background image

6

D.

Operating check points

1.

Check that green Power-on light is illuminated

2.

Check that green Compressor-on light is illuminated
if dryer is on in the manual mode or it is a
scheduled on time

IMPORTANT:  Refrigeration compressor must be restarted
after power interruption.

3.

Check interface panel

NOTE: Interface panel will switch between Current Time/
Operating Status screen and Hours to Service/Total
Operating Hours (HRS TO SVC/TOTAL) screen. TOTAL is
cumulative hours of refrigeration compressor operation.

a.

Verify that current time is correct

b.

Check HRS TO SVC: this indicates time remaining
until service is required; allow time for required
maintenance items to be ordered

c.

Check operating status:
MANUAL OVERRIDE - Dryer is either running
continuously (not being controlled by the
scheduled on/off times) or the refrigeration
compressor has been shut off using the
On/Off button.
SCHEDULE RUNNING - Refrigeration compressor
is being turned on and off by the monitor per-
programmed schedule ( see B.2. to set schedule)

d.

Check Temperature indicator - indicator should
read in the green area

e.

Check Alarm/Service light If illuminated, check
Interface panel.
1)

If SERVICE DRYER appears, scheduled
maintenance time has elapsed (HRS TO SRV is 0).
Perform needed service and reset service
interval (see B.2.).

2). If ALARM appears, a dryer fault is indicated;

see Trouble-shooting Guide for possible
remedies. After fault correction push Reset
button to turn Fault alarm off.
FAULTS
LOW PRESSURE - the refrigeration compressor
control circuit has opened because of  low
suction pressure. Compressor will restart
automatically when fault is corrected.
HIGH PRESSURE - the refrigeration compressor
control circuit has opened because of high
head pressure. The high pressure switch must
be reset manually once the fault is corrected.
Red reset button is located on pressure switch
inside unit.
LOW TEMPERATURE - compressed air
temperature is below the set point

NOTE: If temperature probe is open, one light on lefthand
side of Temperature indicator will be illuminated.

HIGH TEMPERATURE - compressed air tempera-
ture is above the set point.

NOTE: If temperature probe is shorted, Temperature
indicator will be completely illuminated.

DRAIN - electric drain contains a high water
level alarm that activates if drain fails to
discharge.

f.

Check drain operation - push  Drain (push-to-test)
button to energize electric drain.  A flow of
condensate and/or air should be present at the
drain outlet.

E.

Using the RS-232 port
The RS-232 port is used to monitor dryer operation
from a host computer. A (1 to 1) DB-9 cable is required
to connect dryer and computer.  For PC connections,
data is transmitted on pin 2, received on pin 3, ground
is pin 5, pins 7 and 8 are jumpered at dryer.

Operation is at fixed baud rate of 2,400; asynchronous
format is 8 bit, no parity, 1 stop bit (“8,N,1”). No
checksum or error correction values are provided.  If
required, request status string two (or more) times and
compare for agreement.

Request data by sending ASCII  ? character (3FH).
Response may take up to two seconds as certain
processing functions may require completion before
serial port is acknowledged.

Dryer responds with line feed (0AH), carriage return
(0DH), and character string:
(1)    (2)   (3)    (4)     (5)       (6)     (7)
XXX,  X,  XXX,   X,   XXXX,   XXXX,  X

(1) Number of Temperature Indicator LEDs illuminated (1-20)
(2) Compressor state, C=X (1or 031H = ON, 0 or 030H= OFF)
(3) Sum of alarm weights, A=XXX (0 - 255;

e.g. high pressure and service alarms = 132 [4 + 128])
Bit Weight

 Alarm

2

     4

 High press. alarm (1 = alarm)

3

     8

 Low press. alarm (1 = alarm)

5

    32

 Drain alarm (1 = alarm)

7

   128

 Service (service required) alarm (1 = alarm)

For low and high temperature alarm, assign alarm to
number of Temperature Indicator LEDs illuminated:
3 = low, 20 = high

(4) Day of week (1 = Sunday, 7 = Saturday)
(5) Time (24 hour format, hour, minuteS)
(6) Hours to service (0-9999)
(7) Operating mode, M=X (S = schedule  running,

M = manual override)

F.

Using the auxiliary contacts
The monitor is equipped with an auxiliary set of dry
(volt-free) contacts (one set of normally open contacts,
one set of normally closed contacts) which can be used
to operate an auxiliary device (e.g., an air line solenoid
valve).  Rating: 5 amps @ 24VDC or 240VAC

1. These contacts can be activated in one of the

following modes:

Schedule Driven Mode - the contacts will be energized
and de-energized according to the schedule inputted
by the operator of the dryer.  If the refrigeration
compressor shuts down on a fault condition, the
contacts will remain energized (or de-energized)
according to the schedule.  The contacts will operate
independently of the refrigeration compressor in both
the manual override and schedule running modes.

NOTE: The schedule driven mode is the factory
default setting.

For Sales & Service Call:  705-722-5747  Ext.1

Summary of Contents for DRD 200

Page 1: ...NTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEMATICS 8 DIMENSIONS WEIGHTS 9 TROUBLESHOOTING 10 PARTS LIST 11 WARRANTY 12 SERVICE DEPARTMENT 724 746 1100 7610 530 11A 9 01 Refrigerated Compressed Air Dryers Models DRD 200 250 300 400 500 750 Instruction Manual c For Sales Service Call 705 722 5747 Ext 1 ...

Page 2: ...carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found upon unpacking ...

Page 3: ...r cooled 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this and has not been preset at the factory for this altitude contact manufacturer s Service Department NOTE Outdoor installation Standard units are designed for indoor installation Contact manufactu...

Page 4: ...imum working pressure Do not exceed dryer s Maximum Working Pressure NOTE Install dryer in air system at highest pressure possible e g before pressure reducing valves NOTE Install dryer at coolest compressed air temperature possible Maximum inlet compressed air temperature 120 F 49 C If inlet air exceeds this temperature precool the air with an aftercooler B Air Outlet Connect air outlet to downst...

Page 5: ...cy of service Typically element changeout is recommended at least annually e Push Set Run button again to exit Set Mode NOTE If dryer is left in the Set Mode for longer than 30 seconds Alarm light will illuminate and TIME OUT will appear on the Interface panel Dryer will resume previous operating mode C Starting dryer IMPORTANT Dryer must be energized 24 hours before starting refrigeration compres...

Page 6: ...rm that activates if drain fails to discharge f Check drain operation push Drain push to test button to energize electric drain A flow of condensate and or air should be present at the drain outlet E Using the RS 232 port The RS 232 port is used to monitor dryer operation from a host computer A 1 to 1 DB 9 cable is required to connect dryer and computer For PC connections data is transmitted on pi...

Page 7: ...pliers MODEL 200 250 300 400 500 750 Rated capacity of 60 Hz 200 250 300 400 500 750 air cooled models scfm 50 Hz 170 210 250 340 420 630 TABLE 1 Rated capacity scfm and pressure drop 100 psig inlet pressure 100 F inlet temperature and 100 F ambient temperature Air cooled models water cooled models use 1 15 multiplier if cooling water is below 35 C 95 F Element o ring Separator Element Bowl o ring...

Page 8: ... Max Min voltage 253 187 253 187 253 187 253 187 Rated Load Amps 8 4 11 5 13 6 22 9 Locked Rotor Amps 51 65 5 75 90 Minimum Circuit Ampacity 10 5 16 9 17 1 31 7 Branch Circuit Fuse Size amps 15 20 25 45 Watts 35 F Evaporator 100 F Ambient 1335 1940 2620 3600 Resistance Ohms Three phase Total 1 77 1 256 1 058 0 853 Nominal Voltage 460 3 60 460 3 60 460 3 60 460 3 60 Max Min Voltage 506 414 506 414 ...

Page 9: ...eight lb 405 415 416 457 498 625 LEGEND CON CONTACTOR HTR CRANKCASE HEATER MTR COMPRESSOR 1FU FUSE SECONDARY 2FU FUSE PRIMARY 3FU FUSE PRIMARY 1FM FAN MOTOR 1 2FM FAN MOTOR 2 1FPS FAN PRES SWITCH 1 2FPS FAN PRES SWITCH 2 TC1 DEWPOINT TEMPERATURE T1 TRANSFORMER CONTROL T2 TRANSFORMER HDD BOARD SSMP SOLID STATE MOTOR PROTECTION SOL1 DEMAND DRAIN ELECTRICAL SCHEMATIC NOTE Dimensions and Weights are f...

Page 10: ...ol switch Water cooled Cooling temperature too high flow too low clogged strainer faulty water regulating valve a Hot gas by pass valve requires adjustment a Dryer overloaded b Refrigeration system off or not cooling sufficiently a Drain line restricted or frozen b Drain mechanism faulty Dryer left in the Set Mode for longer than 30 seconds Blow out system with dry air Check valve positions Check ...

Page 11: ...0 111 25 4130 111 28 Low refrigerant pressure switch 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 High refrigerant pressure switch 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 Fan cutout switch 1 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 Fan cu...

Page 12: ...uct based on the original date of purchase and or date of manufacture as outlined above There is no other expressed warranty Implied warranties including those of merchantability and fitness for a particular purpose are limited to one 1 year from date of purchase to the extent permitted by law and any and all implied warranties are excluded This is the exclusive remedy Liability for consequential ...

Reviews: