Frequency
Converter mode
setting (10)
①
Enter the setting interface. Press and hold the function
setting key
for more than 2 seconds, then come to
setting interface, Press and hold the scroll key
for more
than half a second(less than 2 seconds), select the function
setting, choose output frequency setting interface, the
letters “OPF” will flash.
②
Enter the output frequency of converter mode setting
interface. Press and hold the function
setting
key
for more
than half a second(less than 2 seconds),the letters “OPF” will
stop flashing. The letters below the “OPF” will flash. Press
and hold the scroll key
for more than half a second (less
than 2 seconds), select the output frequency, “50Hz”(output
fixed to 50Hz and active converter mode) or “60Hz”(output
fixed to 60Hz and active converter mode) or “IPF”(inactive
converter mode and active normal mode)
③
Confirm the setting. After selecting converter mode output
frequency, press and hold the function setting key
for
more than half a second (less than 2 seconds). Now, the
setting is confirmed.
④
Exit from the setting interface. Press and hold function
setting key
for more than half a second (less than
2 seconds), exit from the setting interface and return to
main interface.
IPF:
UPS output frequency with the same frequency as the
mains input.
50.0Hz:
UPS output frequency is fixed at 50.0Hz, independent
of the mains input frequency.
60.0Hz:
UPS output frequency is fixed at 60.0Hz, independent
of the mains input frequency.