Table 14. Electrical Output (All Models)
High Voltage Models
Nominal Outputs
220/230/240V
(voltage configurable orauto-sensing)
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
Frequency
50 or 60 Hz, autosensing
Output Overload
(Normal Mode)
108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Output Overload
(Bypass Mode)
100%±5%–130%±5%: Load transfers to Fault mode after 20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after 2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after 15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
Output Overload
(Battery Mode)
108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Voltage Waveform
Pure Sine wave
Harmonic Distortion
<3% THD on linear load; <5% THD on non-linear load
Transfer Time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power Factor
0.9
Load Crest Factor
3 to 1