9083P
Multifunction Tester
Operating Instructions
328A561 revision1.1
- 21 -
10mA
30mA
100mA
When the required settings have been selected, press
the TEST key to begin the sequence.
Note: The 9083P will determine the fault voltage that
may appear on the protective conductor
during the test. If the fault voltage is greater
than 25V the 9083P will indicate >25V on the
LCD, but the user may proceed with the test. If
the fault voltage is great than 50V, this is
indicated on the LCD and the test is inhibited.
If the fault voltage is less than 50V the test sequence
will proceed and the trip times are shown in the primary
display.
When the sequence is completed, the RCL key (F3) is
used to recall the measurements.
5.8 RCD Trip Time Tests
The 9083P will only allow the Earth Loop
Impedance test to be performed if the correct
voltages are detected between phase-neutral
(PN illuminated), phase-earth (PE illuminated)
and neutral-earth (NE
not
illuminated).
Leakage currents or voltage on the protective
conductor may influence the measurement.
Note: The 9083P will determine the fault voltage that
may appear on the protective conductor
during the test. If the fault voltage is greater
than 25V the 9083P will indicate >25V on the
LCD, but the user may proceed with the test. If
the fault voltage is great than 50V, this is
indicated on the LCD and the test is inhibited.
Use the rotary switch to select the ½ I
∆
n, I
∆
n or 5 I
∆
n
test position.