User Manual DEV 5072
Copyright DEV Systemtechnik GmbH 2016-2017
11
4
Installation Instructions
4.1
Scope of Delivery
1 * DEV 5072 Managed Power Supply Chassis
equipped with the type and number of power supply modules as ordered
1 * User manual (this document)
4.2
Installation of the Product
4.2.1
Mechanical Assembly of the Product
Please refer to the warnings in chapter 2.3 regarding the mechanical integration of
the DEV 5072. For the assembly in a 19" rack the rack slots must be prepared with
rails for the chassis. After inserting the chassis in the rack, fix the chassis with four
screws to the rack at its rack mount flanges.
For the assembly in combination with the DEV 5101 Online UPS for DEV 5072,
please refer to the DEV 5101 user manual.
4.2.2
Grounding, Data Cables, and Power Connection
R e s e t
S ta tu s
A C
3
A C
2
A C
1
A C
4
G N D
-
A
+
A
C o m
E th
-
B
+
B
S ta tu s
R e s e t
+B Secondary DC output terminal for positive polarity
-B Secondary DC output terminal for negative polarity
AC
4
AC plug for power supply module slot 4
Reset "Reset" push button
Status "Status" LED
Eth Ethernet connector, RJ-45
Com Serial interface connector, Sub-D 9 (f)
AC
3
AC plug for power supply module slot 3
AC
2
AC plug for power supply module slot 2
GND Grounding bolt
AC
1
AC plug for power supply module slot 1
-A Primary DC output terminal for negative polarity
+A Primary DC output terminal for positive polarity
For the warnings for the DEV 5072 with respect to "Grounding, AC Connection,
Cables" please refer to chapter 2.3.
First, the DEV 5072 chassis needs to be connected to the rack via a ground wire.
The grounding bolt (labeled
GND
in the figure above) is located on the right at the
rear side of the chassis between the AC plugs for the second (
AC
2
) and for the first
(
AC
1
) power supply module slot. To connect a cable, please take off the upper nut
and the first washer of the grounding bolt. Then connect the grounding cable which
must have a ring tongue terminal matching the M4 fastening bolt. The washer and
the nut have to be tightened again.
Next, establish the external Ethernet connection by plugging the appropriate
Ethernet cable from your network to the Ethernet port of the device (
Eth
); the
configuration of the Ethernet interface is described in chapter 4.4.2.
In combination with the DEV 5101, the serial interface of the DEV 5072 is to be
connected to the Battery Management Controller (BMC) chassis as stated in the
DEV 5101 user manual. For standalone applications of the DEV 5072 and if the basic