35 Pictures for illustrating purposes only
E
LECTRO
V
AP
MC2
Installation - Step 5
RS485 or RS422 or RS232 interface protocol :
ALL WORKS CONCERNED WITH ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A SKILLED AND QUALIFIED PERSONNEL
.
Register
Address
description
Value
Function number
Address
Data
(Dec)
10001
Steam Production (Contactor)
1 = Production: ON / 0 = Production: OFF
02, read only
0
10002
High water level sensor
0 = Low water level /1 = High water level
1
10003
High limit (terminal block 1 and 2)
0 = opened / 1 = closed
2
10004
Fill (Inlet Valve)
1 = Filling / 0 = no filling
3
10005
Drain ( Drain Valve)
1 = draining / 0 = no draining
4
10006
Ventilation Pack (Blower)
1 = Blower: ON -- 0 = Blower: OFF
5
10007
Maintenance
1 is ON -- 0 is OFF
6
10008
General fault
1 is ON -- 0 is OFF
7
1
Stop the humidifier via the BMS
1= ON :Start requested /0= Off :Stop Unit
01 read
05 write
0
30001
Demand
(%)
04, read only
0
30002
Steam output
(Kg/hr) x 10
1
30003
Current
(A) x 10
2
30004
Run status
0: Idle 1: Steam Gen
2: End of season 3: Failure
4: Manual drain 5: Maintenance
3
30005
Bed Life
(Hours)
4
30006
Run Time
(Hours)
5
30007
Idle Time before drain
(Hours)
6
30008
Proportional Signal (analog input)
V x 10 , mA x 10 or % x 10
7
30009
Temperature tank (Maintening hot
water (option))
(°C)
8
30010
Failure
0: Normal operating
1: P1 Error 2: P2 Error 3: P3
Error 4: P4 Error 5: P5 Error
6: P6 Error 7: P7 Error 8: P8
Error 9: P9 Error 10: First inspect.
11: Service overdue
9
30011
water used
1 : Tap water 2 : Softened water
3 : Slightly demineralized water
4 : demineralized water
10
30012
regulation used
20:On/Off 21: Digital Ctrl
22: Digital Sensor 23: 4 steps
24:0-10V 25 :0-20V 26 :0-20mA
27 :1-5V 28 :2-10V 29 :4-20V
30 :4-20mA 31 :Devatec Sensor
32 :0-10V Sensor 33 :0-5V Sensor
34 :4-20mA Sensor
11
40001
"Maintenance interval"
( Hours / 100) mini = 1 and maxi = 200
0
40002
"Adjust steam by "
draining = 1 or evaporation = 2
1
40003
Drain duration
(Foam scale control)
mini = 0 sec and maxi= 15 sec
2
40004
Idle Time (End of Season Time)
(Hour) mini = 1 and maxi = 168
3
40005
Steam capacity limit
(%) mini = 20% and maxi = 100%
4
40006
RH value in digital sensor or
demand value in digital controller
( % ) mini = 1 and maxi = 100
5
40007
RH Set point
( % ) mini = 1 and maxi = 100
6
03 read
06 write