Install a differential electrical circuit breaker at the top of the network supplying the humidifiers inside the
general switchboard. In case of several humidifiers, we would recommend installing a differential circuit
breaker per humidifier to prevent a total power cut off of all the humidifiers.
3
2
1
1.
Power disconnector and circuit breaker
2.
Power supply cable
3.
Electrical compartment
Since the risk of electric shock can be fatal,
it is necessary to install circuit breakers.
Q1 : 2 pôles
2A
L2
L1
N
L3
L
PE
The symbol Δ between Q1 & Q2 means that these MCB
are coupled. The power MCB Q2 and control MCB Q1 are
mechanically linked together. So if a fault is detected, the
power and the control circuits are switched off and there
is no voltage on the unit. The unit is really off voltage.
D) 3 phases without neutral: 3 x 380-400V
In this case, a transformer (option) must be installed
(See page 27)
L2
L1
L
N
PE
L2
L1
N
L3
L
PE
RTH 5 - 50
Q2 : 3 poles
U(V)
50-60Hz
220-230V
50-60Hz
GROUND
GROUND
RTH 5
Q2 : 2 poles
U(V)
220-230V
50-60Hz
RTH 5 - 50
GROUND
Q2 : 3 poles
U(V)
50-60Hz
A) U= 2x220-230V
B) U= 3x380-400V sans neutre et 230V
disponible
C) 3 neutre