ElectroVap RTH-V2
29
Pictures and values are not contractual - The devices may be subject to changes without notice
3.8.5 MODBUS RTU & BACNET MSTP COMMUNICATION PARAMETERS
At the risk of communication errors, the network must consist exclusively of humidifiers. The requests passing
on the BUS must in no case exceed 15 bytes.
ModBus RTU
Bacnet MSTP
Communication speed
2400/ 4800/ 7200/ 9600/ 14400/ 19200/ 28800/
38400/ 57600/ 115200/ 230400 bauds Defaut : 9600
Packet size
8 bits
Parity
NON
Stop bit
2
1
Timeout response
5000ms (5sec)
Time between requests (after response received)
Min. 100ms
standard
Nb of registers per request
5 maxi
3.8.6 COMMUNICATION PROTOCOL FOR RS485 INTERFACE - MODBUS & BACNET