20 Pictures for illustrating purposes only
E
LECTRO
V
AP
MC2
Installation - Step 3
1.
We would recommend to use the steam hose from Devatec supply .
NB : when the humidifier is started up for the first time, a smell of burning may be smelt
especially when brand new hoses are installed. This is normal and will eventually dispel.
2.
Steam hose selection :
• SM CYL = small cylinder, LG CYL = large cylinder
3. The ELMC humidifier can be used with pressure ducts (P) having the following characteristics :
If P is inferior to 150mm CE (Water column) i.e. 1470Pa.
If P is between 150mm CE et 300mm CE, our optional filling cup plateform must be
used
4.
Please adhere to the recommendations given underneath for the installation of the steam hose
according to one of the shown examples, the most suited to your installation. A set of hose
clamps are supplied for ensuring a correct installation.
The humidifier should be located within 3 m. of the steam distribution pipe. If the distance is
superior to 3 m., insulated steel or copper pipe of a slightly larger diameter must be used.
STEAM OUTPUT
Model ELMC
1 SM CYL
1 LG CYL
2 CYL
3 CYL
Nb of steam
outlets
1 1 2 3
Steam outlet Ø
Ø
25mm Ø
40mm Ø
40mm Ø
40mm
Radius of bend for steam hose :
- Ø
25 mm hose = 250 mm minimal radius
- Ø
40 mm hose = 400 mm minimal radius
Example a
Example b
D 8mm condensate hose to
drain
500 mm min.
500 mm min.