Table 9. UPS Model List (All Models)
Model
Power Level
Rear Cover Diagram
DN-170089
1000 VA/900W
FIG. 14
DN-170090
1500 VA/1350W
FIG. 14
DN-170092
2000 VA/1800W
FIG. 15
DN-170091
3000 VA/2700W
FIG. 16
Table 10. Weights and Dimensions (All Models)
Model
Dimensions (W *D *H)
Weight
DN-170089
440*430*86.5mm 15.7
kg
DN-170090
440*430*86.5mm 18.7kg
DN-170092
440*552*86.5mm 22.2
kg
DN-170091
440*720*86.5mm 25.5kg
Table 11. Electrical Input (All Models)
Nominal Frequency
50/60 Hz auto-sensing
Frequency Range
45–55 Hz(50Hz)/55-65Hz(60Hz) before transfer to battery
Bypass Voltage Range
+5%, +10%, +15%, +25% (+25% by default), -20%, -30%,
-45%(-45% by default)
Table 12. Electrical Input (All Models)
Model Default Input
(Voltage/Current)
Selectable Input Voltages
Voltage Range at
100% Load
DN-170089
230V / 4.4A
200
,
208
,
220
,
230
,
240 160-290Vac
DN-170090
230V/6.5A
200, 208, 220, 230, 240
160 - 290Vac
DN-170092
230V / 8.7A
200
,
208
,
220
,
230
,
240 160
-290Vac
DN-170091
230V/13.0A
200, 208, 220, 230, 240
160 - 290Vac
Table 13. Electrical Input Connections (All Models)
Model Input Connection
Input Cable
DN-170089
IEC320 C13-10A
IEC320 C14-10A
DN-170090
IEC320 C13-10A
IEC320 C14-10A