Installation - Step 4
CONDENSATE DRAINING
The following drawings show the water draining connections
that should be made.
1. The
devatec
supplied steam hose should be used :
ELMC 1 cylinder :
1m Ø25mm hose with 1 hose clamp
(supplied).
ELMC 2 cylinders :
1m + 1.2m Ø25mm hose with 2 clamps
(supplied).
ELMC 3 cylinders :
1m + 1.2m + 1.8m Ø25mm hose with 3
clamps (supplied).
These hoses are designed to be connected to the draining
system. Regular replacement is recommended.
2. If rigid piping is used, it must be heat (100°C) and pressure
resistant PVC material and have a 60 mm wide diameter.
3. The discharge hose must be free from any obstacle. It is
recommended that each steam cylinder has its own drain pipe
and tank arrangement.
4. Use water tanks with a lid that has water collecting facilities
(s.a. drawings 1, 2 and 3).
5. A funnel can also be used (s.a. pict. 4), but it should be offset
from the underside of the unit to prevent any steam and/or
condensation from getting into the cabinet. The installation of a
siphon (as per the draining hose) is recommended and
arrangements for holding water spilling should also be made.
6.
CAUTION :
keep a minimum pitch of 10° for both the draining
hose of the humidifier and for general drain pipe (s.a. pictures
1, 2, 3 and 4).