Installation Guide 

DEVIcomfort 10T

•  be stated in any electrical documentation 

following the installation. 

Installation guidelines

•  It is not recommended to install DEVIcomfort 

10T at temperatures below -5°C.

•  If walking on the elements is necessary 

during installation and carefully purring of 

screed, only use soft shoes.

•  Be careful not to damage the thin mat with 

sharp tools, shovel, bucket etc. 

•  Minimum distance between heating ele-

ments; cable and conductive parts; cable 

and other heating sources such as hot water 

pipes and chimneys, must be at least 50 mm.

•  Heating elements may not touch or cross 

themselves or other heating elements.

•  Cable bending diameter must be at least 

40mm.

•  The heating elements are not to be installed 

on irregular surfaces 

•  The subfloor construction must be secure to 

avoid relative movement after installation.

•  Prepare the  installation site properly by 

removing sharp objects, dirt, etc.

•  The thin mat must be fully embedded in 

screed (fine concrete).

•  Do not lay DEVIcomfort 10T under walls and 

fixed obstacles.

•  Do not place objects that will cause a ther-

mal block e.g. furniture, thick carpets, etc. 

Min. 6 cm air is required

•  The flooring must not have a thermal insula-

tion value of more than R < 0.18 m2K/W 

corresponding to 1.8 Tog.

•  Keep DEVIcomfort 10T clear of insulation ma-

terial, other heating sources and expansion 

joints

•  Position the thin mat so that it is at least half 

the C-C distance from obstacles.

•  DEVIcomfort 10T must always be in good 

contact with the heat distributor (e.g. 

concrete)

•  If additional securing is required hot melt 

glue, double adhesive tape or tile glue can 

be used.

•  When the heating element reaches the area 

boundary just turn and continue the roll-out. 

Do not cut the heating cable.

•  The heating element and especially the 

connection must be protected from stress 

and strain.

Application overview 

The heating element DEVIcomfort™ 10T complies 

with the EN/IEC 60335-1 st EN/IEC 60335-

2-96.

Regarding other types of applications please 

contact your local DEVI sales company. 

GB

DE

DK

EE

FI

LT

NO

PL

RO

SE

5

DEVI VIJUB102

Summary of Contents for DEVIcomfort 10T

Page 1: ...Installationsguide DEVIcomfort 10T 1 DEVI VIJUB102 Installation Guide DEVIcomfort 10T Intelligent solutions with lasting effect Visit DEVI com Installation Guide DEVIcomfort 10T...

Page 2: ......

Page 3: ...n Guide DE Installationsanleitung DK Installationsvejledning EE Paigaldusjuhend FI Asennusohje LT Montavimo vadovas NO Installasjonsveiledning PL Instrukcja monta u RO Ghid de instalare SE Installatio...

Page 4: ...tion and service The screen from each heating element must be connected to earth in accordance with local electricity regulations and connected via a residual current device RCD RCD trip rating is ma...

Page 5: ...lly embedded in screed fine concrete Do not lay DEVIcomfort 10T under walls and fixed obstacles Do not place objects that will cause a ther mal block e g furniture thick carpets etc Min 6 cm air is re...

Page 6: ...icht mit dem Ger t spielen Reinigung und Wartung d rfen von Kindern nur unter Aufsicht eines Erwachsenen durch gef hrt werden Alle Stromkreise vor Installation und War tung abschalten Das Geflecht jed...

Page 7: ...rrutschen und Verschiebungen nach dem Verlegen zu vermeiden Reinigen Sie vor dem Verlegen den Unterbo den sorgf ltig von Fremdk rpern Schmutz usw D nnbettheizmatten m ssen vollst ndig in D nnbett Estr...

Page 8: ...eelementsk rmen skal forbindes til jord i henhold til de lokale regulativer p elomr det og skal forbindes via en fejl str msafbryder RCD RCD rel b r v re maks 30 mA DEVIcomfort 10T skal forbindes ved...

Page 9: ...t indst bt i afretningslag finpuds L g ikke DEVIcomfort 10T under v gge og faste forhindringer Anbring ikke objekter der vil for rsage en termisk blokering f eks m bler tykke t pper osv Der skal v re...

Page 10: ...uleb hendada maandusega kohalike elektrieeskirjade kohaselt ning hendada rikkevoolukaitsme ga RCD Rikkevoolukaitsme maksimaalne rakendu misvool on 30 mA DEVIcomfort 10T k ttekehad tuleb hen dada l lit...

Page 11: ...paigaldage DEVIcomfort 10T k tte kehi seinte ja p randale tihedalt toetuvate takistuste alla rge pange neile esemeid mis takistavad soojuse liikumist nagu m bel paksud vai bad jne Vajalik on v hemalt...

Page 12: ...a paikallisten s hk m r ysten mukaisesti ja kytkett v vikavirtasuojaan VVS RCD RCD n laukaisuvirta on enint n 30 mA DEVIcomfort 10T on kytkett v kytkimen kautta joka mahdollistaa molempien napo jen ir...

Page 13: ...oniin l asenna DEVIcomfort 10T t seinien tai kiinteiden rakenteiden alle l aseta kohteita jotka aiheuttavat l m p esteen kuten huonekaluja ja paksuja mattoja J t v hint n 6 cm ilmatilaa Lattian l mp e...

Page 14: ...grandines Kiekvieno ildymo elemento ekranas turi b ti emintas laikantis vietini elektros taisykli ir prijungtas naudojant liekamosios srov s rengin RCD RCD srov turi b ti iki 30 mA DEVIcomfort 10T tur...

Page 15: ...ti pilnai panardintas skiedin i lyginamasis sluoksnis Neklokite DEVIcomfort 10T po sienomis ar stacionaria ranga Nenaudokite daikt sudaran i kli t ilumai pvz bald stor kilim ir pan Reikalingas ma iaus...

Page 16: ...rmingen p hvert varmeelement skal kobles til jord i samsvar med forskriftene Det skal v re en forankoblet jordfeilbryter Jordfeilbryteren skal v re p 30 mA DEVIcomfort 10T m kobles til via en bryter m...

Page 17: ...ematten m v re helt innst pt i avret tingsmasse termomasse Legg ikke DEVIcomfort 10T under vegger eller faste hindringer Unng plassere gjenstander som vil for r sake termisk blokkering f eks m bler ty...

Page 18: ...konserwacyjne nie powinny by wykonywane przez dzieci bez nadzoru Przed przyst pieniem do monta u lub serwisowania nale y od czy zasilanie od wszystkich obwod w Ekran ka dego elementu grzejnego nale y...

Page 19: ...stalacji Przygotuj miejsce instalacji usuwaj c ostre przedmioty brud itp Cienk mat nale y w ca o ci pokry wylewk betonow lub warstw kleju Nie uk adaj DEVIcomfort 10T pod cianami i sta ymi przeszkodami...

Page 20: ...asigura c nu se joac cu instala ia Cur area i ntre inerea la nivel de utilizator nu trebuie efectuate de copii nesuprave ghea i Deconecta i toate circuitele electrice nainte de instalare i nainte de...

Page 21: ...rafe e neregulate Construc ia aflat sub podea trebuie s fie sigur pentru a se evita apari ia mi c rii relative dup instalare Preg ti i corespunz tor locul de instalare ndep rt nd obiectele ascu ite mu...

Page 22: ...t ng av all str m f re installation och underh ll Sk rmen p alla v rmeenheter m ste jordas i enlighet med lokala els kerhetsregler och anslutas via en jordfelsbrytare RCD Jordfelsbrytarens maxtr skel...

Page 23: ...smuts jord osv Den tunna mattan m ste vara fullst ndigt omsluten av avj mningsmassa finbetong L gg inte DEVIcomfort 10T under v ggar eller fasta f rem l Placera inte ut f rem l som kan orsaka termisk...

Page 24: ...Installation Guide DEVIcomfort 10T DEVI VIJUB102 24...

Page 25: ...Installation Guide DEVIcomfort 10T 25 DEVI VIJUB102...

Page 26: ...Installation Guide DEVIcomfort 10T DEVI VIJUB102 26...

Page 27: ...Installation Guide DEVIcomfort 10T 27 DEVI VIJUB102...

Page 28: ...thout subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of...

Reviews: