background image

Installation Instructions       Devireg 530, 531 and 532

AUS     Installation Instructions Devireg™ 530, 531, and 532

Summary of Contents for devireg 530

Page 1: ... Article 08095823 Version 01 01 ...

Page 2: ... Installation Instructions Devireg 530 531 and 532 AUS Installation Instructions Devireg 530 531 and 532 ...

Page 3: ...structions Installing the floor sensor for the Devireg 530 and 532 Placement of the Devireg 530 531 and 532 Connection diagrams for the Devireg 530 531 and 532 Trouble shooting Technical Specifications Warranty conditions and Warranty Certificate The installation must only be carried out by a licensed electrician ...

Page 4: ...31 This thermostat is supplied with a built in air sensor for control of the desired air temperature only The Devireg 532 Is used for air and floor sensing This thermostat has a built in air sensor and an exter nal floor temperature limit sensor The room sensor is used for control of the room air temperature The floor limiter is used to maintain a maximum floor temperature for wooden floors and ot...

Page 5: ... taking off the front cover and with a screwdriver adjust the sunken temperature dial in the top left hand corner For wooden floor constructions DEVI recommend the temperature is limited to a maximum of 30 C Maximum limiter setting for different floor constructions Tiles on timber 30 C Carpet vinyl on timber 35 C Wooden floors parquet plank etc 27 C Tiles on concrete or screed 35 C 2 Maximum floor...

Page 6: ... is on but no heating is required Flashing green light means there is a problem with the floor sensor only applicable for 530 and 532 Please refer to section about Trouble shooting for further information Is used for setting the thermostat to frost protection mode i e keeping the room floor temperature depending on type of thermostat at 5 C 3 Neon light indications LED devireg 550 15 20 25 30 35 L...

Page 7: ...ireg 530 Series you must first remove the front cover To remove the front cover gently press the release tabs in the vents at both sides and then pull off the front You do not need to remove the temperature dial 1 2 3 4 5 6 2 3 4 5 6 4 5 6 2 3 4 5 6 3 4 5 2 3 4 5 6 2 ...

Page 8: ...e operating instructions Where a floor sensor is used it is recommended to install it inside a conduit sealed at the end in the floor enabling easy replacement of the floor sensor if required If installed without a conduit the floor sensor must be installed so that it is inaccessible and not in contact with any conductive building parts If the supplied floor sensor is too short longer ones can be ...

Page 9: ...stallation height typically between 1 1 5m especially when Devireg 531 532 is used At least 500mm away from windows doors that will be left open occasionally In damp rooms it should be installed on an even surface in accordance with AS NZ 3000 ...

Page 10: ... If being used as an air sensing thermostat then it should not be on a cavity wall where it can be affected by draughts Not on the inner side of a wall facing the outside ...

Page 11: ...connection do not use NC no connection do not use Devireg 530 Devireg 531 Devireg 532 15 A Max Load NC N L 5 45 C N NTC L LOAD LOAD N L NTC 15 A Max Load NC NC NC 5 35 C N L LOAD LOAD N L N L 15 A Max Load NC N L NTC 5 35 C 20 50 C N NTC L LOAD LOAD N L Maximum temperature limiter setting ...

Page 12: ...11 N N ...

Page 13: ...stat terminals and that all connections are tight and mak ing contact 2 Mains voltage terminal 1 and 3 Ensure that supply voltage 240v is at terminals 1 and 3 if not then check that the RCD and contactor are on 3 Thermostat output terminal 2 and 4 Measure the voltage at terminal 2 and 4 when the temperature dial is turned up and the neon has turned red The reading should be the same as previously ...

Page 14: ...sured should be within the speci fied range according to the technical specifications If not replace the NTC sensor 4 Heating cable terminal 2 and 4 Disconnect the heating cable from terminal 2 and 4 on the thermostat Measure the resistance of the heating cable with an ohm meter it is now possible to calculate the installed wattage using the following formula An insulation tester must also be used...

Page 15: ... thermostat Floor sensor open circuit If the floor sensor NTC is disconnected or open circuited the thermostat will be constantly off due to the sensor interrupt the LED will flash green Disconnect the external NTC sensor from terminals 5 and 6 on the thermostat Connect an ohm meter to the NTC sensor wire measuring the ohm value The measured value should be within specified range according to the ...

Page 16: ...oltage 240 VAC 10 20 50 Hz Power consumption Max 0 25W Relays Resistive load Inductive load 240V 15A cos φ 0 3 Max 4A Sensing unit NTC 15 kOhm at 25 C Sensing values 0 C 20 C 50 C 42 kOhm 18 kOhm 6 kOhm Hysteresis 0 2 C Ambient temperature 10 to 30 C Frost protection 5 C ...

Page 17: ...he thermostat has a built in monitoring circuit which will switch off the heating if the sensor is disconnected or short circuited LED indicator No light Red light Green light Green light flashing The system is off The temperature set point is not reached The temperature set point is reached Floor sensor fault IP class 31 Dimensions 85 mm x 85 mm ...

Page 18: ...under this warranty is to repair or replaceany product which within the above stated time periods is found toour satisfaction to be defective free of charge to the customer However the labour cost for removing and or refitting any productwill be at the customer s expense In the case of any removableproducts such as Thermostats these are to be returned to the placeof purchase or to DEVI Sydney where...

Page 19: ...ovided the fault is inspected by or submitted to DEVI or an authorised DEVI dealer Please note that the WARRANTYCERTIFICATE must be completed in English or local language DEVI shall undertake any repair free of charge or supply the customer with a new unit Repairs shall be carried out at no further cost to the customer In the case of faulty Devireg thermostats DEVI reserves the right to repair the...

Page 20: ...ss Postal code Electrical Installation by Type of thermostat Installation date Production code Suppliers Stamp Please observe In order to obtain the DEVI Guarantee the following must be carefully filled in See other conditions on previous page DEVI A S DK 7100 Vejle Phone 45 76 42 47 00 Fax 45 76 42 47 03 ...

Reviews: