore Factory Defaults With a click on the button Restore Factory Defaults in the Setup Tab the settings of the device are reset to the factory default values as described in chapter 4 3 including all changes on the Web Interface If the button was operated by a user with admin permission a window pops up to confirm the action If the OK button was clicked another window pops up as a reminder t...

Page 38: ...lename including the path where the file resides Alternatively the Browse button can be used to locate the file When the file is selected click on the Upload button to activate the file transfer to the device After the upload is finished the installation is started please observe the text output that appears in the text window If for any reason a reboot of the device is required the Reboot Device ...

Page 39: ...ata here three modules are installed Type of power supply module here Tyco P2000AC54TEC109 Serial number here 3KZ29005288 3KZ29005344 3KZ29005420 In the right column on the top the Software Configuration is described Device Firmware version here 32 0060 H 01 Linux Kernel version here 2 6 25 M SNMP Software version here 3 1 13 the current IP Address of the device here 192 168 0 11 Web Interface Lic...

Page 40: ...ent collects and stores information from the system translates the information in SNMP compatible form and makes this information available to the manager The agents manage the objects of the node Each of the objects has its own individual management Object ID OID In the system the objects are the variables which can be simple values or tables The information about the objects is stored in the Man...

Page 41: ...bject name of an MIB object results out of the concatenation of the MIB String please refer to chapter 5 5 2 iso org dod internet private enterprises dev systemtechnik dev 5071 and of the corresponding MIB object E g the object instrument controllerMac has the full textual OID and are symbolizing that the corresponding two lines are actually not separated iso org dod internet private enterprise de...

Page 42: ...s of the controller of the device in hexadecimal characters separated by dashes Example 00 05 51 04 90 0C 5 5 4 1 2 instrument firmwareRevision OID 1 3 6 1 4 1 21035 34 1 2 0 Syntax OCTET STRING SIZE 32 Access read only Description The firmware revision of the device Example H 01 5 5 4 1 3 instrument instrumentType OID 1 3 6 1 4 1 21035 34 1 3 0 Syntax INTEGER Access read only Description The type...

Page 43: ...cess read write OR read only Description The operation mode of the device please refer to chapter 5 1 possible values 1 Local Mode i e local operation at the device or via Web Interface 2 Remote Mode i e remote operation via SNMP Note Via the SNMP setup of the Web Interface chapter 5 4 5 4 this object can be set to read write default or to read only By default this object is set to 2 Remote Mode ...

Page 44: ...er supply modules Note This value is used to determine the maximum index of the following table 5 5 4 2 5 application channelTable The table describes the special features and settings of each of the power supply modules 5 5 4 2 5 1 application channelTable channelEntry channelIndex OID 1 3 6 1 4 1 21035 34 2 5 1 1 x Syntax INTEGER 0 8 Access read only Description A unique value for each table ent...

Page 45: ...5 5 application channelTable channelEntry channelFanStatus OID 1 3 6 1 4 1 21035 34 2 5 1 5 x Syntax INTEGER ok 1 error 3 Access read only Description The fan speed status of the module possible values 1 ok i e the fan speed is detected as being ok 3 error i e the fan speed is detected as being not ok 5 5 4 2 5 6 application channelTable channelEntry channelOutVoltageSet OID 1 3 6 1 4 1 21035 34 2...

Page 46: ... Note The output current limit of each power supply module can be set individually However it is recommended to keep the output current set point for all installed modules at the same value Note the default setting and the limits for adjusting this value please refer to chapter 4 3 1 5 5 4 2 5 9 application channelTable channelEntry channelOutCurrent OID 1 3 6 1 4 1 21035 34 2 5 1 9 x Syntax INTEG...

Page 47: ...ding bit is set Note The trapEnableMask for the device is defined as follows Hex 0x80 MSB 0x40 0x20 0x10 0x08 0x04 0x02 0x01 LSB Bit 0 1 2 3 4 5 6 7 Trap unused4 unused3 unused2 unused1 trap modechange trap error trap errortext trap coldstart I e only the lower nibble bits 4 7 is supported refer to chapter 5 5 4 4 Note the differences for the Set method of the trapEnableMask BITS has the reverse o...

Page 48: ...ss Chapter 0 Internal Error 6 1 3 1 Power Supply 6 1 1 2 Fan 6 1 2 3 Switch Card no reference 4 Input Card no reference 5 Output Card no reference 6 Matrix Card no reference 7 Amplifier Card no reference 8 Optical Card no reference 9 Bias no reference A 10 Communication no reference B 11 Antenna Controller no reference C 12 future use no reference D 13 future use no reference E 14 future use no re...

Page 49: ...rveillance errorTable is not available 5 5 4 3 4 1 surveillance errorTable errorEntry errorIndex OID 1 3 6 1 4 1 21035 34 3 4 1 1 x Syntax INTEGER 1 64 Access read only Description A unique value for each table entry Its value ranges between 1 and the number of entries defined by numberOfErrors please refer to chapter 5 5 4 3 3 5 5 4 3 4 2 surveillance errorTable errorEntry errorNr OID 1 3 6 1 4 1...

Page 50: ...GER pending 1 gone 2 Access read only Description The last occurrence of the error is 1 still pending or 2 not pending anymore i e gone 5 5 4 3 4 6 surveillance errorTable errorEntry errorAcknowledge OID 1 3 6 1 4 1 21035 34 3 4 1 6 x Syntax INTEGER not acknowledged 1 acknowledged 2 Access read only Description The last occurrence of the error is 1 not acknowledged or 2 acknowledged ...

Page 51: ...g error description string please refer to chapter 6 1 To enable the trap bit 6 enum errortext in the trapEnableMask chapter 5 5 4 3 1 is to be set 5 5 4 4 2 trapAlarm This trap specific 4 is triggered if the device detects a new error or if a pending error disappears The trap delivers the objects errorNr please refer to chapter 5 5 4 3 4 2 errorPending chapter 5 5 4 3 4 5 for the corresponding en...

Page 52: ...1 Power Supply Errors 1 4 power supply modules are installed which are monitored In case that an AC line error a power supply error a temperature error an output voltage error a current limit exceeded error or that a communication error is detected the corresponding alarm is generated Error Code Description Decimal Hexadecimal 04353 04356 0x1101 0x1104 AC Line i Error i 1 4 04865 04868 0x1301 0x13...

Page 53: ...ctionality Pin 1 do not use Pin 2 Tx Pin 3 Rx Pin 4 do not use Pin 5 GND Pin 6 do not use Pin 7 do not use Pin 8 do not use Pin 9 do not use Note do not use means that normally the pin should be left open It is usually not a problem to use a fully populated 1 1 Sub D 9 m f cable to establish a RS 232 connection between the device and a PC Ethernet Connector at the CPU module Connector RJ 45 Connec...

Page 54: ...nto consideration during development and production of the device are listed here in English EN 50083 2 2006 Cabled Distribution Systems for Television and Sound Signals EN 60950 1 2002 Standard for Safety Information Technology Equipment EN 61000 3 2 2006 EMC Limits for Harmonic Current Emissions Equipment Input Current 16 A per Phase EN 61000 3 3 1995 EMC Limitation of Voltage Changes Voltage A1...

Page 55: ...cksichtigt EN 50083 2 2006 Kabelverteilsysteme für Ton und Fernsehrundfunk Signale EN 60950 1 2002 Sicherheitsbestimmungen für Einrichtungen der Informationstechnik EN 61000 3 2 2006 EMV Grenzwerte für Oberschwingungsströme Geräte Eingangsstrom 16 A je Leiter EN 61000 3 3 1995 Grenzwerte für Spannungsänderungen schwankungen A1 2001 und Flicker in öffentlichen Niederspannungs Versorgungsnetzen A2 2...

Page 56: ...Customer Documentation DEV 5071 56 Copyright DEV Systemtechnik GmbH 2007 2017 This Page Intentionally Left Blank ...

Page 57: ...uct DEV 5071 High Power DC Supply 48 V 4 2000 W 1 RU Options 21 23 79 and future options to which this declaration refers to is in conformity with Directive 2011 65 EU of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS Signed for and on behalf of DEV Systemtechnik GmbH Co KG Name Jör...

Page 58: ...y from a DHCP server IP Internet Protocol LED Light Emitting Diode M C System Management and Control System MAC Media Access Control address is the hardware address for the unique identification of a device within a network MIB Management Information Base NE Network Element NMS Network Management System OID Object IDentifier PC Personal Computer PE Protective Earth RU Rack Unit Units of vertical h...

Page 59: ...America Argentina Catamarca Catamarca CT Chubut CH AR 2926 06651 America Argentina La_Rioja La Rioja LR AR 3132 06831 America Argentina San_Juan San Juan SJ AR 3253 06849 America Argentina Mendoza Mendoza MZ AR 3319 06621 America Argentina San_Luis San Luis SL AR 5138 06913 America Argentina Rio_Gallegos Santa Cruz SC AR 5448 06818 America Argentina Ushuaia Tierra del Fuego TF AS 1416 17042 Pacifi...

Page 60: ... Atlantic Time Nova Scotia most places PEI CA 4612 05957 America Glace_Bay Atlantic Time Nova Scotia places that did not observe DST 1966 1971 CA 4606 06447 America Moncton Atlantic Time New Brunswick CA 5320 06025 America Goose_Bay Atlantic Time Labrador most locations CA 5125 05707 America Blanc Sablon Atlantic Standard Time Quebec Lower North Shore CA 4339 07923 America Toronto Eastern Time Ont...

Page 61: ...ia Harbin Heilongjiang except Mohe Jilin CN 2934 10635 Asia Chongqing central China Sichuan Yunnan Guangxi Shaanxi Guizhou etc CN 4348 08735 Asia Urumqi most of Tibet Xinjiang CN 3929 07559 Asia Kashgar west Tibet Xinjiang CO 0436 07405 America Bogota CR 0956 08405 America Costa_Rica CU 2308 08222 America Havana CV 1455 02331 Atlantic Cape_Verde CW 1211 06900 America Curacao CX 1025 10543 Indian C...

Page 62: ...u Prince HU 4730 01905 Europe Budapest ID 0610 10648 Asia Jakarta Java Sumatra ID 0002 10920 Asia Pontianak west central Borneo ID 0507 11924 Asia Makassar east south Borneo Sulawesi Celebes Bali Nusa Tengarra west Timor ID 0232 14042 Asia Jayapura west New Guinea Irian Jaya Malukus Moluccas IE 5320 00615 Europe Dublin IL 314650 0351326 Asia Jerusalem IM 5409 00428 Europe Isle_of_Man IN 2232 08822...

Page 63: ... 1512 14545 Pacific Saipan MQ 1436 06105 America Martinique MR 1806 01557 Africa Nouakchott MS 1643 06213 America Montserrat MT 3554 01431 Europe Malta MU 2010 05730 Indian Mauritius MV 0410 07330 Indian Maldives MW 1547 03500 Africa Blantyre MX 1924 09909 America Mexico_City Central Time most locations MX 2105 08646 America Cancun Central Time Quintana Roo MX 2058 08937 America Merida Central Tim...

Page 64: ...2540 Atlantic Azores Azores PW 0720 13429 Pacific Palau PY 2516 05740 America Asuncion QA 2517 05132 Asia Qatar RE 2052 05528 Indian Reunion RO 4426 02606 Europe Bucharest RS 4450 02030 Europe Belgrade RU 5443 02030 Europe Kaliningrad Moscow 01 Kaliningrad RU 5545 03735 Europe Moscow Moscow 00 west Russia RU 4844 04425 Europe Volgograd Moscow 00 Caspian Sea RU 5312 05009 Europe Samara Moscow 00 Sa...

Page 65: ...tions UA 4837 02218 Europe Uzhgorod Ruthenia UA 4750 03510 Europe Zaporozhye Zaporozh ye E Lugansk Zaporizhia E Luhansk UA 4457 03406 Europe Simferopol central Crimea UG 0019 03225 Africa Kampala UM 1645 16931 Pacific Johnston Johnston Atoll UM 2813 17722 Pacific Midway Midway Islands UM 1917 16637 Pacific Wake Wake Island US 404251 0740023 America New_York Eastern Time US 421953 0830245 America D...

Page 66: ...a Anchorage Alaska Time US 581807 1342511 America Juneau Alaska Time Alaska panhandle US 571035 1351807 America Sitka Alaska Time southeast Alaska panhandle US 593249 1394338 America Yakutat Alaska Time Alaska panhandle neck US 643004 1652423 America Nome Alaska Time west Alaska US 515248 1763929 America Adak Aleutian Islands US 550737 1313435 America Metlakatla Metlakatla Time Annette Island US 2...

Page 67: ...Customer Documentation DEV 5071 Copyright DEV Systemtechnik GmbH 2007 2017 67 14 NOTES ...

Page 68: ...ower Supply Chassis Features Powerful DC Supply with up to 8000 W maximum Output Power 1 4 hot pluggable 48 V 2000 W Power Supply Modules Compact 19 1 RU Chassis Galvanic Isolation of the Output Terminals Selectable Polarity of the Output Voltage SNMP Support DEV Web Interface ...

Page 69: ...00 W 3 Power Supply Modules Power Consumption 6450 VA 3 Power Supply Modules General Specifications Size 19 483 mm Width 1 RU 44 mm Height 475 mm Depth Weight 15 kg equipped with 4 Power Supply Modules Environmental Conditions ETS 300019 Part 1 3 Class 3 1 Option 21 Additional Power Supply Module The device is delivered with four instead of three power supply modules Number of Power Supplies 4 Out...

Reviews: