Element Series Manual 

 

Page | 3  

 

Feed Water Requirements 

1.

 

Plumbing feeding the element must be at least ¾” in diameter.

 

2.

 

Filtered water must be used on the membrane

. The element has a 5 micron filter to remove 

particles and will drastically extend the life of the membrane. Changing these filters every 
month is recommended to extend the life of the membrane. Follow instructions on page 10 to 
change filters.  
 

30-0021-XX 

Replacement 5 Micron Filter 

30-0122-XX 

Alternate Replacement 5 Micron Filter 

 

3.

 

Soft Water is recommended.

 Excessive water hardness or iron concentrations may form scale 

over the membrane and cause clogging. This will drastically reduce the useful life of the 
membrane. Installing a water softener before each system to reduce hardness and iron is 
recommended.  

4.

 

Anti-Scalent recommended.

 Slightly soluble contaminants like calcium sulfate, silica, or colloidal 

clay will cause clogging. A continuous injection of an anti-scalent should be used if these 
contaminants are present.  

 
 
Recommended Specifications:

 

Total Dissolved Solids    

< 2000 ppm 

 

Hardness 

 

< 17 ppm 

Iron 

 

 

 

< 0.1 ppm 

 

Manganese  

 

< 0.1 ppm 

Silica   

 

 

< 10 ppm 

 

Hydrogen Sulfide 

< 0.0 ppm 

Organics 

 

 

< 2 ppm TOC 

 

Turbidity 

 

< 0.1 NTU 

Feed SDI 

 

 

< 3.0 

 

 

pH 

 

 

 10 

Free Chlorine   

 

0.1 ppm 

 

Temperature   

40-95°F 

Inlet Pressure   

 

20 

 80 psi 

 
 
Membrane Operating Parameters:

 

Membrane 

  

 

Thin Film Composite 

 

Typical Operating Pressure 

150-200 psig 

 

Max Pressure:    

400 psig 

pH Range Continuous   

 10   

 

pH Range, Cleaning 

 12 

Max Pressure Drop 

 

10 psig per membrane  Max Calcium Hardness  < 0.0 LSI 

Nominal Rejection 

 

98% 

 

 

Max Temperature 

113°F 

 
 
 

Summary of Contents for Element ELE-1600

Page 1: ...olved Solids TDS and is corrosive Product Permeate water should not be exposed to metal piping like brass copper or steel Systems installed on metallic plumbing must use Pro Products LLC Neutra 7 for protection from corrosion 2 System produces Concentrated Water The element produces water with very high TDS which can be dangerous Concentrate Reject water will contain a higher concentration of most...

Page 2: ...there is no pressure from the supply c Plumb the water source to the FPT inlet Supply In d Plumb the MPT Permeate Outlet to its endpoint this will contain product water e Plumb the MPT Concentrate Outlet to its endpoint this will contain concentrate water f Either the concentrate or permeate outlet must not be plumbed to a pressurized line If both outlets are pressurized the system will not prime ...

Page 3: ...the membrane Installing a water softener before each system to reduce hardness and iron is recommended 4 Anti Scalent recommended Slightly soluble contaminants like calcium sulfate silica or colloidal clay will cause clogging A continuous injection of an anti scalent should be used if these contaminants are present Recommended Specifications Total Dissolved Solids 2000 ppm Hardness 17 ppm Iron 0 1...

Page 4: ...Element Series Manual Page 4 Control A diagram of the Element controller is shown below ...

Page 5: ...Element Series Manual Page 5 Inner Control Box ...

Page 6: ...Element Series Manual Page 6 CPU Board Diagram ...

Page 7: ...Element Series Manual Page 7 DIP Switch Settings See Page 8 for details on RO Program settings ...

Page 8: ...lush Program 3 Permeate flush low pressure inlet valve closed Program 4 Low pressure feed water flush The program details are shown below These features are disabled by default due to the potential for confusion on the part of end users in the field They can be enabled when needed via the OEM PC programming interface which allows changes to all of the values shown above ...

Page 9: ...Element Series Manual Page 9 Control Programming Parameters Explained ...

Page 10: ...Element Series Manual Page 10 Control Programming Parameters Explained Continued ...

Page 11: ...ottom of the filter housing by rotating counterclockwise Excessive force does not need to be used when tightening the housing but the housing should be secure and snug Changing a Membrane 1 Turn off the control and the incoming water supply and depressurize the incoming water line 2 Remove screws from top of membrane 3 Remove 2 metal securing brackets from top of membrane 4 Slide membrane changing...

Page 12: ...Element Series Manual Page 12 Notes ...

Reviews: