Page 1: ...Automatic Fail Over Switch USER S GUIDE ...

Page 2: ...ndles brown out blackout wiring fault detection and loss of power detection Fast Switching Switching is fast and fully automatic Switching typically occurs in less than 10ms 01s 4 Switched L 15 outlets Four switched outlets are provided fed by two 7 length 14Ga L 15 power cords LCD and RS 232 Serial Status Display Status of the switch may be monitored on the LCD display or remotely via the RS 232 ...

Page 3: ...not adversely affect operation of the switch Total rated load current is 12A Installation Connect the input cords to any two AC power supplies For example you may connect a UPS and a Grid power source to ensure that attached equipment will continue to run in the event of a UPS failure Operation Operation is fully automatic When the primary preferred input power supply fails loads will quickly be s...

Page 4: ...ok at the product FAQ page solutions You may FAX questions to 408 541 8459 or email support digital loggers com For phone support call 408 330 5599 with the following so we can better serve you The firmware version displayed when the switch is powered up A description of the inputs and the loads attached Frequently Asked Questions A list of FAQs is maintained at www digital loggers com ATSFAQs htm...

Page 5: ...let Rating UL CSA 12A 120VAC Input Frequency 50 60Hz Only Operating Temperature 30o to 170oF 34o to 77oC Options OEM Custom firmware Power Supply Rating 70 140VAC Survives spikes to 160V Outlet Specicifcation UL CSA L 15 Standard Outlet Switching SIngle switched circuit Output Current 12A Power Dissipation 3 1W Max Power Fail Hold Over 1500 ms min 2500 ms typ Relay Contact Spec 20A NO AC 277V Seri...

Page 6: ...h proper RMA procedures DLI s liability for repair or replacement is to DLI s customer ONLY WARRANTY SERVICE DOES NOT INCLUDE DAMAGE DUE TO OPERATION ON 240VAC FOR WHICH THE PRODUCT IS NOT INTENDED No warranty service will be provided without an original invoice from DLI and an RMA number provided by technical support RMA material must be shipped prepaid to DLI RMA numbers are valid for 15 days fr...

Page 7: ...SMART FAILOVER SWITCH 7 ...

Page 8: ...Download a Manual Frequently Asked Questions 2695 Walsh Avenue Santa Clara CA 95051 Tel 408 330 5599 Fax 408 541 8459 www digital loggers com Register Online for Free Tech Support Free Upgrades ...

Reviews: