Installation - Step 3
Steam from the cylinder enters the duct via a steam distribution pipe. In order to obtain
optimum performance of the humidifier, it is recommended that these instructions be adhered to as
far as possible.
There are two steam inlet diameters available : Ø 25 mm and Ø 40 mm
STEAM DISTRIBUTION PIPE
ELMC Model
1 SM CYL
1 LG CYL
2 CYL
3 CYL
Number of steam
pipe(s)
1 1 2 3
Steam inlet
diameter (1)
Ø
25mm Ø
40mm Ø
40mm Ø
40mm
Condensate drain
diameter (2)
Ø
8mm Ø
8mm Ø
8mm Ø
8mm
Steam distribution pipe selection table
The number of distribution pipes and the diameters depend on the humidifier model.
• SM CYL = small cylinder, LG CYL = large cylinder
To get the best steam distribution, select the longest possible distribution pipe to fit the duct.
Standard distribution pipes are available on either diameter in 110, 290, 590, 790, 1000, 1250
and 1500 mm long.
1 Steam
inlet
2 Condensate
drain