background image

the PEN HOME or ALARM buttons will store the new 
settings. The unit will take one minute to exit ALARM 
Set Mode once the ALARM button is pressed.

•  If the ALARM is triggered, the LED will show as solid 

red and the ALARM will sound. Press the ALARM 
button to silence the audible ALARM.

ALARM RELAYS (KT6P5)

The SPST 24V 500mA RELAY contacts are normally open 
and will close on ALARM conditions when the ALARMS 
are enabled. RELAY contacts are always functional when 

the ALARM is enabled. The RELAY will close only during 
minimum and maximum ALARM conditions. RELAYS will 
not operate under battery only power conditions.

7-DAY CHART ROTATION
0 TO 100°F

IMPORTANT

Dickson Chart Recorder accuracy specifications are only valid with the use of authentic 
Dickson brand charts and pens. The specifications for chart printing, die cutting and paper 
absorption rates, and the complementary bleed rate specifications of pens are critical factors 
in determining system accuracy.

ON/OFF

The ON/OFF key turns the unit on and off.

PEN HOME

If the pen is located on the outside edge of the chart, 
press PEN HOME to move pen to recording position. If 
the pen is located on the chart, press PEN HOME to move 
the pen to the outside edge of the chart.

ALARM (KT6P5)

•  To set the ALARM, make sure unit is on and press and 

hold the ALARM button. The LED will blink red rapidly 
for about five seconds, then the LED will turn solid 
green. Release the ALARM button and the LED will 
turn solid red. At this point the display will show “On” 
or “Off”. Pressing either the ADJUST-UP or ADJUST-

DOWN buttons, located on the back of the unit next 
to the DIP SWITCH, will toggle the ALARM on or off.

•  Pressing PEN HOME will scroll to the next ALARM 

option. The options are as follows:

 

»

ALARM on or off

 

»

Pen 1 ALARM minimum

 

»

Pen 1 ALARM maximum

•  In order to set pen ALARM minimum and maximum, 

pressing ADJUST-UP will increase the ALARM value, 
and pressing ADJUST-DOWN will decrease the ALARM 
value. There is acceleration if the ADJUST-UP button 
is held down.

•  Repetitively pressing the PEN HOME button will scroll 

through the three options until the ALARM button 
is pressed to exit from ALARM adjust. Each press of 

TO BEGIN OPERATION

1.  Remove the protective pen cap.
2.  Connect probe. Make sure the KTC probe is 

connected firmly to the Replaceable Sensor™ and 
that the Replaceable Sensor™ is plugged in firmly to 
the chart recorder.

3.  Insert 4AA batteries and plug in AC adapter (Reference 

Guide on back). Unit will power on.

4.  The instrument will move pen to the appropriate 

readings.

5.  Install the chart that matches the DIP SWITCH settings 

(Reference settings label on the battery door to set the 
correct dip switch positions for the chart)

6.  Press the PEN HOME key to move the pen to the 

outside of the chart. The pen is automatically raised 
off the chart.

7.  Remove the old chart, place the new chart on the 

CHART HUB being certain that the edge of the chart 
slides under the Chart Guide Clip located at the 
outside of the chart.

8.  Set the appropriate time. Set the chart time manually 

by inserting a coin into the groove in the CHART HUB 
and turning clockwise until the correct hour (and day 
if applicable) on the chart is referenced to the timing 
arrow (just to the right of the pen tip on the dial). Press 
PEN HOME to move the pen back onto the chart.

The KT6 operates on AC power with an optional 4AA battery backup. Depending on 
chart rotation selected and model; battery backup will last approximately 3 days.  

Note: ALARM and RELAYS will not operate under battery only power.

LED Indicators

•  Solid Green 

 AC Power with Battery Backup 

•  Solid Red 

 AC Power with Low Battery or No Battery

•  Blinks Green 

— 

Battery Only

•  Blinks Red 

— 

Battery Only (Low Battery)

To setup the KT6 recorder for your specific 
application, you might need to change some of the 
DIP SWITCHES. The DIP SWITCHES are located on the 
back of the unit. Use a pen or small screw driver to 
flip the switches.

Remember to install the correct chart to match the 
corresponding DIP SWITCH setting.

GETTING STARTED

DIP SWITCH SETUP

QUICK START

KEYPAD AND BUTTON FUNCTIONS

POWER

1

2
3

CH1 = PINS 1,2,3

  Pins 1 and 2 make contact    

  when  CH1 is in alarm
•  Pins 1 and 3 make contact    

  when CH1 is not in alarm

PEN

HOME

POWER

LED

ON/OFF

ALARM

(Alarm button on KT6P5 only)

RECORDING TIME

7 Day

#2 DOWN

24 Hour

#2 UP

RECORD IN °F OR °C

°F

#3 DOWN

°C

#3 UP

TEMPERATURE RANGE

Select the temperature range that matches the chart paper

0° to +100° F/C

#4 DOWN 

 #5 DOWN 

 #6 DOWN

-50° TO 0° F/C

#4 DOWN 

 #5 DOWN 

 #6 UP

-100° TO 0° F/C

#4 DOWN 

 #5 UP 

— 

#6 UP

-50° TO 50° F/C

#4 UP 

— 

#5 DOWN 

— 

#6 DOWN

0° to 50° F/C

#4 DOWN 

— 

#5 UP 

— 

#6 DOWN

50° to 100° F/C

#4 UP 

— 

#5 UP 

— 

#6 UP

0° to 500° F

#4 UP 

— 

#5 UP 

— 

#6 DOWN

0° to 250° F/C

#4 UP 

— 

#5 DOWN 

— 

#6 UP

1

2

3

4

5

6

7

8

Slide toggle UP for ON position

Dip Switches 7 and 8 are not active on this recorder

Slide toggle DOWN for OFF position

2

3

Summary of Contents for KT6

Page 1: ...com Telephone 630 543 3747 Email support dicksondata com 930 S Westwood Avenue Addison IL 60101 KT6 6 TEMPERATURE CHART RECORDER USER MANUAL PRODUCT GUIDE BATTERY COMPARTMENT DIP SWITCHES ADJUST BUTTONS AC ADAPTER REPLACEABLE SENSOR PORT REFERENCE GUIDE ...

Page 2: ...r and that the Replaceable Sensor is plugged in firmly to the chart recorder 3 Insert 4AA batteries and plug in AC adapter Reference Guide on back Unit will power on 4 The instrument will move pen to the appropriate readings 5 Install the chart that matches the DIP SWITCH settings Reference settings label on the battery door to set the correct dip switch positions for the chart 6 Press the PEN HOM...

Page 3: ... display Note Make sure to press the ADJUST DOWN button first so the unit will not turn off 2 To raise the unit of measurement press the ADJUST DOWN button To lower the unit of measurement press the ADJUST UP button 3 When Calibration is complete press the ON OFF button The adjustment is stored in memory even afteryou turn the unit off or ifAC power fails Note Hold ADJUST UP orADJUST DOWN button f...

Page 4: ...from the unit Whywon t the chart recorder respond to changes Is the unit locked up This can be confirmed by pressing any of the buttons on the keypad if the unit is locked up there will be no response to button presses and the unit may appear to be working but the readings won t change also the chart will not rotate Remove power and batteries and then re power Whywon t the unit power up Remove the...

Reviews: