Absorption distance "D"
Make sure that the absorption distance is met to let the air absorb the steam dispersed by the tubes. In this
absorption distance, the steam is still visible in the air stream in the form of fog. If any furniture is placed in this area,
condensate may occur. For this reason, it is imperative to consider this absorption distance when placing the
humidifiers.
3.3.2
How to calculate absorption distance « D »
In order to determine the absorption distance, the attached calculation table can be used:
▪
RH1 = relative humidity of air before humidification in %.
▪
RH2 = relative humidity of air after humidification in %.
▪
D mini = minimum absorption distance in meters (m).
Inlet RH1 [%]
5
10
20
30
40
50
60
70
Outlet RH2 [%]
Minimum absorption distance "D" [m]
40
0,9 0,8
0,7
0,5
-
-
-
-
50
1,1
1
0,9
0,8
0,5
-
-
-
60
1,4 1,3
1,2
1
0,8
0,5
-
-
70
1,8 1,7
1,5
1,4
1,2
1
0,7
-
80
2,3 2,2
2,1
1,9
1,7
1,5
1,2
0,8
90
3,5 3,4
3,2
2,9
2,7
2,4
2,1
1,7
This calculation table is to be used for temperatures between 20°C and 25°C (68°F to 77°F) (Maximum air speed 5m/s).
For calculated distances, contact your Devatec agent.
3.3.3
Minimum absorption distance
The steam dispersion pipes must be positioned after the minimum specified absorption distance. Please follow the
guidelines depending on the configuration of your air handling unit.
Fig. B 3-3.
Before/after a fan
Fig. C 3-3.
Before/after heating battery or filter
1.5 x D before a particle filter or absolute filter
= Dispersion tube
D
D
1.5 x D
5 cm
Summary of Contents for ElectroVap RTH-HC Series
Page 1: ...ElectroVap HUMIDIFIERS RTH HC Series Instruction Operation Manual ...
Page 30: ...ELECTROVAP RTH HC 30 3 8 6 Wiring diagrams Up V 1x200 240V 50 60Hz ...
Page 31: ...ELECTROVAP RTH HC 31 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 32: ...ELECTROVAP RTH HC 32 RTH HC 5 30 Up V 3x380 690V 50 60Hz ...
Page 33: ...ELECTROVAP RTH HC 33 RTH HC 40 50 Up V 3x380 690V 50 60Hz ...
Page 34: ...ELECTROVAP RTH HC 34 RTH HC 60 70 Up V 3x380 690V 50 60Hz ...
Page 35: ...ELECTROVAP RTH HC 35 RTH HC 80 100 Up V 3x380 690V 50 60Hz ...
Page 36: ...ELECTROVAP RTH HC 36 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 37: ...ELECTROVAP RTH HC 37 RTH HC 44 Up V 3x200 240V 50 60Hz ...
Page 39: ...ELECTROVAP RTH HC 39 Case 2 Up V 3x200 240V 50 60Hz Only for Case 3 ...
Page 40: ...ELECTROVAP RTH HC 40 Case 3 Up V 3x380 690V 50 60Hz ...
Page 42: ...ELECTROVAP RTH HC 42 3 9 OPTION TRANSFORMER CONNECTION ...