ElectroVap RTH-V2
54
Pictures and values are not contractual - The devices may be subject to changes without notice
A7: VAPORIZATION
TOO LONG
Meaning :
The vaporization time between level 3 and 1 is too long.
In that case :
When this message appears, the tank is drained, the general fault
contact is activated and the unit is stopped.
Causes and remedies
1. Faulty power supply.
Using a voltmeter, check the presence of
the supply voltage (Vac) of the heating elements, terminals L1,
L2 and L3.
2.
Continuous water supply.
Check the supply pressure (1> P (bar)>
6), replace the inlets valve if necessary.
3. Water level detector.
Check that the level sensor, detector and the pressure balancing hose are clean
and that nothing prevents the water from circulating. Also check the electrical connections between the
level sensor, the level management board and the main board.
4.
Disjunction of the power circuit 'OFF'. Two possible causes:
- Differential switching off : in this case, check and replace the defective heaters.
- Shutdown by an overload current: make an electrician check the entire electrical part (cables, ter
minals, contactor, heating resistors ...):
5. Electronics.
Replace the level management card or the main board.
Also, check that there is no rising steam or water flow in the electrical compartment.