Table 18. Battery
Internal Batteries
Battery Configuration
1K VA: 24Vdc (2, 12V, 9 Ah)
1/1.5 KVA: 36Vdc (3, 12V, 9 Ah)
2K VA: 48Vdc (4, 12V, 9Ah)
2/3K VA: 72 Vdc (6, 12V, 9Ah)
Fuses
(2) 30A/250Vdc fuses
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
8 hours to 90%
8
Troubleshooting
The following messages are the information that users would find on UPS when it meets some problems. Users
can judge if the fault is caused by external factors and know how to deal with it by making full use of the
information.
If you need help, contact our service department, the following messages should be provided for analysis:
UPS MODEL NO. and SERIAL NO.
Date of fault happened
Detailed description of the problem (includeindicator statements on cover)