ElectroVap®
ELMC-SB
24
30004
Have
3
00000003
Run status
0: Idle 1: Steam Gen 2: End of season 3: Failure
4: Manual drain 5: Maintenance
30005
Have
4
00000004
maintenance counter
(Hours)
30006
Have
5
00000005
time
(Hours)
30007
Have
6
00000006
time before end-of-season
draining
(Hours)
30008
Have
7
00000007
Control Signal value
10 x V or 10 x mA gold %
30009
Have
8
00000008
Temperature (maintenance option
or SB)
(C)
30010
Have
9
00000009
Error code
0: Normal operating 1: P1 Error 2: P2 Error 3:
P3 Error 4: P4 Error 5: P5 Error 6: P6 Error 7:
P7 Error 8: P8 Error 9: P9 Error 10: First
inspect. 11: Overdue service
30011
Have
10
0000000A
type of water
1: Tap water 2: Softened water3: Partial DI
water 4: DI water
30012
Have
11
00000000B
type of control
20:On/Off 21: Digital Ctrl 22: Digital Sensor 23:
0-10V CTRL 24:0-5V CTRL 25:0-20mA CTRL
26:0-10V Sensor 27:0-5V Sensor28:4-20mA
Sensor 29: Temp Sensor
30014
Have
13
00000000D
Application
(%)
30015
Have
14
0000000E
steam production
10 x (Kg/hr)
40004
Av
3
00800003
End-of-season (EOS)
(hours) mini - 1 and maxi - 168
40005
Av
4
00800004
Steam capacity limit
(%) mini - 20% and maxi - 100%
40006
Av
5
00800005
RH or demand value (digital or
digital probe).
( %) mini - 1 and maxi - 100
40007
Av
6
00800006
RH set point
( % ) mini - 1 and maxi - 100SB: (C) 25 to 55
40008
Av
7
00800007
Not used)
Not used
40009
Av
8
00800008
Not used
Not used
40010
Av
9
00800009
maintenance interval
(hours / 100) mini - 1 and maxi - 200
40011
Av
10
0080000A
production adjustment
Draining - 1 or evaporation - 2
40012
Av
11
0080000B
anti-foam drain time
mini - 0 sec and maxi 15 sec
Summary of Contents for ElectroVap ELMC 20-30 SB
Page 1: ...STEAM GENERATOR FOR STEAM ROOM ElectroVap ELMC SB Series Instruction Operation Manual ...
Page 25: ...ElectroVap ELMC SB 25 3 8 6 Wiring diagrams ELMC 5 to 10 Up V 1x200 240V 50 60Hz ...
Page 26: ...ElectroVap ELMC SB 26 ELMC 5 to 30 Up V 3x200 690V 50 60Hz ...
Page 27: ...ElectroVap ELMC SB 27 ELMC 40 to 60 Up V 3x200 690V 50 60Hz ...
Page 28: ...ElectroVap ELMC SB 28 ELMC 90 Up V 3x200 690V 50 60Hz ...
Page 29: ...ElectroVap ELMC SB 29 3 9 OPTION Transformer connection ...
Page 51: ...ElectroVap ELMC SB 51 ...