2 - 8
PL-6900 Series User Manual
Specifications
(Interface Circuit)
(Connection Example)
Cable
R
PC357
Dsub 25pin
connector
N3904
DOUT(-)pin 7
Alarm Output(-)pin 9
Lamp Output(-)pin 21
DOUT(+)pin 8
Alarm )pin 10
Lamp )pin 22
+5V
4.7k
Ω
Output Port
(Interface Circuit)
(Connection Example)
Cable
DC12 to
24V
External
Power
Reset Input(+)pin 5
DIN0(+)pin 6
DIN1(+)pin 13
(12 to 24V)
R
PC357
Reset Input(-)pin 11
DIN0(-)pin 12
DIN1(-)pin 24
D-sub 25 pin
Connector
+5V
3.3k
Ω
1/4W
Input Port
Input Port (Dual use of DIN, Remote Set Input Port)
- External Power : DC12V to 24V connection possible
- Input Hold
: Hold Diode
-
Isolation
: Used (Photo isolation)
Output Port (DOUT, Alarm Output, Lamp Output Port)
- Output Spec.
: DC 24V 100mA (MAX)
-
Isolation
: Used (Photo isolation)