5. Install sensor for Devireg™ 530 and 532
The floor sensor is inserted into a 10mm or 13mm
conduit which is sealed at the end to prevent
penetration of concrete, screed, etc into the conduit.
The Minimum
bending radius for the conduit is 50 mm.
The sensor conduit must be placed in between two
cable runs.
To avoid cracks in the concrete floor you must
ensure that the floor is completely hardened before
the heat is switched on. Refer to the operating
instructions.
Where a floor sensor is used, it is recommended to
install it inside a conduit, sealed at the end in the
floor, enabling easy replacement of the floor sensor
if required. If installed without a conduit, the floor
sensor must be installed so that it is inaccessible and
not in contact with any conductive building parts.
If the supplied floor sensor is too short, longer ones
can be purchased from you local DEVI supplier or
it can be extended upto 50m using double insulated
cable .
The floor sensor is a LIVE cable; therefore any exten-
sion made to the sensor wiring should be treated as
for normal mains voltage cabling.