Page 1 

Digiflex Vision 64  Keyswitch wiring & programming                                            RDC_3138_E_TA 

 

Digiflex Vision 64 Alarm Panel 

 

Keyswitch wiring   

 

Keyswitch programming   

Background: There are three (3) Outputs available. 

 

Outputs are ‘Open Collector’ @50mA switching negative - for heavier loads a relay must be used.  

  Outputs can be used for e.g. Keyswitch, opening gates or doors etc. 

  Ensure there is a common negative between Permaconn and the device being switched.  

  The outputs can be Opened, Closed or Pulsed remotely using the Permaconn Atlas web portal.  

 

The Pocket Secure App can only ‘Pulse’ the Outputs. A Pulse is approx 1sec. 

 

  These outputs when wired to a Keyswitch zone on the Alarm Panel can arm & disarm up to a  

maximum of three (3) areas when using ‘Pocket Secure’ app. 

  Each area should be independently controlled using a separate Keyswitch zone. 

  Arm/Disarm reporting 

MUST be Enabled

. Pocket Secure App requires this for its status notifications. 

  Test each Output by placing the +ve leg of a multi meter on the +ve terminal that supplies power to the 

Permaconn, then place the -ve leg of a multi meter on the Output terminal you wish to test. Pulse the 
selected Output the result should go from 0v DC to 12v DC for approx 1sec and back to 0vDC.

 

 

 

 

Digiflex Vision 64  Alarm Panel 

Enter Program mode: Installer code (default 1234) + menu. 
(

Red and Green LED’s on the keypad will flash indicating program mode). 

 
Method 1

Using RF Receiver ‘Input’.

 

Menu 3-5-0 

Select 02 (Pulse On/Off). 

 
E.g. 1: Using the RF Input terminal

 

 

 

RF DATA INPUT

Bosch 6000

 

 

 

Compatible with ‘Pocket Secure’ remote arming App, available on iTunes, Google Play and the Windows Phone Store. 

Digiflex Vision 64 