HBE3 M3 LE3/LS3 Installation Leaflet 

DIL-0300-0068 

Revision - B 

 

25/04/2022 

 

5.

 

 

 
 
 
 
 
 
 

Connect the battery. 

6.

 

 

 
 
 
 
 
 
 

 

Install the fitting in the recessed bracket and secure in 

place. 

7. 

Reconnect the power supply and check that the green LED 

indicator is illuminated. This green indicator confirms the 

battery is charging. 

 

LS3 only: 

 

Any faults with the luminaire will be displayed by a flashing 

red indicator. 

 

Normal operation - Green indicator 

Battery failure - Red indicator, once every 3 seconds 

Lighting source failure - Red indicator, twice every 3 seconds 

Less than rated duration time - Red indicator, three times 

every 3 seconds 

 

8.           

Self-Test (LS3 only):

 

 

Every month, the luminaire will undergo an 

automatic test which lasts for 10 minutes. An 

annual duration test will also occur for a total 

of 3 hours. The luminaire will return to 

normal operation once the test has finished. 

 

During testing, the battery is not charging 

and the red LED indicator will flash 

continuously. 

9.

 

Do NOT cover the luminaire in any way and 

provide sufficient ventilation. 

 

Installation is now complete. 

 

Summary of Contents for HBE3 M3 LE3

Page 1: ...operational with the cover removed NOTE INSTALLATION AND OPERATION OF THE LUMINAIRE BEYOND ITS SCOPE OF SUPPLY WILL INVALIDATE THE WARRANTY 1 Ceiling Wall surface mount Drill a hole in the ceiling and feed the cable through 2 Remove the top cover and drill the cable entry hole in the indicated location 3 Drill two fixing holes and secure the cover in place with two screws 4 Pass the cable through ...

Page 2: ...ll two fixing holes and secure the bracket in place with two screws 4 Pass the cable through and wire directly into the terminal block Secure the mains cable using the internal cable clamp 5 Connect the battery 6 Attach the top cover to the suspended bracket and secure the fitting in place 1 Side mounted Drill a hole in the ceiling and feed the cable through 2 Remove the top cover and drill the ca...

Page 3: ...nal cable clamp 5 Connect the battery 6 Attach the top cover to the side bracket and secure the fitting in place 1 Recessed Make a cut out in the ceiling using the dimensions pictured 2 Remove the top cover and drill the cable entry hole in the indicated location 3 Pass the cable through and install the recessed bracket 4 Pass the cable through and wire directly into the terminal block Secure the ...

Page 4: ...attery failure Red indicator once every 3 seconds Lighting source failure Red indicator twice every 3 seconds Less than rated duration time Red indicator three times every 3 seconds 8 Self Test LS3 only Every month the luminaire will undergo an automatic test which lasts for 10 minutes An annual duration test will also occur for a total of 3 hours The luminaire will return to normal operation once...

Reviews: