ELECTROVAP
®
RTH-HC
60
6.3
WATER INLET VALVE
Maintenance of the water inlet valve is to be done after the first 50 hours of
operation. Thereafter, twice a year (minimum).
•
Switch the appliance off.
•
Switch off the water supply to the humidifier and unscrew the water
supply hose.
•
Disconnect the cables from the water inlet valve of your humidifier (Item
1).
•
Loosen the clamp and remove the water supply hose. (Item 2)
•
Unscrew the two screws securing the valve (Item 3).
•
Pull out your valve, remove the filter with pliers and remove the coil (Item
4) by prying it off with a screwdriver.
•
Run water through the valve body and over the filter to remove any
particles.
Once all these operations completed, please reassemble the unit, taking care to check the condition of the water
supply hose clamp. You can put your appliance back into service.
Ensure that all the clamps are properly tightened whenever the humidifier is maintained.
6.4
WATER LEVEL DETECTOR
Maintenance of the detector should be done during each tank maintenance.
•
Disconnect the cables of the water level sensor (1).
•
Unscrew the clamp of the pressure balancing tube (2) and disconnect it
from the cover.
•
To release the sensor, unscrew the hose clamp (3) and disconnect the hose.
Caution, there may still be water inside the tube.
•
Clean the hose without unscrewing it.
•
Unscrew the 3 screws (4) in order to clean the floats and the body of the
level sensor.
Fig. 6-3.
Humidifier water inlet valve
Fig. 6-4.
Humidifier water level detector
Summary of Contents for ElectroVap RTH-HC Series
Page 1: ...ElectroVap HUMIDIFIERS RTH HC Series Instruction Operation Manual ...
Page 30: ...ELECTROVAP RTH HC 30 3 8 6 Wiring diagrams Up V 1x200 240V 50 60Hz ...
Page 31: ...ELECTROVAP RTH HC 31 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 32: ...ELECTROVAP RTH HC 32 RTH HC 5 30 Up V 3x380 690V 50 60Hz ...
Page 33: ...ELECTROVAP RTH HC 33 RTH HC 40 50 Up V 3x380 690V 50 60Hz ...
Page 34: ...ELECTROVAP RTH HC 34 RTH HC 60 70 Up V 3x380 690V 50 60Hz ...
Page 35: ...ELECTROVAP RTH HC 35 RTH HC 80 100 Up V 3x380 690V 50 60Hz ...
Page 36: ...ELECTROVAP RTH HC 36 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 37: ...ELECTROVAP RTH HC 37 RTH HC 44 Up V 3x200 240V 50 60Hz ...
Page 39: ...ELECTROVAP RTH HC 39 Case 2 Up V 3x200 240V 50 60Hz Only for Case 3 ...
Page 40: ...ELECTROVAP RTH HC 40 Case 3 Up V 3x380 690V 50 60Hz ...
Page 42: ...ELECTROVAP RTH HC 42 3 9 OPTION TRANSFORMER CONNECTION ...