4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table 

below.  

Symptom Possible 

cause 

Remedy 

No indication and alarm even 

though the main is normal.   

The AC input power is not 

connected well. 

Check if input power cord 

firmly connected to the 
mains.  

The AC input is connected 

to the UPS output. 

Plug AC input power cord 

to AC input correctly.   

The icon 

  is flashing and the 

warning code 

  is lighting on 

LCD display. Alarm is sounding 
every second. 

EPO function is activated. 

Set the circuit in closed 
position to disable EPO 

function. 

The icon 

  is flashing and 

 

is lighting on LCD display. Alarm is 

sounding every second. 

Line and neutral 

conductors of UPS input 
are reversed. 

Rotate mains power socket 

by 180° and then connect 
to UPS system. 

The icon 

and 

 flashing on 

LCD display and alarm is sounding 

every second. 

The external or internal 

battery is incorrectly 
connected. 

Check if all batteries are 

connected well. 

Fault code is shown as 27 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery voltage is too high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too low 
or the charger is fault. 

Contact your dealer. 

The icon 

 and

is flashing 

on LCD display and alarm is 

sounding twice every second. 

UPS is overload   

Remove excess loads from 

UPS output. 

UPS is overloaded. Devices 

connected to the UPS are 
fed directly by the 

electrical network via the 

Bypass. 

Remove excess loads from 

UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 

the mains. 

Remove excess loads from 
UPS output first. Then shut 

down the UPS and restart 
it. 

Summary of Contents for DN-170040

Page 1: ...USER MANUAL DN 170040 DN 170041 Online UPS Uninterruptible Power Supply System Version 1 0 ...

Page 2: ...l view 3 2 2 Install the UPS 4 2 3 Setup the UPS 4 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 7 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 11 3 3 Audible Alarm 12 3 4 LCD display wordings index 12 3 5 UPS Setting 13 3 6 Operating Mode Description 16 3 7 Faults Reference Code 16 3 8 Warning indicator 17 4 Troubleshooting 18 5 Storage and Maintenance 20 6 Specifications 21 ...

Page 3: ... over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked mains cable e g the mains cable of your computer to connect the UPS system to the bu...

Page 4: ...s must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any...

Page 5: ...table Model No Type Model No Type DN 170040 Standard DN 170040L Long run DN 170041 DN 170041L 2 1 Rear panel view 1K 1 5K IEC 2K IEC 3K IEC 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Network Fax Modem surge protection 6 Emergency power off function connector EPO 7 USB communication port 8 RS 232 c...

Page 6: ...l Connect the AC input and re connect battery wires Put the front panel back to the unit This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 Tower Installation Step 1 Step 2 Step 3 2 3 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded rece...

Page 7: ...UPS is equipped with intelligent slot perfect for either SNMP or AS400 card When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options PS USB port and RS 232 port can t work at the same time Step 4 Network connection Network Fax Phone surge port Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS ...

Page 8: ...ery Replacement NOTICE This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads hot swappable battery design Replacement is a safe procedure isolated from electrical hazards CAUTION Consider all warnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages ...

Page 9: ...w to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Tapes Tapes Ta...

Page 10: ...astic shell as below chart Then battery kit is assembly well 4 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Dummy battery Tapes Tapes ...

Page 11: ... tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Tapes Tapes ...

Page 12: ...this button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltag...

Page 13: ...nformation Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is w...

Page 14: ...t voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger SF Site Fault EP...

Page 15: ...put voltage is 240Vac For 100 110 115 120VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac 02 Frequency Converter enable disable Interface Setting CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency setting I...

Page 16: ...S is off Interface Setting ENA Bypass mode is enabled when UPS is off DIS Bypass mode is disabled when UPS is off Default 07 Programmable outlets enable disable Interface Setting ENA Programmable outlets enable DIS Programmable outlets disable Default 08 Programmable outlets setting Interface Setting 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect ...

Page 17: ...ptable input voltage range is from 160V to 260V 170 270 flashing in turns The acceptable input voltage range is from 170V to 270V For 100 110 115 120 VAC models you may choose the following selection for acceptable input voltage range 55 150 flashing in turns The acceptable input voltage range is from 55V to 150V 80 130 flashing in turns The acceptable input voltage range is from 80V to 130V 85 13...

Page 18: ...timizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode Rack When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the accep...

Page 19: ...o high 27 Bus unbalance 04 x Battery voltage too low 28 Bus short circuited 05 x Over temperature 41 x Inverter soft start fail 11 x Over load 43 Inverter voltage high 12 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Over Charge Sounding every second Site Fault Sounding every...

Page 20: ... icon and flashing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 and the icon is lighting on LCD ...

Page 21: ...CD display and alarm is continuously sounding A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the probl...

Page 22: ...dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months 1 2 hours Be sure to deliver the spent battery to a recycling facility or ship it to your dealer i...

Page 23: ... 97 BATTERY Battery Type 12V 9Ah Depending on application 12V 9Ah Depending on application Numbers 3 6 Typical Recharge Time 4 hours recover to 90 capacity for standard model only Charging Current max 1 A 1A 2A 4A 8A 1 A 1A 2A 4A 8A Charging Voltage 41 1 VDC 1 82 1VDC 1 INDICATORS LCD UPS status Load level Battery level Input Output battery info Discharge time and Fault indicators ALARM Battery Mo...

Reviews: