ElectroVap RTH-V2
20
Pictures and values are not contractual - The devices may be subject to changes without notice
3.4 STEAM OUTLET
1.
Use preferably hose from our supply.
NB : when new hoses are installed, a smell of burnt plastic may be smelt during the first running of the
steam humidifier. This is normal and will eventually diminish.
2.
Selection of the steam pipe:
3.
The RTH humidifier can be used with pressure ducts (P) having the following characteristics :
•
If P is inferior to 220 mm CE (Water column) i.e. 2157 Pa.
•
If P is between 220 mm CE and 370 mm CE (3627 Pa.), options available for 700 mm CE.
4.
Please adhere to the recommendations given underneath for the installation of the steam hose. A set of
hose clamps is supplied for ensuring a correct installation.
•
Ø40 or Ø60 mm steam hose : max 3 m length.
•
Stainless steel or copper pipe with a slightly larger diameter, connected to the ground. Use a flexible
steam hose cuff to connect the humidifier to the steam distribution pipe. The length of the hose must not
exceed 6 m and must be insulated.
Make sure that the steam hose is not leaky / or does not form a water pocket.
Failure to
follow these instructions can lead to serious malfunctions.
Example b
*
Optional stainless steel reducer Ø60/Ø40 mm (See page 14)
RTH
RTH 5 - 20
RTH 30 - 50
Number of steam outlets
1
1
Diamètre tuyau sortie vapeur
Ø 60 mm
Ø 60 mm
Example a
Keep the hose tight before
joining it to the sleeve(s).
Ring bearing clamp
supplied with optional
stainless steel union
Ø60 mm stainless steel union
(option)
70-90 ring clamp supplied
with the humidifier
Radius of bend for steam hose :
•
Ø 40 mm steam hose = 400 mm minimal
radius
•
Ø 60 mm steam hose = 750 mm minimal
radius