Environmental Monitoring Unit (EMU)
3–12 UltraSCSI RAID Enclosure
Table 3–3 Temperature Set Point Rules
1. Enter all temperatures in degrees Centigrade (°C). You cannot enter
temperatures as fractions, decimals, or degrees Fahrenheit (°F).
2. The EMU set point (sensor_3) temperature must be a minimum of
6°C (11°F) greater than the highest expected ambient (intake)
temperature.
3. The backplane set points (sensor_1 and sensor_2) must be a
minimum of 13°C (23°F) greater than the highest expected ambient
temperature. (7°C [13°F] greater the EMU set point).
4. The backplane set points (sensor_1 and sensor_2) must be the same
temperature.
5. When operating with EMU firmware versions 1.0 or 1.2, you cannot
use the command:
set emu sensor_
n_setpoint=default.
6. When operating with EMU firmware versions 1.0 or 1.2, you must
use the commands
set emu sensor_
n_setpoint=nn,
where
nn is the temperature in °C.